{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW4444-2BC46","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW4444-2BC46","canonicalUrl":"https://aoctrl.com/siemens/3RW4444-2BC46","factsUrl":"https://aoctrl.com/api/mcp/products/3RW4444-2BC46","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW4444-2BC46 soft starter, 433 A at 40 °C, 690 V insulation voltage, 50/60 Hz, inside-delta circuit, thyristor, screw fixing, 230 x 210 x 298 mm.","salesMarkdown":"## Continuous current and the derating that matters The 3RW4444-2BC46: That 40 °C figure is the baseline — in a closed panel with other heat sources, expect to budget for the 50 °C or 60 °C column unless you have forced ventilation. Insulation voltage rated 690 V, operating frequency 50…60 Hz. The 690 V ceiling means this unit handles 400 V line-to-line systems with margin; no voltage derating needed for standard 380–480 V grids. ## Inside-delta wiring and current limitation Supports inside-delta circuit configuration — the soft starter connects in the delta legs of a six-lead motor, reducing the line current the device carries relative to the motor full-load current. For a given motor, this lets a smaller-frame soft starter do the job. Adjustable current limitation lets you set the start current between 8% and 100% of the device rating. The 8% minimum load threshold means the thyristors may not fire reliably below that point — factor this into no-load commissioning or very light loads. ## Panel layout and wiring constraints Clearance requirements: 100 mm above, 75 mm below, 5 mm at the sides — these are for ventilation and arc-flash separation per IEC 60947-4-2. Main circuit accepts stranded 70…240 mm² or kcmil 2/0…500. Auxiliary connections take solid 0.25…1.5 mm². The main current circuit uses busbar connection — plan for busbar lugs, not cable lugs, on the power terminals. Dimensions 230 mm high, 210 mm wide, 298 mm deep. The depth is the largest envelope — ensure the enclosure depth accommodates the unit plus the 100 mm top clearance for cable bending and airflow. ## Protection and diagnostics built in Integrated motor overload protection eliminates the separate overload relay in many panels. Intrinsic device protection covers the soft starter itself against overtemperature and overcurrent. On-board display for fault signals — no external HMI needed for basic diagnostics. External reset input allows remote clearing of fault conditions. Pollution degree 3 per IEC 60947-4-2 — rated for industrial environments with conductive dust or occasional condensation. Storage temperature -25…+80 °C, operation up to 60 °C ambient.","metaTitle":"Siemens 3RW4444-2BC46 Soft Starter, 433 A, 690 V, SIRIUS","metaDescription":"Siemens 3RW4444-2BC46 SIRIUS soft starter, 433 A at 40°C, 690 V insulation, inside-delta capable, active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"298 mm","Width":"210 mm","Height":"230 mm","Mounting":"screw fixing","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/77fd6a75098c20d94592a6045a3ca756.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=531301&mlfb=3RW4444-2BC46","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW4444-2BC46/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW4444-2BC46","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW4444-2BC46 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}