{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5214-3TC05","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5214-3TC05","canonicalUrl":"https://aoctrl.com/siemens/3RW5214-3TC05","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5214-3TC05","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW5214-3TC05 soft starter, 200-600 V AC, Class 10A trip class, PROFIBUS/Modbus/EtherNet/IP/PROFINET, UL/CSA/CE, screw fixing, 275 x 170 x 152 mm.","salesMarkdown":"## Trip class and motor protection — the real starting duty The 3RW5214-3TC05 ships with a default Trip Class 10A per IEC 60947-4-2, but can be set to 10E or 20E depending on the load's acceleration profile. Class 10A clears the start within 10 seconds at locked-rotor current — that's the right fit for centrifugal pumps and fans where the load drops off quickly. Class 20E buys you 20 seconds, useful for high-inertia loads like a long conveyor or a crusher that needs more time to spin up. The minimum settable current is 7.5 A, and the minimum load is 15% of that Ie setting. Below that floor the soft starter may not detect the motor correctly — size the unit so the motor FLA lands above 15% of the chosen current range. ## Fieldbus mix — PROFIBUS, Modbus, and Ethernet on one unit This generation of SIRIUS soft starter carries PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET on the same hardware — no need to swap a comms module when the plant migrates from PROFIBUS to PROFINET. The PROFINET implementation supports PROFIenergy, so the drive can signal the controller to shed loads during idle periods. ## Mounting and panel fit — screw-fixed, not DIN-rail The 3RW5214-3TC05 uses screw fixing, not a DIN-rail snap — plan for four mounting points on the backplate. Dimensions are 275 mm high, 170 mm wide, 152 mm deep. Clearance requirements: 100 mm above, 75 mm below, 10 mm forward, 5 mm at the sides, and 0 mm behind the unit. The 0 mm rear clearance means it can sit flush against the panel backplane, but the forward gap is needed for the power wiring and fieldbus connectors. Mounting position allows +/-10° rotation and can be tilted forward or backward on a vertical surface — useful when the backplate is not perfectly plumb. ## Wiring terminals — solid and stranded capacity That covers most motor feeders up to about 25 A depending on the cable type. The control supply is 24 V DC — separate from the main power circuit, which keeps the logic alive during a fault condition. ## Approvals and compliance documentation The unit is classified under product category 'Hybrid switching devices' and carries a service factor of 1.0 — no continuous overload margin beyond the nameplate rating.","metaTitle":"Siemens 3RW5214-3TC05 SIRIUS Soft Starter, 200-600 V","metaDescription":"Siemens 3RW5214-3TC05 SIRIUS soft starter. Rated 200-600 V AC, Class 10A/10E/20E trip class per IEC 60947-4-2. UL/CSA/CE. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"152 mm","Width":"170 mm","Height":"275 mm","Mounting":"screw fixing","Trip Class":"CLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2","Product Status":"Active","Service Factor":"1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8e1b38a1ec4845773c27059efafa95a0.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=830869&mlfb=3RW5214-3TC05","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW5214-3TC05/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5214-3TC05","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5214-3TC05 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}