{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW4446-2BC36","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW4446-2BC36","canonicalUrl":"https://aoctrl.com/siemens/3RW4446-2BC36","factsUrl":"https://aoctrl.com/api/mcp/products/3RW4446-2BC36","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW4446-2BC36 soft starter, 617 A at 40 °C, 690 V insulation voltage, pollution degree 3, inside-delta circuit capable, screw fixing, 298 mm depth.","salesMarkdown":"## Rated current and thermal derating — the real limit in a closed panel At 40 °C ambient the 3RW4446-2BC36 delivers 617 A continuous. If the panel ambient runs at 50 °C, the motor full-load current must stay below 546 A, not the 617 A headline figure. The derating temperature is 40 °C, meaning the unit is rated at that ambient without penalty. Above it, every degree costs current — budget the panel airflow accordingly. ## Mounting and integration into the panel Screw fixing — no DIN-rail clip. The unit mounts to a vertical surface and can be rotated ±90° or tilted ±22.5° front/back, giving flexibility in tight enclosures. Dimensions: 230 mm high, 210 mm wide, 298 mm deep. Clearance: 100 mm above, 75 mm below, 5 mm at the sides. Main circuit connection is via busbar or cable — stranded 70–240 mm², finely stranded 50–240 mm², or two 2/0–500 kcmil conductors per phase. The back clamping point accepts 250–500 kcmil; the front accepts 3/0–600 kcmil. Maximum motor cable length is 500 m — beyond that, voltage drop and reflected-wave effects on the thyristors need evaluation. ## Pollution degree and environmental limits Rated pollution degree 3 per IEC 60947-4-2 — suitable for industrial environments where conductive dust or occasional condensation occurs. Operating temperature range: -25 to +60 °C during operation; storage from -25 to +80 °C.","metaTitle":"Siemens 3RW4446-2BC36 SIRIUS Soft Starter, 617 A, 690 V","metaDescription":"Siemens 3RW4446-2BC36 SIRIUS soft starter, 617 A at 40°C, 690 V insulation, pollution degree 3. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"298 mm","Width":"210 mm","Height":"230 mm","Mounting":"screw fixing","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c8e4b89b3ddda2f1092da0dc38e987b3.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=51697&mlfb=3RW4446-2BC36","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW4446-2BC36/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW4446-2BC36","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW4446-2BC36 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}