{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5217-3AC14","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5217-3AC14","canonicalUrl":"https://aoctrl.com/siemens/3RW5217-3AC14","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5217-3AC14","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3RW5217-3AC14 soft starter, 15.5 A minimum, 200-480 V, Trip Class 10A/10E/20E, PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, PROFINET, UL, CSA, CE.","salesMarkdown":"## Trip class and motor protection profile The 3RW5217-3AC14 is set to Trip Class 10A by default, with selectable 10E and 20E curves per IEC 60947-4-2. Minimum load is 15 % of the smallest settable Ie, so the unit handles lightly loaded motors without dropping out of the start ramp. ## Fieldbus and control network integration This soft starter carries onboard PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET interfaces — no separate communication module needed for most architectures. PROFINET standard with PROFIenergy support is included for energy monitoring during idle phases. The analog output is configurable as 4-20 mA or 0-10 V (via the High Feature HMI), and the unit logs errors to an internal logbook when the optional accessory is fitted. ## Mounting and panel clearance Dimensions are 275 mm high, 170 mm wide, and 152 mm deep — screw-fixed to a vertical surface. Clearance requirements: 100 mm above, 75 mm below, 10 mm in front, 5 mm at the sides, and 0 mm behind. Mounting position allows ±90° rotation and ±22.5° tilt front-to-back on a vertical surface, giving flexibility in tight enclosures. ## Operating temperature and derating Rated for -25 to +60 °C during operation, but derating applies above 40 °C — factor in the thermal load if the panel ambient runs hot. Shock resistance is 15 g for 11 ms; potential contact lifting starts at 12 g for 11 ms, so the unit is robust for machine-mounted installations. ## Approvals and compliance Carries UL, CSA, and CE markings — accepted for North American and European installations without additional certification steps.","metaTitle":"Siemens 3RW5217-3AC14 Soft Starter, 15.5 A, 200-480 V","metaDescription":"Siemens 3RW5217-3AC14 soft starter, 15.5 A minimum, 200-480 V, Trip Class 10A/10E/20E. UL, CSA, CE. Active production, quoted to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"152 mm","Width":"170 mm","Height":"275 mm","Mounting":"screw fixing","Trip Class":"CLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2","Product Status":"Active","Service Factor":"1","Digital Output Version":"2 normally-open contacts (NO) / 1 changeover contact (CO)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/6c67fdb32cc55264d2635989ad98b5b0.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=830914&mlfb=3RW5217-3AC14","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW5217-3AC14/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5217-3AC14","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5217-3AC14 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}