{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5215-3AC14","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5215-3AC14","canonicalUrl":"https://aoctrl.com/siemens/3RW5215-3AC14","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5215-3AC14","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3RW5215-3AC14 soft starter, hybrid switching device, rated 200...480 V, minimum 11.5 A, Trip Class 10A/10E/20E, PROFIBUS/Modbus/EtherNet/IP/PROFINET, screw fixing, 275 x 170 x 152 mm.","salesMarkdown":"## What the current range and trip class mean for your motor protection The 3RW5215-3AC14 has a minimum adjustable current of 11.5 A, which sets the lower bound for the motor full-load current it can protect — if your motor draws less than that, the starter won't set correctly and nuisance tripping is likely. Class 10E and 20E are selectable for longer acceleration times or higher-inertia loads, per IEC 60947-4-2. ## Fieldbus and control integration — what connects where This soft starter supports PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard — so it drops into most common industrial networks without a gateway. An analog output is provided — 4...20 mA by default, or 0...10 V if parameterized with the High Feature HMI — for feeding motor current or other process signals back to a PLC. ## Panel mounting and clearance — what the wireman needs to know The unit measures 275 mm high by 170 mm wide by 152 mm deep, and requires the following free air space around it: 100 mm above, 10 mm in front, 0 mm behind (can sit flush to the backplane), 75 mm below, and 5 mm on each side — these are the minimum clearances for heat dissipation and wiring access. The solid wire terminals accept two conductors of 1.0...2.5 mm² and two of 2.5...10 mm², covering both control wiring and power connections in a single terminal block. It carries CE, UL, and CSA approvals, so it is accepted in North American and European installations without additional certification work.","metaTitle":"Siemens 3RW5215-3AC14 Soft Starter, 200-480 V, 11.5 A min","metaDescription":"Siemens 3RW5215-3AC14 soft starter, rated 200-480 V, minimum 11.5 A, Trip Class 10A/10E/20E per IEC 60947-4-2. Active production, CE/UL/CSA. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"152 mm","Width":"170 mm","Height":"275 mm","Mounting":"screw fixing","Trip Class":"CLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2","Product Status":"Active","Service Factor":"1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9758dc9cb572e8413a486d517481227d.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=830882&mlfb=3RW5215-3AC14","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW5215-3AC14/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5215-3AC14","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5215-3AC14 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}