{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5235-6TC05","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5235-6TC05","canonicalUrl":"https://aoctrl.com/siemens/3RW5235-6TC05","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5235-6TC05","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW5235-6TC05 soft starter, 68 A minimum, 200-600 V, Trip Class 10A/10E/20E, PROFIBUS, Modbus RTU/TCP, EtherNet/IP, PROFINET, 203 x 185 x 306 mm.","salesMarkdown":"## What this soft starter covers — motor FLA and voltage range The 3RW5235-6TC05: Trip Class is selectable between CLASS 10A (default), 10E, and 20E per IEC 60947-4-2. For a motor with a 60-second locked-rotor withstand, CLASS 10A clears before the rotor heats past the insulation class; CLASS 20E gives more headroom on high-inertia loads like centrifuges or crushers. ## Fieldbus and control — what's onboard This soft starter ships with PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard communication. No separate gateway module needed for most PLC networks — it talks directly to a S7-1500 or CompactLogix over the same cable. PROFIenergy is supported when used with the PROFINET communication module. That lets the controller put the soft starter into a low-power state during production pauses without cycling the main contactor. Control supply voltage is 24 V DC. Remote reset is possible by cycling the control supply off and on. ## Mounting and environmental limits Dimensions are 203 mm deep, 185 mm wide, 306 mm high. Fastening is screw fixing. Mounting position allows a vertical surface with ±90° rotation and ±22.5° tilt forward/back — useful when the panel layout forces an off-angle installation. Operating temperature range is -25…+60 °C, with derating required above 40 °C. Pollution degree 3 per IEC 60947-4-2 means it tolerates conductive dust and humidity typical in industrial enclosures without conformal coating. Clearances: 100 mm above, 10 mm in front, 0 mm behind, 75 mm below, 5 mm at the sides. The zero rear clearance is handy for shallow back panels.","metaTitle":"Siemens 3RW5235-6TC05 Soft Starter, 68 A min, 200-600 V","metaDescription":"Siemens 3RW5235-6TC05 SIRIUS soft starter, rated 68 A minimum, 200-600 V, Trip Class 10A/10E/20E. UL/CSA/CE. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"203 mm","Width":"185 mm","Height":"306 mm","Mounting":"screw fixing","Trip Class":"CLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2","Product Status":"Active","Service Factor":"1","Digital Output Version":"2 normally-open contacts (NO) / 1 changeover contact (CO)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/926f34e3c2ab8a4264bab82695b453d8.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=830613&mlfb=3RW5235-6TC05","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW5235-6TC05/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5235-6TC05","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5235-6TC05 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}