{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW4458-6BC34","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW4458-6BC34","canonicalUrl":"https://aoctrl.com/siemens/3RW4458-6BC34","factsUrl":"https://aoctrl.com/api/mcp/products/3RW4458-6BC34","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW4458-6BC34 soft starter, 1680 A at 40 °C, 690 V insulation voltage, integrated bypass contact system, inside-delta circuit capable, screw fixing.","salesMarkdown":"## Active production, current rating that drives the selection The 3RW4458-6BC34: Rated 1680 A at 40 °C, it handles heavy motor loads. Derate to 1472 A at 50 °C and 1316 A at 60 °C — the thermal ceiling is 60 °C during operation, so a panel with marginal airflow pushes the usable current down. The derating temperature threshold is 40 °C, meaning full rating only holds below that ambient. ## Bypass, inside-delta, and wiring constraints Integrated bypass contact system means the thyristors are shorted out once the motor is up to speed — no external bypass contactor needed, and the heat load on the panel drops after start. Inside-delta circuit connection is supported — this reduces the current through each thyristor leg to 58% of the line current, effectively extending the rating range for a given soft starter frame. Confirm the motor winding configuration before wiring. Main current circuit connection is busbar; the main conductor range accepts stranded 70–240 mm² and finely stranded 50–240 mm², or 2/0–500 kcmil. ## Mounting, clearance, and environmental fit Degree of pollution 3 per IEC 60947-4-2 — this is the industrial environment rating (conductive pollution or dry non-conductive pollution that becomes conductive due to condensation). No additional conformal coating required for typical factory-floor panels, but outdoor or washdown cabinets need a higher enclosure rating. Storage temperature range is -25 to +80 °C — the unit can sit in an unheated warehouse through most climates without damage. ## Protection, diagnostics, and commissioning notes Motor overload protection and intrinsic device protection (thyristor overtemperature, phase imbalance, etc.) are built in — no separate overload relay needed for most applications. Adjustable current limitation lets you set the start current between 8% and the rated value, which helps on weak supply networks or mechanically sensitive loads. Fault signal display is on the unit itself — a local readout shows the fault code without needing a connected HMI or PLC. External reset input allows remote clearing of latched faults from the control room. Maximum motor cable length is 500 m — beyond that, capacitive charging current from the cable can interfere with the thyristor gating. For long cable runs, consider an output reactor. A motor brake output is included as a component — useful for applications that need a DC injection brake after the soft starter ramps down.","metaTitle":"Siemens 3RW4458-6BC34 Soft Starter, 1680 A, SIRIUS","metaDescription":"Siemens 3RW4458-6BC34 SIRIUS soft starter rated 1680 A at 40 °C. Active production, integrated bypass, inside-delta capable. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":[],"specifications":{"Depth":"290 mm","Width":"510 mm","Height":"640 mm","Mounting":"screw fixing","Product Status":"Active"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a14d24391cac9522f1bdfe73bcc78f0b.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=203902&mlfb=3RW4458-6BC34","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW4458-6BC34/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW4458-6BC34","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW4458-6BC34 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}