{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5225-1TC15","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5225-1TC15","canonicalUrl":"https://aoctrl.com/siemens/3RW5225-1TC15","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5225-1TC15","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW5225-1TC15 soft starter, 200-600 VAC, 25.5 A minimum setting, Class 10A/10E/20E trip class, screw fixing, 306 x 185 x 203 mm (HxWxD).","salesMarkdown":"## SIRIUS 3RW52 — what this soft starter does on the line The 3RW5225-1TC15: Trip class is configurable as CLASS 10A (default), 10E, or 20E per IEC 60947-4-2 — the standard that governs motor-starter coordination. Minimum settable current is 25.5 A, with a minimum load threshold of 15 % relative to the smallest settable Ie — relevant when the motor FLA falls near the bottom of the adjustment range. ## Fieldbus and control — what connects where The 3RW5225-1TC15 ships with onboard PROFIBUS DP and PROFINET standard interfaces, plus Modbus RTU, Modbus TCP, and EtherNet/IP — five fieldbus protocols on one base unit without an add-on module. PROFIenergy is supported in conjunction with the PROFINET standard communication module. Remote reset is available by cycling the control supply off and on — no separate reset signal wire needed. Firmware updates are field-loadable. An error logbook function is present but requires special accessories (not included in the base unit). ## Panel fit — dimensions, mounting, and clearances Envelope is 306 mm high, 185 mm wide, 203 mm deep. Required clearances: 100 mm above, 75 mm below, 10 mm in front, 5 mm at the sides, 0 mm behind. The mounting surface can be tilted ±10° forward or backward on a vertical plane. ## Approvals and environmental limits Carries CE marking, UL approval, and CSA approval — accepted across North American and European installations without additional agency review. Shock resistance is 15 g / 11 ms, dropping to 12 g / 11 ms if contact lifting is a concern. ## Pump-specific features and soft torque Soft Torque and Pump Ramp Down are both available — the ramp-down feature reduces pressure surge on pump shutdown by gradually reducing motor voltage rather than coasting to stop. Auto-reset is configurable. Analog output and torque control are not provided on this variant (HMI-High Feature is also absent).","metaTitle":"Siemens 3RW5225-1TC15 SIRIUS Soft Starter, 200-600 V","metaDescription":"Siemens 3RW5225-1TC15 SIRIUS soft starter, 200-600 VAC, Class 10A/10E/20E trip class. Active production, UL/CSA/CE.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"203 mm","Width":"185 mm","Height":"306 mm","Mounting":"screw fixing","Trip Class":"CLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2","Product Status":"Active","Service Factor":"1","Digital Output Version":"2 normally-open contacts (NO) / 1 changeover contact (CO)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4ae8b5b7644935f322a3f845c4924f9e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=830543&mlfb=3RW5225-1TC15","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW5225-1TC15/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5225-1TC15","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5225-1TC15 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}