{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5227-1AC05","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5227-1AC05","canonicalUrl":"https://aoctrl.com/siemens/3RW5227-1AC05","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5227-1AC05","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW5227-1AC05 soft starter, 40.5 A minimum, 200-600 V, Class 10A/10E/20E, screw fixing, 306 x 185 x 203 mm (HxWxD).","salesMarkdown":"## Panel fit and mounting — 306 x 185 x 203 mm The 3RW5227-1AC05 measures 306 mm high, 185 mm wide, and 203 mm deep — screw-fixing mount, not DIN rail. Clearance requirements: 100 mm above, 75 mm below, 10 mm forward, 5 mm at the sides, and zero backward clearance needed. That 203 mm depth plus forward clearance means the enclosure depth must be at least 213 mm from the backplane to the door. ## Motor starting duty — 40.5 A minimum, trip class options Rated for a minimum motor current of 40.5 A at 200-600 V AC. The trip class is configurable: default CLASS 10A, with CLASS 10E and CLASS 20E available per IEC 60947-4-2. CLASS 20E gives a longer 20-second ramp for high-inertia loads, reducing thermal stress on the motor during start. ## Fieldbus and control — PROFIBUS, PROFINET, Modbus, EtherNet/IP Built-in support for PROFIBUS, PROFINET standard, Modbus RTU, Modbus TCP, and EtherNet/IP — no separate communication module needed for these protocols. Also supports PROFIenergy for energy management when used with a PROFINET communication module. The analog output is configurable as 4-20 mA or 0-10 V via the High Feature HMI. Remote reset is available by cycling the 24 V DC control supply. ## Environmental and approvals — UL, CSA, CE, pollution degree 3 Carries UL, CSA, and CE marking — accepted in North American and European installations. Pollution degree 3 per IEC 60947-4-2 means it tolerates conductive pollution in industrial atmospheres. Operating temperature range -25 to +60 °C, with derating required above 40 °C. Shock resistance 15 g / 11 ms, with potential contact lifting above 12 g.","metaTitle":"Siemens 3RW5227-1AC05 SIRIUS Soft Starter, 40.5 A, 200-600 V","metaDescription":"Siemens 3RW5227-1AC05 SIRIUS soft starter, 40.5 A minimum, 200-600 V, Class 10A/10E/20E. Active production. UL/CSA/CE. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"203 mm","Width":"185 mm","Height":"306 mm","Mounting":"screw fixing","Trip Class":"CLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2","Product Status":"Active","Service Factor":"1"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0b8fbebf8792bad97f1e6a2cb1297dd4.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=830569&mlfb=3RW5227-1AC05","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW5227-1AC05/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5227-1AC05","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5227-1AC05 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}