{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5117-1XC14","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5117-1XC14","canonicalUrl":"https://aoctrl.com/siemens/3RW5117-1XC14","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5117-1XC14","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW5117-1XC14 soft starter, 15.5 A minimum, 200-480 V, Trip Class 10A/10E/20E, PROFIBUS, Modbus RTU, PROFINET, IP00/IP20 with terminal covers, screw fixing.","salesMarkdown":"## Trip class and motor protection — what the rating means The 3RW5117-1XC14 is a SIRIUS soft starter rated Trip Class 10A (default), 10E, or 20E per IEC 60947-4-2. Class 10A clears a locked-rotor condition within 10 seconds at 7.5× FLA — the standard choice for standard-start motors driving pumps, fans, and compressors where the load accelerates in under 10 seconds. Minimum settable current is 15.5 A, with a minimum load of 15 % relative to the smallest settable Ie. That means the soft starter can handle lightly loaded motors without nuisance tripping — useful on conveyors or agitators that run well below nameplate. ## Voltage range, control supply, and fieldbus Rated operating voltage is 200–480 V, covering common 208/230/400/460 V three-phase systems. Onboard PROFIBUS, Modbus RTU, and PROFINET standard — no option card required. The analog output is 4–20 mA (default) or 0–10 V, parameterizable via the High Feature HMI. This makes the 3RW5117-1XC14 a single-order-code solution for PLC-controlled lines that need current feedback for load monitoring. ## Mounting, clearances, and environmental limits Dimensions are 321 mm high, 185 mm wide, 203 mm deep — plan for the 100 mm clearance above and 75 mm below for airflow and cable entry. Side clearance is 5 mm; no clearance needed at the rear. IP00 as shipped; IP20 with the optional terminal covers for vertical touch protection from the front. Pollution degree 3 per IEC 60947-4-2, so the soft starter is rated for industrial environments with conductive dust or light moisture. ## Soft stop, inside-delta, and firmware update capability Ramp-down (soft stop) is standard — adjustable from 50 % stopping voltage, which reduces water hammer on pump lines and mechanical shock on conveyors. Voltage ramp start is also standard, with starting voltage adjustable from 30 to 100 %. Inside-delta circuit wiring is supported — this reduces the soft starter current rating to 58 % of the motor FLA, allowing a smaller unit on delta-connected motors. Firmware updates are field-loadable, and the unit logs errors in an onboard logbook for fault tracing.","metaTitle":"Siemens 3RW5117-1XC14 SIRIUS Soft Starter, 15.5 A min","metaDescription":"Siemens 3RW5117-1XC14 SIRIUS soft starter, active production. Trip Class 10A/10E/20E, 200-480 V, PROFIBUS/Modbus/PROFINET. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Soft Starters"],"specifications":{"Depth":"203 mm","Width":"185 mm","title":"3RW5117-1XC14","Height":"321 mm","Maximum":"5 000 m; Derating as of 1000 m, see catalog","Minimum":"15.5 A","Upwards":"100 mm","Forwards":"10 mm","PROFIBUS":"Yes","at 50 Hz":"110 ... 250 V","at 60 Hz":"110 ... 250 V","Backwards":"0 mm","Downwards":"75 mm","Modbus RTU":"Yes","Trip Class":"CLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2","auto-RESET":"Yes","At The Side":"5 mm","Rated Value":"200 ... 480 V","Soft Torque":"Yes","description":"SIRIUS soft starter 200-480 V 38 A, 110-250 V AC Screw terminals without bypass, Analog output","Remote Reset":"Yes; By turning off the control supply voltage","Voltage Ramp":"Yes","Analog Output":"Yes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High Feature HMI)","Error Logbook":"Yes","Service Factor":"1","Firmware Update":"Yes","lifecycle_stage":"current","During Operation":"-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above","Fastening Method":"screw fixing","Minimum Load [%]":"15 %; Relative to smallest settable Ie","Shock Resistance":"15 g / 11 ms, from 12 g / 11 ms with potential contact lifting","Mounting Position":"+/- 10° rotation possible and can be tilted forward or backward on vertical mounting surface","PROFINET standard":"Yes","Product Brand Name":"SIRIUS","Degree Of Pollution":"3, acc. to IEC 60947-4-2","For Control Circuit":"screw-type terminals","protection class IP":"IP00; IP20 with additional terminal covers for vertical touching from the front","Inside-Delta Circuit":"Yes","Starting Voltage [%]":"30 ... 100 %","Stopping Voltage [%]":"50 ... 50 %","Vibration Resistance":"15 mm to 6 Hz; 2g to 500 Hz","Ramp-Down (Soft Stop)":"Yes","at 40 °C rated value":"65.8 A","at 50 °C rated value":"58 A","at 60 °C rated value":"52.8 A","Communication Function":"Yes","Digital Output Version":"2 normally-open contacts (NO) / 1 changeover contact (CO)","Ramp-Up (Soft Starting)":"Yes","at 40 °C after startup":"12 W","at 50 °C after startup":"12 W","at 60 °C after startup":"12 W","For Main Current Circuit":"box terminal","Number Of Analog Outputs":"1","Number Of Digital Inputs":"1","Weight Without Packaging":"5.2 kg","at 40 °C during startup":"464 W","at 50 °C during startup":"399 W","at 60 °C during startup":"355 W","For Control Circuit Solid":"1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)","Motor Overload Protection":"Yes","Number Of Digital Outputs":"3","Via Software Configurable":"No","is supported HMI-Standard":"Yes","Impulse Voltage Rated Value":"6 kV","Intrinsic Device Protection":"Yes","Number Of Controlled Phases":"3","During Storage And Transport":"-40 ... +80 °C","Via Software Parameterizable":"No","at DC-13 at 24 V rated value":"1 A","Adjustable Current Limitation":"Yes","Electromagnetic Compatibility":"acc. to IEC 60947-4-2","at AC-15 at 250 V rated value":"3 A","is supported HMI-High Feature":"Yes","of standard HMI module usable":"3RW5980-0HS00","Ramp-Down Time Of Soft Starter":"0 ... 20 s","at 230 V at 40 °C rated value":"11 kW","at 400 V at 40 °C rated value":"18.5 kW","At Inside-Delta Circuit Minimum":"26.8 A","Width Of Connection Bar Maximum":"25 mm","Control Supply Voltage Frequency":"50 ... 60 Hz","Operating Measured Value Display":"Yes; with optional HMI","during storage acc. to IEC 60721":"1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4","Operating frequency 1 rated value":"50 Hz","Operating frequency 2 rated value":"60 Hz","of high feature HMI module usable":"3RW5980-0HF00","of the gG fuse usable up to 690 V":"3NA3824-6; Type of coordination 1, Iq = 65 kA","Between Main And Auxiliary Circuit":"480 V","Start-Up Ramp Time Of Soft Starter":"0 ... 20 s","during operation acc. to IEC 60721":"3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6","during transport acc. to IEC 60721":"2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)","of circuit breaker usable at 400 V":"3RV2032-4WA10; Type of coordination 1, Iq = 65 kA, CLASS 10","of circuit breaker usable at 500 V":"3RV2032-4WA10; Type of coordination 1, Iq = 10 kA, CLASS 10","reference code acc. to IEC 81346-2":"Q","At Inside-Delta Circuit Rated Value":"200 ... 480 V","at the digital inputs at AC maximum":"100 m","Design Of The Overvoltage Protection":"Varistor","Surge Voltage Resistance Rated Value":"6 kV","Current Limiting Value [%] Adjustable":"130 ... 700 %","Between Soft Starter And Motor Maximum":"800 m","Removable Terminal For Control Circuit":"Yes","of communication module PROFIBUS usable":"3RW5980-0CP00","Blocking Voltage Of The Thyristor Maximum":"1 400 V","of communication module Modbus RTU usable":"3RW5980-0CR00","utilization category acc. to IEC 60947-4-2":"AC-53b","For Main Contacts With Screw-Type Terminals":"40 ... 53 lbf·in","At Rotary Coding Switch On Switch Position 1":"15.5 A","At Rotary Coding Switch On Switch Position 2":"17 A","At Rotary Coding Switch On Switch Position 3":"18.5 A","At Rotary Coding Switch On Switch Position 4":"20 A","At Rotary Coding Switch On Switch Position 5":"21.5 A","At Rotary Coding Switch On Switch Position 6":"23 A","At Rotary Coding Switch On Switch Position 7":"24.5 A","At Rotary Coding Switch On Switch Position 8":"26 A","At Rotary Coding Switch On Switch Position 9":"27.5 A","At Rotary Coding Switch On Switch Position 10":"29 A","At Rotary Coding Switch On Switch Position 11":"30.5 A","At Rotary Coding Switch On Switch Position 12":"32 A","At Rotary Coding Switch On Switch Position 13":"33.5 A","At Rotary Coding Switch On Switch Position 14":"35 A","At Rotary Coding Switch On Switch Position 15":"36.5 A","At Rotary Coding Switch On Switch Position 16":"38 A","Number Of Digital Outputs Not Parameterizable":"2","Type Of Voltage Of The Control Supply Voltage":"AC","Product Feature Integrated Bypass Contact System":"No","of communication module PROFINET standard usable":"3RW5980-0CS00","Control Supply Current In Standby Mode Rated Value":"30 mA","Relative Negative Tolerance Of The Operating Voltage":"-15 %","Relative Positive Tolerance Of The Operating Voltage":"10 %","Design Of Short-Circuit Protection For Control Circuit":"4 A gG fuse (Icu=1 kA), 6 A quick-acting fuse (Icu=1 kA), C1 miniature circuit breaker (Icu= 600 A), C6 miniature circuit breaker (Icu= 300 A); Is not part of scope of supply","Relative Negative Tolerance Of The Operating Frequency":"-10 %","Relative Positive Tolerance Of The Operating Frequency":"10 %","of the gG fuse usable at inside-delta circuit up to 500 V":"3NA3824-6; Type of coordination 1, Iq = 65 kA","of circuit breaker usable at 400 V at inside-delta circuit":"3RV2032-4RA10; Type of coordination 1, Iq = 65 kA, CLASS 10","of circuit breaker usable at 500 V at inside-delta circuit":"3RV2032-4RA10; Type of coordination 1, Iq = 10 kA, CLASS 10","For Auxiliary And Control Contacts With Screw-Type Terminals":"7 ... 10.3 lbf·in","For Control Circuit Finely Stranded With Core End Processing":"1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)","For Main Contacts For Box Terminal Using Both Clamping Points Solid":"2x (2.5 ... 16 mm²)","Relative Negative Tolerance Of The Control Supply Voltage Frequency":"-10 %","Relative Positive Tolerance Of The Control Supply Voltage Frequency":"10 %","Inrush Current Peak At Application Of Control Supply Voltage Maximum":"12.2 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 1":"26.8 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 2":"29.4 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 3":"32 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 4":"34.6 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 5":"37.2 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 6":"39.8 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 7":"42.4 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 8":"45 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 9":"47.6 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 10":"50.2 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 11":"52.8 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 12":"55.4 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 13":"58 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 14":"60.6 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 15":"63.2 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 16":"65.8 A","For Main Contacts For Box Terminal Using Both Clamping Points Stranded":"2x (6 ... 16 mm²), 2x (10 ... 50 mm²)","For Main Contacts For Box Terminal Using The Back Clamping Point Solid":"1x (2.5 ... 16 mm²)","of back-up R fuse link for semiconductor protection usable up to 690 V":"3NE8024-1; Type of coordination 2, (soft starter in conjunction with the associated protective device circuit breaker/fuse), Iq = 65 kA","For Main Contacts For Box Terminal Using The Front Clamping Point Solid":"1x (2.5 ... 16 mm²)","Duration Of Inrush Current Peak At Application Of Control Supply Voltage":"2.2 ms","relative negative tolerance of the control supply voltage at AC at 50 Hz":"-15 %","relative negative tolerance of the control supply voltage at AC at 60 Hz":"-15 %","relative positive tolerance of the control supply voltage at AC at 50 Hz":"10 %","relative positive tolerance of the control supply voltage at AC at 60 Hz":"10 %","For Main Contacts For Box Terminal Using The Back Clamping Point Stranded":"1x (10 ... 70 mm²)","of full range R fuse link for semiconductor protection usable up to 690 V":"3NE1021-2; Type of coordination 2, Iq = 65 kA","For Main Contacts For Box Terminal Using The Front Clamping Point Stranded":"1x (10 ... 70 mm²)","Relative Negative Tolerance Of The Operating Voltage At Inside-Delta Circuit":"-15 %","Relative Positive Tolerance Of The Operating Voltage At Inside-Delta Circuit":"10 %","For Main Contacts For Box Terminal Using Both Clamping Points Finely Stranded With Core End Processing":"2x (2.5 ... 35 mm²)","For Main Contacts For Box Terminal Using The Back Clamping Point Finely Stranded With Core End Processing":"1x (2.5 ... 50 mm²)","For Main Contacts For Box Terminal Using The Front Clamping Point Finely Stranded With Core End Processing":"1x (2.5 ... 50 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d7f660fb586922f4ed35ba1dbc943210.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=830826&mlfb=3RW5117-1XC14"},"ai":{"faq":[{"question":"What is the 3RW5117-1XC14 used for?","answer":"It is a SIRIUS soft starter for three-phase induction motors, providing reduced-voltage starting with adjustable ramp and soft stop. Typical applications include pumps, fans, compressors, and conveyors where mechanical shock and inrush current need to be limited."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5117-1XC14","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5117-1XC14 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}