{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5213-1TC15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5213-1TC15","canonicalUrl":"https://aoctrl.com/siemens/3RW5213-1TC15","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5213-1TC15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3RW5213-1TC15 soft starter, 200-600 V rated voltage, 5.5 A minimum, Class 10A/10E/20E trip class per IEC 60947-4-2, PROFIBUS/Modbus/PROFINET/EtherNet/IP, UL/CSA/CE.","salesMarkdown":"## Motor starting profile and trip class The 3RW5213-1TC15 is a Siemens soft starter rated for 200-600 V supply, with a minimum settable current of 5.5 A. Its trip class defaults to CLASS 10A per IEC 60947-4-2, but can be configured to 10E or 20E — meaning you can match the thermal overload curve to the motor's acceleration time: 10A for standard starts under 10 seconds, 20E for longer ramp-ups like conveyors or crushers. The soft torque feature and pump ramp down function are built in — the ramp down reduces pressure surges in pumping systems by extending the deceleration profile, while soft torque limits inrush on high-inertia loads without oversizing the starter. ## Fieldbus and control integration This unit ships with PROFIBUS onboard, plus support for Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard — you can drop it into a Siemens S7 environment or a Rockwell plant-floor network without a separate gateway module. PROFIenergy is supported when used with the PROFINET communication module, allowing energy management profiles during idle periods. Firmware updates are field-loadable, and an error logbook is accessible with the optional accessory. Remote reset is handled by cycling the control supply voltage — no physical button press needed for automated restart sequences. ## Mounting and environmental limits The 3RW5213-1TC15 measures 170 mm wide, 275 mm high, and 152 mm deep — screw-fixing mount, with a +/-10° rotation allowance on a vertical surface. Clearance requirements: 100 mm upwards, 75 mm downwards, 10 mm forwards, 5 mm at the sides, 0 mm backwards. That backwards zero means it can sit flush against a backplate, saving panel depth. Shock rated at 15 g / 11 ms, with potential contact lifting noted at 12 g / 11 ms. ## Terminal wiring and approvals Power terminals accept solid wire: 2x (1.0-2.5 mm²) and 2x (2.5-10 mm²) — covers standard motor cable sizes up to 10 mm². UL and CSA approved, CE marked — the compliance documentation covers the major North American and European jurisdictions without extra certification legwork.","metaTitle":"Siemens 3RW5213-1TC15 Soft Starter, 200-600 V, Class 10A","metaDescription":"Siemens 3RW5213-1TC15 soft starter, 200-600 V, Class 10A/10E/20E trip class. Active production, sourced to order. UL/CSA/CE.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Soft Starters"],"specifications":{"Depth":"152 mm","Solid":"2x (1.0 ... 2.5 mm²), 2x (2.5 ... 10 mm²)","Width":"170 mm","title":"3RW5213-1TC15","Height":"275 mm","Minimum":"5.5 A","Upwards":"100 mm","Forwards":"10 mm","PROFIBUS":"Yes","at 50 Hz":"110 ... 250 V","at 60 Hz":"110 ... 250 V","Backwards":"0 mm","Downwards":"75 mm","CE marking":"Yes","Modbus RTU":"Yes","Modbus TCP":"Yes","Trip Class":"CLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2","auto-RESET":"Yes","At The Side":"5 mm","EtherNet/IP":"Yes","PROFIenergy":"Yes; in connection with the PROFINET Standard communication module","Rated Value":"200 ... 600 V","Soft Torque":"Yes","UL approval":"Yes","description":"SIRIUS soft starter 200-600 V 13 A, 110-250 V AC Screw terminals Thermistor input","CSA approval":"Yes","Remote Reset":"Yes; By turning off the control supply voltage","Analog Output":"No","Error Logbook":"Yes; Only in conjunction with special accessories","Pump Ramp Down":"Yes","Service Factor":"1","Torque Control":"No","Firmware Update":"Yes","lifecycle_stage":"current","During Operation":"-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above","Fastening Method":"screw fixing","HMI-High Feature":"No","Minimum Load [%]":"15 %; Relative to smallest settable Ie","Product Category":"Hybrid switching devices","Shock Resistance":"15 g / 11 ms, from 12 g / 11 ms with potential contact lifting","Mounting Position":"+/- 10° rotation possible and can be tilted forward or backward on vertical mounting surface","PROFINET standard":"Yes","Product Brand Name":"SIRIUS","Degree Of Pollution":"3, acc. to IEC 60947-4-2","For Control Circuit":"screw-type terminals","Not Parameterizable":"2","Product Designation":"Soft starter","Inside-Delta Circuit":"Yes","Starting Voltage [%]":"30 ... 100 %","Stopping Voltage [%]":"50 %; non-adjustable","Vibration Resistance":"15 mm to 6 Hz; 2g to 500 Hz","Ramp-Down (Soft Stop)":"Yes","at 40 °C rated value":"22.5 A","at 50 °C rated value":"19.9 A","at 60 °C rated value":"18.2 A","Communication Function":"Yes","Digital Output Version":"2 normally-open contacts (NO) / 1 changeover contact (CO)","Ramp-Up (Soft Starting)":"Yes","at 40 °C after startup":"16 W","at 50 °C after startup":"15 W","at 60 °C after startup":"15 W","EMC emitted interference":"acc. to IEC 60947-4-2: Class A","For Main Current Circuit":"screw-type terminals","Number Of Analog Outputs":"0","Number Of Digital Inputs":"1","Weight Without Packaging":"2.1 kg","at 40 °C during startup":"210 W","at 50 °C during startup":"178 W","at 60 °C during startup":"161 W","For Control Circuit Solid":"1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)","Motor Overload Protection":"Yes; Full motor protection (thermistor motor protection and electronic motor overload protection)","Number Of Digital Outputs":"3","Via Software Configurable":"Yes","is supported HMI-Standard":"Yes","Impulse Voltage Rated Value":"6 kV","Intrinsic Device Protection":"Yes","Number Of Controlled Phases":"3","During Storage And Transport":"-40 ... +80 °C","Via Software Parameterizable":"No","at DC-13 at 24 V rated value":"1 A","Adjustable Current Limitation":"Yes","Electromagnetic Compatibility":"in accordance with IEC 60947-4-2","Substance Prohibitance (Date)":"02/15/2018","at AC-15 at 250 V rated value":"3 A","is supported HMI-High Feature":"Yes","of standard HMI module usable":"3RW5980-0HS00","Insulation Voltage Rated Value":"600 V","at 230 V at 40 °C rated value":"3 kW","at 400 V at 40 °C rated value":"5.5 kW","at 500 V at 40 °C rated value":"7.5 kW","At Inside-Delta Circuit Minimum":"9.5 A","Control Supply Voltage Frequency":"50 ... 60 Hz","Operating Measured Value Display":"Yes; Only in conjunction with special accessories","Operating frequency 1 rated value":"50 Hz","Operating frequency 2 rated value":"60 Hz","of high feature HMI module usable":"3RW5980-0HF00","of the gG fuse usable up to 690 V":"3NA3820-6; Type of coordination 1, Iq = 65 kA","Between Main And Auxiliary Circuit":"600 V","Start-Up Ramp Time Of Soft Starter":"0 ... 20 s","at 200/208 V at 50 °C rated value":"2 hp","at 220/230 V at 50 °C rated value":"3 hp","at 460/480 V at 50 °C rated value":"7.5 hp","at 575/600 V at 50 °C rated value":"10 hp","of circuit breaker usable at 400 V":"3RV2032-4TA10; Type of coordination 1, Iq = 65 kA, CLASS 10","of circuit breaker usable at 500 V":"3RV2032-4TA10; Type of coordination 1, Iq = 18 kA, CLASS 10","At Inside-Delta Circuit Rated Value":"200 ... 600 V","at the digital inputs at AC maximum":"100 m","of communication module Ethernet/IP":"3RW5980-0CE00","Design Of The Overvoltage Protection":"Varistor","Surge Voltage Resistance Rated Value":"6 kV","Current Limiting Value [%] Adjustable":"130 ... 700 %","during storage according to IEC 60721":"1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4","Between Soft Starter And Motor Maximum":"800 m","Removable Terminal For Control Circuit":"Yes","at AWG cables for control circuit solid":"1x (20 ... 12), 2x (20 ... 14)","during operation according to IEC 60721":"3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6","during transport according to IEC 60721":"2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)","of communication module PROFIBUS usable":"3RW5980-0CP00","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (1.0 ... 2.5 mm²), 2x (2.5 ... 6.0 mm²)","Blocking Voltage Of The Thyristor Maximum":"1 600 V","Evaluation Of Thermistor Motor Protection":"Yes; Type A PTC or Klixon / Thermoclick","of communication module Modbus RTU usable":"3RW5980-0CR00","of communication module Modbus TCP usable":"3RW5980-0CT00","For Main Contacts With Screw-Type Terminals":"18 ... 22 lbf·in","At Rotary Coding Switch On Switch Position 1":"5.5 A","At Rotary Coding Switch On Switch Position 2":"6 A","At Rotary Coding Switch On Switch Position 3":"6.5 A","At Rotary Coding Switch On Switch Position 4":"7 A","At Rotary Coding Switch On Switch Position 5":"7.5 A","At Rotary Coding Switch On Switch Position 6":"8 A","At Rotary Coding Switch On Switch Position 7":"8.5 A","At Rotary Coding Switch On Switch Position 8":"9 A","At Rotary Coding Switch On Switch Position 9":"9.5 A","at AWG cables for main current circuit solid":"2x (16 ... 12), 2x (14 ... 8)","At Rotary Coding Switch On Switch Position 10":"10 A","At Rotary Coding Switch On Switch Position 11":"10.5 A","At Rotary Coding Switch On Switch Position 12":"11 A","At Rotary Coding Switch On Switch Position 13":"11.5 A","At Rotary Coding Switch On Switch Position 14":"12 A","At Rotary Coding Switch On Switch Position 15":"12.5 A","At Rotary Coding Switch On Switch Position 16":"13 A","Type Of Voltage Of The Control Supply Voltage":"AC","With Conductor Cross-Section = 0.5 Mm2 Maximum":"50 m","With Conductor Cross-Section = 1.5 Mm2 Maximum":"150 m","With Conductor Cross-Section = 2.5 Mm2 Maximum":"250 m","Holding Current In Bypass Operation Rated Value":"75 mA","utilization category according to IEC 60947-4-2":"AC 53a","Product Feature Integrated Bypass Contact System":"Yes","of communication module PROFINET standard usable":"3RW5980-0CS00","Control Supply Current In Standby Mode Rated Value":"30 mA","Relative Negative Tolerance Of The Operating Voltage":"-15 %","Relative Positive Tolerance Of The Operating Voltage":"10 %","contact rating of auxiliary contacts according to UL":"R300-B300","Design Of Short-Circuit Protection For Control Circuit":"4 A gG fuse (Icu=1 kA), 6 A quick-acting fuse (Icu=1 kA), C1 miniature circuit breaker (Icu= 600 A), C6 miniature circuit breaker (Icu= 300 A); Is not part of scope of supply","Relative Negative Tolerance Of The Operating Frequency":"-10 %","Relative Positive Tolerance Of The Operating Frequency":"10 %","Installation Altitude At Height Above Sea Level Maximum":"5 000 m; Derating as of 1000 m, see catalog","Locked-Rotor Current At Close Of Bypass Contact Maximum":"0.17 A","of the gG fuse usable at inside-delta circuit up to 500 V":"3NA3820-6; Type of coordination 1, Iq = 65 kA","of circuit breaker usable at 400 V at inside-delta circuit":"3RV2032-4DA10; Type of coordination 1, Iq = 65 kA, CLASS 10","of circuit breaker usable at 500 V at inside-delta circuit":"3RV2032-4DA10; Type of coordination 1, Iq = 18 kA, CLASS 10","For Auxiliary And Control Contacts With Screw-Type Terminals":"7 ... 10.3 lbf·in","For Control Circuit Finely Stranded With Core End Processing":"1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)","Relative Negative Tolerance Of The Control Supply Voltage Frequency":"-10 %","Relative Positive Tolerance Of The Control Supply Voltage Frequency":"10 %","Inrush Current Peak At Application Of Control Supply Voltage Maximum":"12.2 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 1":"9.5 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 2":"10.4 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 3":"11.3 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 4":"12.1 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 5":"13 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 6":"13.9 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 7":"14.7 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 8":"15.6 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 9":"16.5 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 10":"17.3 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 11":"18.2 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 12":"19.1 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 13":"19.9 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 14":"20.8 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 15":"21.7 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 16":"22.5 A","of back-up R fuse link for semiconductor protection usable up to 690 V":"3NE8017-1; Type of coordination 2, Iq = 65 kA","Duration Of Inrush Current Peak At Application Of Control Supply Voltage":"2.2 ms","relative negative tolerance of the control supply voltage at AC at 50 Hz":"-15 %","relative negative tolerance of the control supply voltage at AC at 60 Hz":"-15 %","relative positive tolerance of the control supply voltage at AC at 50 Hz":"10 %","relative positive tolerance of the control supply voltage at AC at 60 Hz":"10 %","of full range R fuse link for semiconductor protection usable up to 690 V":"3NE1815-0; Type of coordination 2, Iq = 65 kA","Relative Negative Tolerance Of The Operating Voltage At Inside-Delta Circuit":"-15 %","Relative Positive Tolerance Of The Operating Voltage At Inside-Delta Circuit":"10 %"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ba768e4d8c20170720b650f440217f7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=830847&mlfb=3RW5213-1TC15"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5213-1TC15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5213-1TC15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}