{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW4455-2BC46","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW4455-2BC46","canonicalUrl":"https://aoctrl.com/siemens/3RW4455-2BC46","factsUrl":"https://aoctrl.com/api/mcp/products/3RW4455-2BC46","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW4455-2BC46 soft starter, 1200 A at 40 °C, 690 V insulation voltage, 50/60 Hz, integrated bypass contact system, inside-delta circuit, screw fixing, 640 x 510 x 290 mm.","salesMarkdown":"## Rated current and thermal derating The 3RW4455-2BC46: The derating temperature threshold is 40 °C — above that, the continuous current drops linearly. For a 50 °C panel ambient, budget the 1065 A figure as the usable rating. ## Integrated bypass and inside-delta topology Integrated bypass contact system means the thyristors are shorted out after start, eliminating heat dissipation in the power stack during run. Inside-delta circuit configuration reduces the current through each thyristor leg — the soft starter sees phase-to-phase voltage rather than line-to-neutral, which lowers the per-device current requirement for a given motor power. ## Protection and control features Motor overload protection, intrinsic device protection, and adjustable current limitation are all onboard. External reset input allows remote fault clearing. A display shows fault signals — no separate HMI needed for diagnostics. Motor brake output is included as a product component. ## Mounting and connection details Screw fixing to a vertical mounting surface; the unit can be rotated ±90° or tilted ±22.5° front/back. Main current circuit uses busbar connection; main wire range is 2/0–500 kcmil (stranded 70–240 mm², finely stranded 50–240 mm²). Pollution degree 3 per IEC 60947-4-2. ## Dimensions and clearances Height 640 mm, width 510 mm, depth 290 mm. Required clearance: 100 mm upwards, 75 mm downwards, 5 mm at the sides. Storage temperature range -25 to +80 °C; operating ambient max 60 °C. Maximum motor cable length 500 m.","metaTitle":"Siemens 3RW4455-2BC46 SIRIUS Soft Starter, 1200 A, 690 V","metaDescription":"Siemens 3RW4455-2BC46 SIRIUS soft starter, 1200 A at 40 °C, 690 V insulation, integrated bypass, inside-delta. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"290 mm","Width":"510 mm","Height":"640 mm","Mounting":"screw fixing","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9432ff87602c3a2ad1b7b257c4f6ed3f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=42642&mlfb=3RW4455-2BC46","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW4455-2BC46/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW4455-2BC46","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW4455-2BC46 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}