{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5072-6AB15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5072-6AB15","canonicalUrl":"https://aoctrl.com/siemens/3RW5072-6AB15","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5072-6AB15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3RW5072-6AB15 soft starter, 90 A minimum rated current, 200-600 V operating voltage, Class 10A/10E/20E, ATEX, UKEX, IECEx, UL, CSA, 160 x 230 x 282 mm.","salesMarkdown":"## Trip class and motor protection The 3RW5072-6AB15: Trip class is selectable between CLASS 10A, 10E (preset), and 20E per IEC 60947-4-2. CLASS 10A suits standard induction motors with short acceleration times; CLASS 20E handles high-inertia loads like centrifuges or crushers where the start current must be sustained longer without nuisance tripping. The minimum load setting is 15 % of the smallest settable Ie, which allows the soft starter to protect lightly loaded motors without false overcurrent trips. A service factor of 1 means no built-in overload margin beyond the set current — the trip threshold matches the motor FLA exactly. ## Fieldbus and control integration Onboard fieldbus options include PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP, plus PROFIenergy support when paired with the PROFINET communication module. This lets the starter participate in energy-management schedules and coordinated start sequences without a separate gateway. The analog output is configurable as 4-20 mA or 0-10 V (default 4-20 mA), parameterizable via the High Feature HMI. Remote reset is achieved by cycling the control supply voltage — no separate reset signal needed. ## Mounting and thermal derating Dimensions are 160 mm wide, 230 mm high, and 282 mm deep, with screw fixing to the mounting plate. Clearance requirements: 100 mm upward, 75 mm downward, 10 mm forward, 5 mm sideways, and 0 mm backward — the back can sit flush against the panel backplate. In a sealed enclosure with multiple drives, plan for forced ventilation or a larger cabinet to stay below the derating threshold. ## Compliance and sourcing No direct cross-reference to the alternate MPNs listed in the catalog — verify panel wiring before substituting.","metaTitle":"Siemens 3RW5072-6AB15 Soft Starter, 90 A, 200-600 V, ATEX","metaDescription":"Siemens 3RW5072-6AB15 soft starter, 90 A min, 200-600 V, Class 10A/10E/20E. ATEX, UKEX, IECEx, UL, CSA. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"282 mm","Width":"160 mm","Height":"230 mm","Mounting":"screw fixing","Trip Class":"CLASS 10 A / 10E (preset) / 20E; acc. to IEC 60947-4-2","Product Status":"Active","Service Factor":"1","Digital Output Version":"2 normally-open contacts (NO) / 1 changeover contact (CO)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1a845196afa7b3bcb005390f0b085d41.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=830737&mlfb=3RW5072-6AB15","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW5072-6AB15/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5072-6AB15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5072-6AB15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}