{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5517-3HA04","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5517-3HA04","canonicalUrl":"https://aoctrl.com/siemens/3RW5517-3HA04","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5517-3HA04","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3RW5517-3HA04 soft starter, 200-480 V rated voltage, ATEX certified, trip class 10A/10E/20E/30E per IEC 60947-4-2, PROFIBUS/Modbus RTU/Modbus TCP/EtherNet/IP, UL/CSA/CE, active production.","salesMarkdown":"## Soft starter for ATEX-rated motor circuits The Siemens 3RW5517-3HA04 is a soft starter with ATEX certification (Yes) and IECEx (Yes), making it suitable for starting motors in potentially explosive atmospheres where controlled acceleration and deceleration are required per the equipment protection level. Rated voltage is 200-480 V, covering common low-voltage motor supplies across 50/60 Hz networks worldwide. The trip class is configurable between CLASS 10A / 10E (default) / 20E / 30E per IEC 60947-4-2, allowing coordination with motor thermal protection for normal-start, heavy-start, or extended-start duty cycles. Global approvals include UL (Yes), CSA (Yes), and CE marking (Yes), satisfying North American and European regulatory requirements for panel builders and site electrical engineers. ## Panel integration and mounting clearances Dimensions are 170 mm width, 275 mm height, and 152 mm depth, fitting standard enclosure backplate layouts. Required clearances: 100 mm upwards, 10 mm forwards, 0 mm backwards, 75 mm downwards, and 5 mm at the side — these must be maintained for airflow and thermal dissipation. Solid connections accept 2x (1.0-2.5 mm²) and 2x (2.5-10 mm²) conductors; screw terminals are not used (No), so the wiring method is likely spring-cage or push-in — confirm the termination type on the product drawing before panel wiring. ## Fieldbus and control integration Supports PROFIBUS (Yes), Modbus RTU (Yes), Modbus TCP (Yes), and EtherNet/IP (Yes), covering the three dominant industrial Ethernet protocols plus legacy PROFIBUS. PROFIenergy is supported in connection with PROFINET Standard and PROFINET High-Feature communication modules, enabling energy management during idle phases. The accuracy class is 5 per IEC 61557-12, suitable for monitoring rather than precision metering. ## Motor control features for demanding applications Includes voltage ramp (Yes), torque control (Yes), pump ramp down (Yes), breakaway pulse (Yes), and DC braking (Yes) — these cover soft starting, soft stopping, and braking for pumps, conveyors, fans, and high-inertia loads. Combined braking (Yes) integrates DC injection with the ramp profile for faster controlled stops. Auto-reset (Yes) and remote reset (Yes) allow automated restart after a fault trip, reducing manual intervention in remote or unmanned installations. Motor heating (Yes) provides pre-heating for motors in cold environments to prevent condensation or winding damage before start. Diagnostic features include an event list (Yes), error logbook (Yes), and trace function (Yes) for post-fault analysis. Firmware update (Yes) allows field upgrades without replacing the unit.","metaTitle":"Siemens 3RW5517-3HA04 Soft Starter, 200-480 V, ATEX, Active","metaDescription":"Siemens 3RW5517-3HA04 soft starter, rated 200-480 V, ATEX certified, trip class 10A/10E/20E/30E. Active production. UL/CSA/CE. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Soft Starters"],"specifications":{"ATEX":"Yes","Depth":"152 mm","IECEx":"Yes","Solid":"2x (1.0 ... 2.5 mm²), 2x (2.5 ... 10 mm²)","Width":"170 mm","title":"3RW5517-3HA04","Height":"275 mm","Upwards":"100 mm","Forwards":"10 mm","PROFIBUS":"Yes","Backwards":"0 mm","Downwards":"75 mm","CE marking":"Yes","DC braking":"Yes","Event List":"Yes","Modbus RTU":"Yes","Modbus TCP":"Yes","Trip Class":"CLASS 10A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2","auto-RESET":"Yes","At The Side":"5 mm","EtherNet/IP":"Yes","PROFIenergy":"Yes; in connection with the PROFINET Standard and PROFINET High-Feature communication modules","Rated Value":"200 ... 480 V","UL approval":"Yes","description":"SIRIUS soft starter 200-480 V 38 A, 24 V AC/DC spring-type terminals","CSA approval":"Yes","Remote Reset":"Yes","Voltage Ramp":"Yes","Analog Output":"Yes; 4 ... 20 mA (default) / 0 ... 10 V","Error Logbook":"Yes","Motor Heating":"Yes","Accuracy Class":"5 (based on IEC 61557-12)","Pump Ramp Down":"Yes","Screw Terminal":"No","Service Factor":"1.15","Torque Control":"Yes","Trace Function":"Yes","Breakaway Pulse":"Yes","Firmware Update":"Yes","Parameterizable":"4","lifecycle_stage":"current","Combined Braking":"Yes","During Operation":"-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above","Fastening Method":"screw fixing","HMI-High Feature":"Yes","Minimum Load [%]":"10 %; Relative to set Ie","Product Category":"Hybrid switching devices","Shock Resistance":"15 g / 11 ms, from 6 g / 11 ms with potential contact lifting","Start Torque [%]":"10 ... 100 %","Mounting Position":"Vertical (can be rotated +/- 90° and tilted forward or backward +/- 22.5°)","PROFINET standard":"Yes","at DC rated value":"24 V","Product Brand Name":"SIRIUS","Application Wizards":"Yes","Degree Of Pollution":"3, acc. to IEC 60947-4-2","For Control Circuit":"spring-loaded terminals","Product Designation":"Soft starter","Reversing Operation":"Yes","Stopping Torque [%]":"10 ... 100 %","Alternative Run-Down":"Yes","Condition Monitoring":"Yes","Idle Time Adjustable":"0 ... 255 s","Inside-Delta Circuit":"Yes","Starting Voltage [%]":"20 ... 100 %","Stopping Voltage [%]":"50 %; non-adjustable","Vibration Resistance":"15 mm up to 6 Hz; 2 g up to 500 Hz","at 50 Hz rated value":"24 V","at 60 Hz rated value":"24 V","PROFINET high-feature":"Yes","Ramp-Down (Soft Stop)":"Yes","Torque Limitation [%]":"20 ... 200 %","at 40 °C rated value":"65.8 A","at 50 °C rated value":"58 A","at 60 °C rated value":"52.8 A","Communication Function":"Yes","Digital Output Version":"3 normally-open contacts (NO) / 1 changeover contact (CO)","Slave Pointer Function":"Yes","Spring-Loaded Terminal":"Yes","Ramp-Up (Soft Starting)":"Yes","at 40 °C after startup":"11 W","at 50 °C after startup":"10 W","at 60 °C after startup":"9 W","EMC emitted interference":"acc. to IEC 60947-4-2: Class A","Emergency Operation Mode":"Yes","For Main Current Circuit":"screw-type terminals","Number Of Analog Outputs":"1","Number Of Digital Inputs":"4","Number Of Parameter Sets":"3","Weight Without Packaging":"2.6 kg","at 40 °C during startup":"616 W","at 50 °C during startup":"511 W","at 60 °C during startup":"447 W","Breakaway Time Adjustable":"0 ... 2 s","For Control Circuit Solid":"2x (0.25 ... 1.5 mm²)","Motor Overload Protection":"Yes; Full motor protection (thermistor motor protection and electronic motor overload protection) / When using the motor overload protection according to ATEX, an upstream contactor is required in inside-delta circuit.","Number Of Digital Outputs":"4","Via Software Configurable":"Yes","Automatic Parameterisation":"Yes","Impulse Voltage Rated Value":"6 kV","Intrinsic Device Protection":"Yes","Number Of Controlled Phases":"3","During Storage And Transport":"-40 ... +80 °C","Type Of The Motor Protection":"Electronic, tripping in the event of thermal overload of the motor","Via Software Parameterizable":"Yes","at DC-13 at 24 V rated value":"1 A","Adjustable Current Limitation":"Yes","Electromagnetic Compatibility":"acc. to IEC 60947-4-2","Substance Prohibitance (Date)":"02/15/2018","at 40 °C rated value minimum":"7.5 A","at AC-15 at 250 V rated value":"3 A","is supported HMI-High Feature":"Yes","Insulation Voltage Rated Value":"480 V","Ramp-Down Time Of Soft Starter":"0 ... 360 s","at 230 V at 40 °C rated value":"11 kW","at 400 V at 40 °C rated value":"18.5 kW","Breakaway Voltage [%] Adjustable":"40 ... 100 %","Control Supply Voltage Frequency":"50 ... 60 Hz","Operating Measured Value Display":"Yes","Operating frequency 1 rated value":"50 Hz","Operating frequency 2 rated value":"60 Hz","of high feature HMI module usable":"3RW5980-0HF00","of the gG fuse usable up to 690 V":"3NA3824-6; Type of coordination 1, Iq = 65 kA","Between Main And Auxiliary Circuit":"480 V; does not apply for thermistor connection","Start-Up Ramp Time Of Soft Starter":"0 ... 360 s","at 200/208 V at 50 °C rated value":"10 hp","at 220/230 V at 50 °C rated value":"10 hp","at 460/480 V at 50 °C rated value":"20 hp","of circuit breaker usable at 400 V":"3RV2032-4WA10; Type of coordination 1, Iq = 65 kA, CLASS 10","of circuit breaker usable at 500 V":"3RV2032-4WA10; Type of coordination 1, Iq = 10 kA, CLASS 10","At Inside-Delta Circuit Rated Value":"200 ... 480 V","Programmable Control Inputs/Outputs":"Yes","at the digital inputs at DC maximum":"1 000 m","of communication module Ethernet/IP":"3RW5980-0CE00","Current Unbalance Limiting Value [%]":"10 ... 60 %","Design Of The Overvoltage Protection":"Varistor","Surge Voltage Resistance Rated Value":"6 kV","Current Limiting Value [%] Adjustable":"125 ... 800 %","during storage according to IEC 60721":"1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4","Between Soft Starter And Motor Maximum":"800 m","Removable Terminal For Control Circuit":"Yes","according to ATEX directive 2014/34/EU":"BVS 18 ATEX F 003 X","at AWG cables for control circuit solid":"2x (24 ... 16)","during operation according to IEC 60721":"3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6","during transport according to IEC 60721":"2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)","of communication module PROFIBUS usable":"3RW5980-0CP00","reference code according to IEC 81346-2":"Q","Finely Stranded With Core End Processing":"2x (1.0 ... 2.5 mm²), 2x (2.5 ... 6.0 mm²)","Blocking Voltage Of The Thyristor Maximum":"1 600 V","Evaluation Of Thermistor Motor Protection":"Yes; Type A PTC or Klixon / Thermoclick","Number Of Digital Outputs Parameterizable":"3","of communication module Modbus RTU usable":"3RW5980-0CR00","of communication module Modbus TCP usable":"3RW5980-0CT00","Creep Speed In Both Directions Of Rotation":"Yes","Ground-Fault Monitoring Limiting Value [%]":"10 ... 95 %","Soft Starting At Heavy Starting Conditions":"Yes","For Main Contacts With Screw-Type Terminals":"18 ... 22 lbf·in","Recovery Time After Overload Trip Adjustable":"60 ... 1 800 s","at AWG cables for main current circuit solid":"2x (16 ... 12), 2x (14 ... 8)","Number Of Digital Outputs Not Parameterizable":"1","Type Of Voltage Of The Control Supply Voltage":"AC/DC","With Conductor Cross-Section = 0.5 Mm2 Maximum":"50 m","With Conductor Cross-Section = 1.5 Mm2 Maximum":"150 m","With Conductor Cross-Section = 2.5 Mm2 Maximum":"250 m","Holding Current In Bypass Operation Rated Value":"820 mA","utilization category according to IEC 60947-4-2":"AC 53a","Product Feature Integrated Bypass Contact System":"Yes","of communication module PROFINET standard usable":"3RW5980-0CS00","Control Supply Current In Standby Mode Rated Value":"420 mA","Relative Negative Tolerance Of The Operating Voltage":"-15 %","Relative Positive Tolerance Of The Operating Voltage":"10 %","contact rating of auxiliary contacts according to UL":"R300-B300","of communication module PROFINET high-feature usable":"3RW5950-0CH00","Inrush Current By Closing The Bypass Contacts Maximum":"0.91 A","Design Of Short-Circuit Protection For Control Circuit":"4 A gG fuse (Icu=1 kA), 6 A quick-acting fuse (Icu=1 kA), C1 miniature circuit breaker (Icu= 600 A), C6 miniature circuit breaker (Icu= 300 A); Is not part of scope of supply","Relative Negative Tolerance Of The Operating Frequency":"-10 %","Relative Positive Tolerance Of The Operating Frequency":"10 %","Installation Altitude At Height Above Sea Level Maximum":"5 000 m; Derating as of 1000 m, see catalog","of the gG fuse usable at inside-delta circuit up to 500 V":"3NA3824-6; Type of coordination 1, Iq = 65 kA","of circuit breaker usable at 400 V at inside-delta circuit":"3RV2032-4RA10; Type of coordination 1, Iq = 65 kA, CLASS 10","of circuit breaker usable at 500 V at inside-delta circuit":"3RV2032-4RA10; Type of coordination 1, Iq = 10 kA, CLASS 10","For Auxiliary And Control Contacts With Screw-Type Terminals":"7 ... 10.3 lbf·in","For Control Circuit Finely Stranded With Core End Processing":"2x (0.25 ... 1.5 mm²)","relative negative tolerance of the control supply voltage at DC":"-20 %","relative positive tolerance of the control supply voltage at DC":"20 %","Relative Negative Tolerance Of The Control Supply Voltage Frequency":"-10 %","Relative Positive Tolerance Of The Control Supply Voltage Frequency":"10 %","Inrush Current Peak At Application Of Control Supply Voltage Maximum":"7.5 A","of back-up R fuse link for semiconductor protection usable up to 690 V":"3NE8024-1; Type of coordination 2, Iq = 65 kA","Duration Of Inrush Current Peak At Application Of Control Supply Voltage":"20 ms","relative negative tolerance of the control supply voltage at AC at 50 Hz":"-20 %","relative negative tolerance of the control supply voltage at AC at 60 Hz":"-20 %","relative positive tolerance of the control supply voltage at AC at 50 Hz":"20 %","relative positive tolerance of the control supply voltage at AC at 60 Hz":"20 %","of full range R fuse link for semiconductor protection usable up to 690 V":"3NE1820-0; Type of coordination 2, Iq = 65 kA","at AWG cables for control circuit finely stranded with core end processing":"2x (24 ... 16)","Relative Negative Tolerance Of The Operating Voltage At Inside-Delta Circuit":"-15 %","Relative Positive Tolerance Of The Operating Voltage At Inside-Delta Circuit":"10 %"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e7cd287ce8d6f25c6dbc6fa9dc477145.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=831000&mlfb=3RW5517-3HA04"},"ai":{"faq":[{"question":"What compliance documentation does Siemens provide for 3RW5517-3HA04?","answer":"The soft starter carries UL approval (Yes), CSA approval (Yes), and CE marking (Yes), covering North American and European regulatory requirements. ATEX (Yes) and IECEx (Yes) certifications are also listed for hazardous-area installations. RoHS and REACH documentation is typically provided by Siemens upon request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5517-3HA04","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5517-3HA04 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}