{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5235-6TC04","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5235-6TC04","canonicalUrl":"https://aoctrl.com/siemens/3RW5235-6TC04","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5235-6TC04","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW5235-6TC04 soft starter, 68 A minimum, 200-480 VAC, Trip Class 10A/10E/20E, multi-protocol communications, screw fixing.","salesMarkdown":"## What this soft starter does for a motor line The Siemens 3RW5235-6TC04 is a SIRIUS-series soft starter rated for a minimum motor current of 68 A across a 200 to 480 VAC supply. It's built for three-phase induction motors where you need controlled acceleration and deceleration — pump ramp-down is built in — and the Trip Class is selectable between CLASS 10A (default), 10E, or 20E per IEC 60947-4-2, so you match the thermal model to your motor's start profile. This unit communicates over PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET, with PROFIenergy support when paired with the PROFINET communication module. That makes it a drop-in for most plant-floor networks without an extra gateway. ## Mounting and clearances — panel layout matters The 3RW5235-6TC04 measures 306 mm high, 185 mm wide, and 203 mm deep. It mounts with screw fixing on a vertical surface, rotatable ±90° or tiltable ±22.5° front-to-back. Clearance requirements: 100 mm above, 75 mm below, 10 mm forward, 5 mm at the sides, and 0 mm backward — tight on the backplane, but plan for airflow above and below.","metaTitle":"Siemens 3RW5235-6TC04 SIRIUS Soft Starter, 68 A, 200-480 V","metaDescription":"Siemens 3RW5235-6TC04 SIRIUS soft starter, rated 68 A at 200-480 VAC. Trip Class 10A/10E/20E. Supports PROFIBUS, Modbus RTU/TCP, EtherNet/IP, PROFINET.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"203 mm","Width":"185 mm","Height":"306 mm","Mounting":"screw fixing","Trip Class":"CLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2","Product Status":"Active","Service Factor":"1","Digital Output Version":"2 normally-open contacts (NO) / 1 changeover contact (CO)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d68cff3234093993b70f4d201689c4c7.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=830612&mlfb=3RW5235-6TC04","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW5235-6TC04/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5235-6TC04","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5235-6TC04 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}