{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5245-6TC04","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5245-6TC04","canonicalUrl":"https://aoctrl.com/siemens/3RW5245-6TC04","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5245-6TC04","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW5245-6TC04 soft starter, 135 A minimum, 200-480 V, Class 10A/10E/20E, screw fixing, 393 x 210 x 203 mm.","salesMarkdown":"## Field-fit and electrical ratings The 3RW5245-6TC04 is a SIRIUS hybrid switching device — a soft starter built for three-phase induction motors up to 135 A minimum rated operational current (Ie) across a 200-480 V supply range. Trip class is selectable: default CLASS 10A, with CLASS 10E and CLASS 20E available per IEC 60947-4-2. That means it handles the inrush of a standard squirrel-cage motor without nuisance tripping, but still protects against a locked-rotor condition within the 10- or 20-second thermal limit. Minimum load is 15% of the smallest settable Ie — if the motor is oversized relative to the starter, the controller may not detect a valid load. ## Communications and fieldbus options This soft starter ships with onboard PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard — no separate communication module needed for common industrial networks. PROFIenergy is supported via the PROFINET standard communication module, allowing coordinated energy management during idle phases. Firmware updates are field-loadable, so a network change or bug fix doesn't require swapping the unit. ## Mounting and environmental limits Fastening is screw fixing; the unit measures 393 mm high by 210 mm wide by 203 mm deep. Clearance requirements: 100 mm above, 75 mm below, 10 mm forward, 5 mm at the sides, 0 mm backward — plan the gland plate and busbar routing accordingly. Shock resistance is 15 g / 11 ms, dropping to 12 g / 11 ms if contact lifting is a concern. ## Agency approvals and compliance Carries CE, UL, and CSA approvals — accepted across European and North American jurisdictions without additional certification delays. Degree of pollution is 3 per IEC 60947-4-2, meaning the unit is rated for conductive pollution environments typical of industrial control panels. ## Application-specific features Includes soft torque and pump ramp down — the soft torque profile reduces mechanical shock on belt-driven loads, and the pump ramp down prevents water hammer on pump deceleration. Auto-reset and remote reset (by cycling the 24 V control supply) are built in, so a fault that clears itself doesn't require a panel visit. Error logbook is available, but only with the special accessory — budget for that if trending faults is part of the maintenance plan.","metaTitle":"Siemens 3RW5245-6TC04 SIRIUS Soft Starter, 135 A, 200-480 V","metaDescription":"Siemens 3RW5245-6TC04 SIRIUS soft starter, 135 A minimum, 200-480 V, Class 10A/10E/20E. Active production. UL/CSA/CE. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"203 mm","Width":"210 mm","Height":"393 mm","Mounting":"screw fixing","Trip Class":"CLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2","Product Status":"Active","Service Factor":"1","Digital Output Version":"2 normally-open contacts (NO) / 1 changeover contact (CO)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/67b343fce855a5c847c29faa91cf0487.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=830676&mlfb=3RW5245-6TC04","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW5245-6TC04/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5245-6TC04","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5245-6TC04 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}