{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5214-1TC14","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5214-1TC14","canonicalUrl":"https://aoctrl.com/siemens/3RW5214-1TC14","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5214-1TC14","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3RW5214-1TC14 soft starter, 200-480 V rated voltage, 7.5 A minimum, Trip Class 10A (default)/10E/20E per IEC 60947-4-2, PROFIBUS/Modbus RTU/TCP/EtherNet/IP/PROFINET, UL/CSA/CE, 275 x 170 x 152 mm.","salesMarkdown":"## Trip class and motor protection for pump and conveyor starts The 3RW5214-1TC14 is a hybrid switching device — a soft starter — whose trip class governs how long it can carry locked-rotor current during a start without thermally overloading the motor. Minimum settable load current is 7.5 A, with a minimum load of 15% relative to the smallest settable Ie — so the unit will not regulate below that threshold, which matters when commissioning a lightly loaded motor that draws less than the floor. ## Fieldbus connectivity and remote control This soft starter carries PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard interfaces onboard — no separate communication module needed for most plant networks. PROFIenergy is supported in connection with the PROFINET standard communication module, which allows the drive to respond to energy-management commands from the controller during idle phases. Firmware updates are possible via the fieldbus connection, and an error logbook is available but only in conjunction with special accessories — factor that into your commissioning toolkit if you rely on event history for root-cause analysis. Auto-reset is standard; remote reset is achieved by cycling the control supply voltage off and back on — a simple means of clearing a trip from a remote panel without a hardwired reset pushbutton. ## Mounting clearances and ambient derating The enclosure dimensions are 275 mm height, 170 mm width, 152 mm depth — screw fixing to the mounting plate. Clearance requirements: 100 mm upwards, 75 mm downwards, 10 mm forwards, 5 mm at the sides, 0 mm backwards. The backwards allowance of zero means the unit can sit flush against a backplate, which simplifies panel layout in tight cabinets. Shock resistance is 15 g / 11 ms, with potential contact lifting from 12 g / 11 ms — the unit holds the grid under normal vibration but the contacts may bounce if the panel is subjected to repeated shock events near that threshold.","metaTitle":"Siemens 3RW5214-1TC14 Soft Starter, 200-480 V, Class 10A","metaDescription":"Siemens 3RW5214-1TC14 soft starter, rated 200-480 V, 7.5 A min, Class 10A/10E/20E trip. Active production. UL, CSA, CE. Quoted to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"152 mm","Width":"170 mm","Height":"275 mm","Mounting":"screw fixing","Trip Class":"CLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2","Product Status":"Active","Service Factor":"1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/7ca8e72145f1d8b92d189333ff8db0b4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=830862&mlfb=3RW5214-1TC14","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW5214-1TC14/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5214-1TC14","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5214-1TC14 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}