{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW4435-2BC46","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW4435-2BC46","canonicalUrl":"https://aoctrl.com/siemens/3RW4435-2BC46","factsUrl":"https://aoctrl.com/api/mcp/products/3RW4435-2BC46","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW4435-2BC46 soft starter, 232 A at 40°C, 230 V AC, 50/60 Hz, inside-delta circuit, adjustable current limitation, motor overload protection, screw fixing, 170 x 200 x 270 mm.","salesMarkdown":"## Rated current and thermal derating — the real continuous ceiling At 40°C ambient the 3RW4435-2BC46 is rated 232 A continuous. That drops to 203 A at 50°C and 173 A at 60°C. For a motor with a 200 A FLA at 40°C, this starter has headroom; at 50°C you're at the limit. The derating temperature is 40°C — above that, the thyristor junction temperature governs the continuous current, not the nameplate. ## Inside-delta wiring — cuts the line current by 58% This soft starter supports inside-delta circuit connection. In that configuration the thyristors sit inside the motor delta windings, so the line current is 1/√3 of the motor phase current. For a 232 A motor, the line contactor and cable only need to carry about 134 A. The main circuit connection accepts busbar or cable up to 250 kcmil, with stranded wire range 25–120 mm² and finely stranded 16–95 mm². ## Motor overload and device protection — one unit, no separate relay Motor overload protection is integrated — the starter's thermal model tracks I²t and trips on overload without an external relay. Intrinsic device protection guards the thyristors against overtemperature and phase loss. The adjustable current limitation lets you set the start current from 8% up to the rated value, matching the load inertia. Minimum load is 8% of rated current — below that the motor may not accelerate reliably. ## Mounting and panel fit — 170 x 200 x 270 mm, screw-fixed Fastening is screw fixing on a vertical mounting surface. The unit can be rotated ±90° and tilted ±22.5° front-to-back. Clearances: 100 mm above, 75 mm below, 5 mm at the sides. Dimensions are 170 mm wide, 200 mm high, 270 mm deep. That's a substantial footprint — plan the enclosure depth for cable bending radius on the 120 mm² terminals. ## Environmental and compliance — pollution degree 3, 60°C operation Pollution degree 3 per IEC 60947-4-2 means the starter is rated for conductive dust and condensation typical of industrial panels. Operating temperature range is up to 60°C; storage range is -25 to +80°C. Insulation voltage rated 690 V. The display shows fault signals and an external reset input is provided.","metaTitle":"Siemens 3RW4435-2BC46 SIRIUS Soft Starter, 232 A, 230 V","metaDescription":"Siemens 3RW4435-2BC46 SIRIUS soft starter, 232 A at 40°C, 230 V, 50/60 Hz. Active production.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"270 mm","Width":"170 mm","Height":"200 mm","Mounting":"screw fixing","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cc333cddce461eba26d8d5c5cede65b2.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=253858&mlfb=3RW4435-2BC46","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW4435-2BC46/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW4435-2BC46","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW4435-2BC46 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}