{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5247-6AC04","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5247-6AC04","canonicalUrl":"https://aoctrl.com/siemens/3RW5247-6AC04","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5247-6AC04","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW5247-6AC04 soft starter, 200 A minimum, 200-480 V, Trip Class 10A/10E/20E, multi-protocol fieldbus, UL/CSA/CE, screw fixing, 203x210x393 mm.","salesMarkdown":"## Motor starting duty and overload protection The 3RW5247-6AC04 is a SIRIUS soft starter rated for a minimum motor FLA of 200 A at 200-480 V supply, covering the common low-voltage motor range for pumps, fans, and compressors. Trip Class is selectable between CLASS 10A (default), 10E, or 20E per IEC 60947-4-2, which sets the overload protection curve to match the motor's thermal withstand during starting — CLASS 10A for standard starts, 20E for high-inertia loads. ## Fieldbus integration and control options Built-in support for PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFINET (with PROFIenergy) means this starter can drop into most industrial Ethernet or serial networks without an external gateway. Analog output is configurable as 4-20 mA (default) or 0-10 V via the High Feature HMI, giving the PLC a real-time current signal for monitoring motor load. Remote reset is achieved by cycling the 24 V control supply — no need to open the panel door for a manual reset after a trip. ## Mounting and panel layout Dimensions are 203 mm deep, 210 mm wide, 393 mm high — a substantial footprint that requires a backplate or sub-panel with screw-fixing provisions; not a DIN-rail snap-on device. Mounting position allows vertical surface with ±90° rotation and ±22.5° tilt forward/back, so the starter can be oriented to fit the enclosure layout without derating. Clearance requirements: 100 mm above, 10 mm in front, 75 mm below, 5 mm at the sides — plan the gland plate and cable routing to maintain these gaps for airflow and service access. ## Approvals and compliance Carries CE marking for European markets, plus UL and CSA approval for North American installations — the nameplate and declaration of conformity cover the regulatory requirements for most industrial panels. Pollution degree 3 per IEC 60947-4-2 means it is rated for industrial environments with conductive dust or occasional condensation — no additional conformal coating needed in typical machine-tool or process-plant cabinets.","metaTitle":"Siemens 3RW5247-6AC04 SIRIUS Soft Starter, 200 A, 200-480 V","metaDescription":"Siemens 3RW5247-6AC04 SIRIUS soft starter, 200 A minimum, 200-480 V, Trip Class 10A/10E/20E. UL/CSA/CE. Active production, quoted to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"203 mm","Width":"210 mm","Height":"393 mm","Mounting":"screw fixing","Trip Class":"CLASS 10 A (default) / 10E / 20E; acc. to IEC 60947-4-2","Product Status":"Active","Service Factor":"1","Digital Output Version":"2 normally-open contacts (NO) / 1 changeover contact (CO)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9d2b5d3bc96d80eb752196b654015525.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=830704&mlfb=3RW5247-6AC04","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW5247-6AC04/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5247-6AC04","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5247-6AC04 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}