{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW4455-2BC45","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW4455-2BC45","canonicalUrl":"https://aoctrl.com/siemens/3RW4455-2BC45","factsUrl":"https://aoctrl.com/api/mcp/products/3RW4455-2BC45","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW4455-2BC45 soft starter, 1200 A at 40 °C, 690 V insulation voltage, thyristor-based, integrated bypass contact system, screw fixing.","salesMarkdown":"## Sizing the 3RW4455-2BC45 for motor starting duty Insulation voltage is 690 V, certified to IEC 60947-4-2 with pollution degree 3 — the standard for industrial motor starting where conductive dust and condensation are present. The operating frequency covers 50... 60 Hz, so it lands on either line frequency without a configuration change. Thyristor-based switching with an integrated bypass contact system means the silicon handles the ramp-up, then the bypass contactor carries the full-load current continuously — the thyristors are only stressed during start/stop, not at steady state. Adjustable current limitation and motor overload protection are built in, so no separate overload relay is needed for the motor branch. ## Panel integration and clearance constraints Clearance requirements: 100 mm upwards, 75 mm downwards, and only 5 mm at the side — the side clearance is tight enough that adjacent components can sit nearly flush, but the vertical air path needs room for convection cooling. The derating curve assumes free air flow; stacking units without the vertical gap will push the operating temperature above the 60 °C ceiling. Main circuit wiring accepts stranded 70... 240 mm² or finely stranded 50... 240 mm², plus 2/0... 500 kcmil for North American builds. ## Lifecycle and compliance documentation The product carries pollution degree 3 per IEC 60947-4-2, which is the relevant product standard for soft starters. The insulation voltage rating of 690 V and the 50/60 Hz operating frequency are declared on the nameplate. For RoHS/REACH declarations, the manufacturer provides a declaration of conformity referenced to the SIRIUS series; request the current declaration at RFQ.","metaTitle":"Siemens 3RW4455-2BC45 SIRIUS Soft Starter, 1200 A, 690 V","metaDescription":"Siemens SIRIUS 3RW4455-2BC45 soft starter, 1200 A at 40 °C, 690 V insulation, integrated bypass, thyristor control. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"290 mm","Width":"510 mm","Height":"640 mm","Mounting":"screw fixing","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9b57ac51502c01c84201ab88baff598d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=456394&mlfb=3RW4455-2BC45","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW4455-2BC45/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW4455-2BC45","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW4455-2BC45 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}