{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5072-2AB15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5072-2AB15","canonicalUrl":"https://aoctrl.com/siemens/3RW5072-2AB15","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5072-2AB15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3RW5072-2AB15 soft starter, 200-600 VAC, 90 A minimum setting, Class 10A/10E/20E, ATEX/UKEX/IECEx, PROFIBUS/Modbus/EtherNet/IP, screw fixing, 160 x 230 x 282 mm.","salesMarkdown":"## Active production and hazardous-area approvals The 3RW5072-2AB15: CE and UL/CSA approvals are also present, covering European and North American regulatory jurisdictions. Rated 200 to 600 V, covering the common 208 V, 400 V, and 480 V industrial line voltages without a separate tap or transformer. The minimum settable motor current is 90 A, with a minimum load of 15 % relative to the smallest settable Ie — so it will not drop a lightly loaded motor into a hard start. Trip class is selectable between Class 10A (preset), 10E, and 20E per IEC 60947-4-2. Class 10A clears the start within 10 seconds at 7× Ie — this is the standard for most pump and fan starts. ## Fieldbus connectivity and soft-start algorithms Onboard PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP mean the starter talks directly to the PLC without an external gateway — the commissioning engineer maps the control word and status word into the drive profile, not a generic Modbus map. PROFIenergy is supported when used with the PROFINET communication module. Soft Torque, Voltage Ramp, and Pump Ramp Down are built in — no option card needed. The analog output defaults to 4-20 mA but can be parameterised to 0-10 V via the High Feature HMI. Auto-reset and remote reset (by cycling control supply voltage) are standard. ## Mounting and thermal derating Screw fixing to the back panel, not DIN rail — the 160 mm width × 230 mm height × 282 mm depth requires a dedicated mounting footprint. Clearance requirements: 100 mm upwards, 75 mm downwards, 10 mm forwards, 5 mm at the sides, 0 mm backwards — the minimum side gap is tight, but the top and bottom gaps must be respected for convection airflow. Shock resistance is 15 g / 11 ms, dropping to 12 g / 11 ms if contact lifting is a concern.","metaTitle":"Siemens 3RW5072-2AB15 Soft Starter, 200-600 V, ATEX","metaDescription":"Siemens 3RW5072-2AB15 soft starter, 200-600 VAC, ATEX/UKEX/IECEx approved, Class 10A/10E/20E per IEC 60947-4-2, PROFIBUS/Modbus/EtherNet/IP.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"282 mm","Width":"160 mm","Height":"230 mm","Mounting":"screw fixing","Trip Class":"CLASS 10 A / 10E (preset) / 20E; acc. to IEC 60947-4-2","Product Status":"Active","Service Factor":"1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/59c3f1c7cb5cf2b335a60fedc167965e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=830729&mlfb=3RW5072-2AB15","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW5072-2AB15/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5072-2AB15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5072-2AB15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}