{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5213-3AC04","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5213-3AC04","canonicalUrl":"https://aoctrl.com/siemens/3RW5213-3AC04","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5213-3AC04","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW5213-3AC04 soft starter, 200-480 V rated voltage, minimum 5.5 A, Trip Class 10A/10E/20E per IEC 60947-4-2, PROFIBUS/Modbus RTU/Modbus TCP/EtherNet/IP/PROFINET, screw fixing, 275 x 170 x 152 mm.","salesMarkdown":"## Trip class and motor protection logic The 3RW5213-3AC04 is configured with Trip Class 10A as default, with selectable 10E and 20E classes per IEC 60947-4-2 — this determines the thermal overload curve the soft starter follows during a stall or jam condition. A minimum load threshold of 15 % relative to the smallest settable Ie means the soft starter will not attempt to regulate below that floor — useful when the downstream motor is oversized relative to the actual pump or fan load. ## Supply voltage and ambient derating Rated supply voltage spans 200 to 480 V AC, covering common 230/400/480 V industrial feeds without a tap-change transformer. The control supply is 24 V DC, which keeps the logic isolated from the power stage and allows a standard 24 V control transformer or UPS-backed bus to hold the soft starter in a known state during a voltage dip. ## Fieldbus and communications integration This SIRIUS soft starter carries PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard interfaces natively — no separate gateway module needed for most plant-floor networks. PROFIenergy is supported in connection with the PROFINET Standard communication module, which allows the drive to shed load during production pauses without cycling the main contactor. The analog output is configurable as 4-20 mA (default) or 0-10 V via the High Feature HMI, giving the DCS or PLC a real-time current or torque signal without a separate transducer. ## Mechanical footprint and panel clearances Dimensions are 275 mm height, 170 mm width, 152 mm depth — screw fixing to the back panel, not DIN rail, so the mounting plate must be drilled for the fixing centres. Required clearances: 100 mm upwards, 75 mm downwards, 10 mm forwards, 5 mm at the side, 0 mm backwards — the zero rear clearance means it can sit flush against the back panel, saving depth in a shallow enclosure. ## Approvals and compliance documentation CE marking, UL approval, and CSA approval are all confirmed on the record — the unit carries the marks needed for North American and European panel certification without a separate component-level review.","metaTitle":"Siemens 3RW5213-3AC04 SIRIUS Soft Starter, 200-480 V","metaDescription":"Siemens 3RW5213-3AC04 SIRIUS soft starter, rated 200-480 V, minimum 5.5 A, Trip Class 10A/10E/20E per IEC 60947-4-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Soft Starters"],"specifications":{"Depth":"152 mm","Solid":"2x (1.0 ... 2.5 mm²), 2x (2.5 ... 10 mm²)","Width":"170 mm","title":"3RW5213-3AC04","Height":"275 mm","Minimum":"5.5 A","Upwards":"100 mm","Forwards":"10 mm","PROFIBUS":"Yes","Backwards":"0 mm","Downwards":"75 mm","CE marking":"Yes","Modbus RTU":"Yes","Modbus TCP":"Yes","Trip Class":"CLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2","auto-RESET":"Yes","At The Side":"5 mm","EtherNet/IP":"Yes","PROFIenergy":"Yes; in connection with the PROFINET Standard communication module","Rated Value":"200 ... 480 V","Soft Torque":"Yes","UL approval":"Yes","description":"SIRIUS soft starter 200-480 V 13 A, 24 V AC/DC spring-type terminals Analog output","CSA approval":"Yes","Remote Reset":"Yes; By turning off the control supply voltage","Analog Output":"Yes; 4 ... 20 mA (default) / 0 ... 10 V (parameterizable with High Feature HMI)","Error Logbook":"Yes; Only in conjunction with special accessories","Pump Ramp Down":"Yes","Service Factor":"1","Torque Control":"No","Firmware Update":"Yes","lifecycle_stage":"current","During Operation":"-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above","Fastening Method":"screw fixing","HMI-High Feature":"No","Minimum Load [%]":"15 %; Relative to smallest settable Ie","Product Category":"Hybrid switching devices","Shock Resistance":"15 g / 11 ms, from 12 g / 11 ms with potential contact lifting","Mounting Position":"+/- 10° rotation possible and can be tilted forward or backward on vertical mounting surface","PROFINET standard":"Yes","at DC rated value":"24 V","Product Brand Name":"SIRIUS","Degree Of Pollution":"3, acc. to IEC 60947-4-2","For Control Circuit":"spring-loaded terminals","Not Parameterizable":"2","Product Designation":"Soft starter","Inside-Delta Circuit":"Yes","Starting Voltage [%]":"30 ... 100 %","Stopping Voltage [%]":"50 %; non-adjustable","Vibration Resistance":"15 mm to 6 Hz; 2g to 500 Hz","at 50 Hz rated value":"24 V","at 60 Hz rated value":"24 V","Ramp-Down (Soft Stop)":"Yes","at 40 °C rated value":"22.5 A","at 50 °C rated value":"19.9 A","at 60 °C rated value":"18.2 A","Communication Function":"Yes","Digital Output Version":"2 normally-open contacts (NO) / 1 changeover contact (CO)","Ramp-Up (Soft Starting)":"Yes","at 40 °C after startup":"16 W","at 50 °C after startup":"15 W","at 60 °C after startup":"15 W","EMC emitted interference":"acc. to IEC 60947-4-2: Class A","For Main Current Circuit":"screw-type terminals","Number Of Analog Outputs":"1","Number Of Digital Inputs":"1","Weight Without Packaging":"2.1 kg","at 40 °C during startup":"210 W","at 50 °C during startup":"178 W","at 60 °C during startup":"161 W","For Control Circuit Solid":"2x (0.25 ... 1.5 mm²)","Motor Overload Protection":"Yes; Electronic motor overload protection","Number Of Digital Outputs":"3","Via Software Configurable":"Yes","is supported HMI-Standard":"Yes","Impulse Voltage Rated Value":"6 kV","Intrinsic Device Protection":"Yes","Number Of Controlled Phases":"3","During Storage And Transport":"-40 ... +80 °C","Via Software Parameterizable":"No","at DC-13 at 24 V rated value":"1 A","Adjustable Current Limitation":"Yes","Electromagnetic Compatibility":"in accordance with IEC 60947-4-2","Substance Prohibitance (Date)":"02/15/2018","at AC-15 at 250 V rated value":"3 A","is supported HMI-High Feature":"Yes","of standard HMI module usable":"3RW5980-0HS00","Insulation Voltage Rated Value":"600 V","at 230 V at 40 °C rated value":"3 kW","at 400 V at 40 °C rated value":"5.5 kW","At Inside-Delta Circuit Minimum":"9.5 A","Control Supply Voltage Frequency":"50 ... 60 Hz","Operating Measured Value Display":"Yes; Only in conjunction with special accessories","Operating frequency 1 rated value":"50 Hz","Operating frequency 2 rated value":"60 Hz","of high feature HMI module usable":"3RW5980-0HF00","of the gG fuse usable up to 690 V":"3NA3820-6 ; Type of coordination 1, Iq = 65 kA","Between Main And Auxiliary Circuit":"600 V","Start-Up Ramp Time Of Soft Starter":"0 ... 20 s","at 200/208 V at 50 °C rated value":"2 hp","at 220/230 V at 50 °C rated value":"3 hp","at 460/480 V at 50 °C rated value":"7.5 hp","of circuit breaker usable at 400 V":"3RV2032-4TA10 ; Type of coordination 1, Iq = 65 kA, CLASS 10","of circuit breaker usable at 500 V":"3RV2032-4TA10 ; Type of coordination 1, Iq = 18 kA, CLASS 10","At Inside-Delta Circuit Rated Value":"200 ... 480 V","at the digital inputs at AC maximum":"100 m","at the digital inputs at DC maximum":"1 000 m","of communication module Ethernet/IP":"3RW5980-0CE00","Design Of The Overvoltage Protection":"Varistor","Surge Voltage Resistance Rated Value":"6 kV","Current Limiting Value [%] Adjustable":"130 ... 700 %","during storage according to IEC 60721":"1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4","Between Soft Starter And Motor Maximum":"800 m","Removable Terminal For Control Circuit":"Yes","at AWG cables for control circuit solid":"2x (24 ... 16)","during operation according to IEC 60721":"3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6","during transport according to IEC 60721":"2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)","of communication module PROFIBUS usable":"3RW5980-0CP00","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (1.0 ... 2.5 mm²), 2x (2.5 ... 6.0 mm²)","Blocking Voltage Of The Thyristor Maximum":"1 600 V","Evaluation Of Thermistor Motor Protection":"No","of communication module Modbus RTU usable":"3RW5980-0CR00","of communication module Modbus TCP usable":"3RW5980-0CT00","For Main Contacts With Screw-Type Terminals":"18 ... 22 lbf·in","At Rotary Coding Switch On Switch Position 1":"5.5 A","At Rotary Coding Switch On Switch Position 2":"6 A","At Rotary Coding Switch On Switch Position 3":"6.5 A","At Rotary Coding Switch On Switch Position 4":"7 A","At Rotary Coding Switch On Switch Position 5":"7.5 A","At Rotary Coding Switch On Switch Position 6":"8 A","At Rotary Coding Switch On Switch Position 7":"8.5 A","At Rotary Coding Switch On Switch Position 8":"9 A","At Rotary Coding Switch On Switch Position 9":"9.5 A","at AWG cables for main current circuit solid":"2x (16 ... 12), 2x (14 ... 8)","At Rotary Coding Switch On Switch Position 10":"10 A","At Rotary Coding Switch On Switch Position 11":"10.5 A","At Rotary Coding Switch On Switch Position 12":"11 A","At Rotary Coding Switch On Switch Position 13":"11.5 A","At Rotary Coding Switch On Switch Position 14":"12 A","At Rotary Coding Switch On Switch Position 15":"12.5 A","At Rotary Coding Switch On Switch Position 16":"13 A","Type Of Voltage Of The Control Supply Voltage":"AC/DC","Holding Current In Bypass Operation Rated Value":"360 mA","utilization category according to IEC 60947-4-2":"AC 53a","Product Feature Integrated Bypass Contact System":"Yes","of communication module PROFINET standard usable":"3RW5980-0CS00","Control Supply Current In Standby Mode Rated Value":"160 mA","Relative Negative Tolerance Of The Operating Voltage":"-15 %","Relative Positive Tolerance Of The Operating Voltage":"10 %","contact rating of auxiliary contacts according to UL":"R300-B300","Inrush Current By Closing The Bypass Contacts Maximum":"0.75 A","Design Of Short-Circuit Protection For Control Circuit":"4 A gG fuse (Icu=1 kA), 6 A quick-acting fuse (Icu=1 kA), C1 miniature circuit breaker (Icu= 600 A), C6 miniature circuit breaker (Icu= 300 A); Is not part of scope of supply","Relative Negative Tolerance Of The Operating Frequency":"-10 %","Relative Positive Tolerance Of The Operating Frequency":"10 %","Installation Altitude At Height Above Sea Level Maximum":"5 000 m; Derating as of 1000 m, see catalog","of the gG fuse usable at inside-delta circuit up to 500 V":"3NA3820-6 ; Type of coordination 1, Iq = 65 kA","of circuit breaker usable at 400 V at inside-delta circuit":"3RV2032-4DA10 ; Type of coordination 1, Iq = 65 kA, CLASS 10","of circuit breaker usable at 500 V at inside-delta circuit":"3RV2032-4DA10 ; Type of coordination 1, Iq = 18 kA, CLASS 10","For Auxiliary And Control Contacts With Screw-Type Terminals":"7 ... 10.3 lbf·in","For Control Circuit Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","relative negative tolerance of the control supply voltage at DC":"-20 %","relative positive tolerance of the control supply voltage at DC":"20 %","Relative Negative Tolerance Of The Control Supply Voltage Frequency":"-10 %","Relative Positive Tolerance Of The Control Supply Voltage Frequency":"10 %","Inrush Current Peak At Application Of Control Supply Voltage Maximum":"3.3 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 1":"9.5 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 2":"10.4 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 3":"11.3 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 4":"12.1 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 5":"13 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 6":"13.9 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 7":"14.7 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 8":"15.6 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 9":"16.5 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 10":"17.3 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 11":"18.2 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 12":"19.1 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 13":"19.9 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 14":"20.8 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 15":"21.7 A","For Inside-Delta Circuit At Rotary Coding Switch On Switch Position 16":"22.5 A","of back-up R fuse link for semiconductor protection usable up to 690 V":"3NE8017-1 ; Type of coordination 2, Iq = 65 kA","Duration Of Inrush Current Peak At Application Of Control Supply Voltage":"12.1 ms","relative negative tolerance of the control supply voltage at AC at 50 Hz":"-20 %","relative negative tolerance of the control supply voltage at AC at 60 Hz":"-20 %","relative positive tolerance of the control supply voltage at AC at 50 Hz":"20 %","relative positive tolerance of the control supply voltage at AC at 60 Hz":"20 %","of full range R fuse link for semiconductor protection usable up to 690 V":"3NE1815-0 ; Type of coordination 2, Iq = 65 kA","at AWG cables for control circuit finely stranded with core end processing":"2x (24 ... 16)","Relative Negative Tolerance Of The Operating Voltage At Inside-Delta Circuit":"-15 %","Relative Positive Tolerance Of The Operating Voltage At Inside-Delta Circuit":"10 %"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/dc02a05d06e4f7c81eb774f4b1426c1d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=830848&mlfb=3RW5213-3AC04"},"ai":{"faq":[{"question":"What compliance documentation does Siemens provide for the 3RW5213-3AC04?","answer":"CE marking, UL approval, and CSA approval are confirmed on the record, covering the documentation needed for North American and European panel certification."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5213-3AC04","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5213-3AC04 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}