{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5246-6TC14","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5246-6TC14","canonicalUrl":"https://aoctrl.com/siemens/3RW5246-6TC14","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5246-6TC14","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW5246-6TC14 soft starter, 160 A minimum, 200-480 V, Class 10A/10E/20E trip, PROFIBUS/Modbus RTU/Modbus TCP/EtherNet/IP/PROFINET, 393 x 210 x 203 mm.","salesMarkdown":"## Motor starting duty and trip class selection The 3RW5246-6TC14 is a SIRIUS hybrid switching device rated for a minimum motor current of 160 A at a supply voltage range of 200 to 480 V. The trip class is configurable as CLASS 10A (default), 10E, or 20E per IEC 60947-4-2, which governs the allowable thermal overload during acceleration. For a high-inertia load like a centrifuge or large fan, selecting CLASS 20E extends the start time window without nuisance tripping; CLASS 10A is the standard for most pump and conveyor starts. The unit supports soft torque and pump ramp down, which reduces mechanical shock on the load train during start and stop. This is relevant for applications where water hammer or belt stress is a failure mode. ## Fieldbus integration and communication options This soft starter ships with onboard PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET standard communication. PROFIenergy is supported when used with the PROFINET communication module, enabling energy management during idle phases. The device also supports firmware updates in the field. No analog output is present, so closed-loop torque control is not available. The remote reset function is triggered by cycling the control supply voltage. ## Panel fit and mounting clearances Dimensions are 393 mm height, 210 mm width, and 203 mm depth. Required clearances: 100 mm upwards, 75 mm downwards, 10 mm forwards, 5 mm at the side, and 0 mm backwards. Shock resistance is 15 g for 11 ms, with potential contact lifting at 12 g for 11 ms. ## Regulatory approvals and compliance documentation The 3RW5246-6TC14 carries CE marking, UL approval, and CSA approval. Service factor is 1.0. The minimum load is 15% relative to the smallest settable Ie.","metaTitle":"Siemens 3RW5246-6TC14 SIRIUS Soft Starter, 160 A, 200-480 V","metaDescription":"Siemens 3RW5246-6TC14 SIRIUS soft starter, 160 A minimum, 200-480 V, Class 10A/10E/20E trip. Active production, UL/CSA/CE. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"203 mm","Width":"210 mm","Height":"393 mm","Mounting":"screw fixing","Trip Class":"CLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2","Product Status":"Active","Service Factor":"1","Digital Output Version":"2 normally-open contacts (NO) / 1 changeover contact (CO)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0c8a3137ad0862c81dce061c90d8547f.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=830694&mlfb=3RW5246-6TC14","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW5246-6TC14/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5246-6TC14","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5246-6TC14 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}