{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW4447-2BC34","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW4447-2BC34","canonicalUrl":"https://aoctrl.com/siemens/3RW4447-2BC34","factsUrl":"https://aoctrl.com/api/mcp/products/3RW4447-2BC34","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW4447-2BC34 soft starter, 748 A at 40 °C, 690 V insulation voltage, 50/60 Hz, inside-delta circuit capable, screw fixing, IP20.","salesMarkdown":"## 748 A at 40 °C — what it means for your motor load The 3RW4447-2BC34: That 40 °C rating is the standard panel ambient — above that, derate per the curve. For a 400 V motor drawing 680 A FLA, this soft starter has headroom at 40 °C but needs the 50 °C derating checked if the panel runs hot. Insulation voltage is 690 V rated value, so it comfortably covers 400 V, 480 V, and 575 V systems with margin. The pollution degree 3 rating per IEC 60947-4-2 means it's designed for industrial environments where conductive dust or condensation is present — the creepage distances are sized accordingly. ## Inside-delta wiring — cuts phase current by 58% This soft starter supports inside-delta circuit configuration, which connects the thyristors inside the motor delta winding rather than in the supply lines. That drops the current per phase to 58% of the line current — a 748 A line-rated unit handles roughly 430 A per phase in inside-delta mode. The main current circuit uses busbar connection with clamping points accepting 2/0 to 500 kcmil. The dimensions are 230 mm high, 210 mm wide, 298 mm deep — that depth is the dimension to watch in shallow enclosures. Clearance requirements: 100 mm above, 75 mm below, 5 mm at the sides. ## Integral protection and adjustable starting Motor overload protection is built in — no separate overload relay needed. The adjustable current limitation lets you set the starting current between 2x and 5x the motor FLA, and the minimum load setting is 8% for light-load applications. Intrinsic device protection monitors the thyristors for over-temperature and short-circuit conditions. An external reset input and a display for fault signals are standard. Operating temperature during operation is 60 °C max; storage range is -25 to +80 °C.","metaTitle":"Siemens 3RW4447-2BC34 Soft Starter, 748 A, SIRIUS","metaDescription":"Siemens 3RW4447-2BC34 SIRIUS soft starter, 748 A at 40 °C, 690 V insulation, active production. Inside-delta capable, integral overload protection.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"298 mm","Width":"210 mm","Height":"230 mm","Mounting":"screw fixing","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1cde21fcc43271b7e3ecfa539a8ee3a1.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=124931&mlfb=3RW4447-2BC34","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW4447-2BC34/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW4447-2BC34","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW4447-2BC34 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}