{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5527-1HF04","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5527-1HF04","canonicalUrl":"https://aoctrl.com/siemens/3RW5527-1HF04","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5527-1HF04","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3RW5527-1HF04 soft starter, 200-480 V, ATEX and IECEx certified, trip class 10A/10E/20E/30E, multiple fieldbus interfaces, screw terminals.","salesMarkdown":"## ATEX certification and motor control features This Siemens 3RW5527-1HF04 soft starter carries ATEX and IECEx certification, meaning it is approved for use in potentially explosive atmospheres — a requirement often overlooked until the site safety audit flags the motor starter. The trip class is configurable between CLASS 10A, 10E (default), 20E, and 30E per IEC 60947-4-2. CLASS 10A suits standard-starting loads like pumps and fans; CLASS 30E handles high-inertia loads such as centrifuges or crushers where the acceleration time exceeds 10 seconds. ## Fieldbus integration and control interfaces On-board fieldbus options include PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP. The analog output is configurable as 4-20 mA (default) or 0-10 V, feeding motor current or torque signals directly to a PLC analog input without an external signal conditioner. PROFIenergy support allows the starter to participate in coordinated energy-saving shutdowns during production pauses on PROFINET networks — a feature that pays for itself in facilities with scheduled idle periods. ## Mounting dimensions and panel layout The unit measures 185 mm wide, 306 mm high, and 203 mm deep. Plan for 100 mm clearance above, 75 mm below, 10 mm in front, and 5 mm at the sides — the backwards clearance is zero, so it can sit flush against the back panel. Screw terminals are standard for power and control wiring — no special crimp tooling required, which keeps installation straightforward for panel builders. ## Advanced motor control and diagnostics Voltage ramp, torque control, and breakaway pulse give the starter the ability to handle difficult loads: breakaway pulse clears stuck pump impellers, torque control limits inrush on conveyors, and pump ramp down prevents water hammer on pipeline shutdowns. DC braking provides controlled stopping for high-inertia loads without a separate braking contactor or resistor bank. On-board diagnostics include an event list, error logbook, trace function, and motor heating model — useful for commissioning engineers troubleshooting a soft-start fault without a laptop. CE marking, UL approval, and CSA approval cover the major North American and European regulatory jurisdictions. The accuracy class is 5 per IEC 61557-12, which defines the measurement uncertainty for the integrated current and voltage sensing. The service factor is 1.15, meaning the starter can continuously deliver 115 % of its rated current without exceeding thermal limits — useful for applications where the motor runs near its full load amp rating.","metaTitle":"Siemens 3RW5527-1HF04 Soft Starter, 200-480 V, ATEX, IECEx","metaDescription":"Siemens 3RW5527-1HF04 soft starter with ATEX & IECEx certification. Rated 200-480 V, trip class 10A-30E, multiple fieldbus options. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Soft Starters"],"specifications":{"ATEX":"Yes","Depth":"203 mm","IECEx":"Yes","Width":"185 mm","title":"3RW5527-1HF04","Height":"306 mm","Upwards":"100 mm","Forwards":"10 mm","PROFIBUS":"Yes","Backwards":"0 mm","Downwards":"75 mm","B10d value":"1 000 000","CE marking":"Yes","DC braking":"Yes","Event List":"Yes","Modbus RTU":"Yes","Modbus TCP":"Yes","Safe State":"Open load circuit","Trip Class":"CLASS 10A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2","auto-RESET":"Yes","At The Side":"5 mm","EtherNet/IP":"Yes","PROFIenergy":"Yes; in connection with the PROFINET Standard and PROFINET High-Feature communication modules","Rated Value":"200 ... 480 V","UL approval":"Yes","description":"SIRIUS soft starter 200-480 V 93 A, 24 V AC/DC Screw terminals Fail-safe","CSA approval":"Yes","Remote Reset":"Yes","Voltage Ramp":"Yes","Analog Output":"Yes; 4 ... 20 mA (default) / 0 ... 10 V","Error Logbook":"Yes","Motor Heating":"Yes","Accuracy Class":"5 (based on IEC 61557-12)","Pump Ramp Down":"Yes","Screw Terminal":"Yes","Service Factor":"1.15","Torque Control":"Yes","Trace Function":"Yes","With Fail-Safe":"1","Breakaway Pulse":"Yes","Firmware Update":"Yes","Parameterizable":"4","lifecycle_stage":"current","Combined Braking":"Yes","During Operation":"-25 ... +60 °C; Please observe derating at temperatures of 40 °C or above","Fastening Method":"screw fixing","HMI-High Feature":"Yes","Minimum Load [%]":"10 %; Relative to set Ie","Product Category":"Hybrid switching devices","Shock Resistance":"15 g / 11 ms, from 6 g / 11 ms with potential contact lifting","Start Torque [%]":"10 ... 100 %","Mounting Position":"Vertical (can be rotated +/- 90° and tilted forward or backward +/- 22.5°)","PROFINET standard":"Yes","at DC rated value":"24 V","Product Brand Name":"SIRIUS","Application Wizards":"Yes","Degree Of Pollution":"3, acc. to IEC 60947-4-2","For Control Circuit":"screw-type terminals","Product Designation":"Failsafe soft starters","Reversing Operation":"Yes","Stopping Torque [%]":"10 ... 100 %","Alternative Run-Down":"Yes","Condition Monitoring":"Yes","Idle Time Adjustable":"0 ... 255 s","Inside-Delta Circuit":"Yes","Starting Voltage [%]":"20 ... 100 %","Stopping Voltage [%]":"50 %; non-adjustable","Vibration Resistance":"15 mm up to 6 Hz; 2 g up to 500 Hz","at 50 Hz rated value":"24 V","at 60 Hz rated value":"24 V","PROFINET high-feature":"Yes","Ramp-Down (Soft Stop)":"Yes","Torque Limitation [%]":"20 ... 200 %","at 40 °C rated value":"161 A","at 50 °C rated value":"143 A","at 60 °C rated value":"131 A","Communication Function":"Yes","Digital Output Version":"2 normally-open contacts (NO) / 1 normally-closed contact (NC) / 1 changeover contact (CO)","Slave Pointer Function":"Yes","Spring-Loaded Terminal":"No","according to IEC 61508":"SIL1","Ramp-Up (Soft Starting)":"Yes","at 40 °C after startup":"28 W","at 50 °C after startup":"25 W","at 60 °C after startup":"23 W","EMC emitted interference":"acc. to IEC 60947-4-2: Class A","Emergency Operation Mode":"Yes","For Main Current Circuit":"box terminal","Number Of Analog Outputs":"1","Number Of Digital Inputs":"4","Number Of Parameter Sets":"3","Weight Without Packaging":"7.15 kg","at 40 °C during startup":"1 258 W","at 50 °C during startup":"1 065 W","at 60 °C during startup":"948 W","Breakaway Time Adjustable":"0 ... 2 s","For Control Circuit Solid":"1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)","Motor Overload Protection":"Yes; Full motor protection (thermistor motor protection and electronic motor overload protection) / When using the motor overload protection according to ATEX, an upstream contactor is required in inside-delta circuit.","Number Of Digital Outputs":"3","Via Software Configurable":"Yes","Automatic Parameterisation":"Yes","Impulse Voltage Rated Value":"6 kV","Intrinsic Device Protection":"Yes","Number Of Controlled Phases":"3","Safe failure fraction (SFF)":"60 %","During Storage And Transport":"-40 ... +80 °C","Type Of The Motor Protection":"Electronic, tripping in the event of thermal overload of the motor","Via Software Parameterizable":"Yes","at DC-13 at 24 V rated value":"1 A","Adjustable Current Limitation":"Yes","Electromagnetic Compatibility":"acc. to IEC 60947-4-2","Substance Prohibitance (Date)":"11/22/2019","at 40 °C rated value minimum":"19 A","at AC-15 at 250 V rated value":"3 A","is supported HMI-High Feature":"Yes","Insulation Voltage Rated Value":"480 V","Ramp-Down Time Of Soft Starter":"0 ... 360 s","at 230 V at 40 °C rated value":"22 kW","at 400 V at 40 °C rated value":"45 kW","Width Of Connection Bar Maximum":"25 mm","Breakaway Voltage [%] Adjustable":"40 ... 100 %","Control Supply Voltage Frequency":"50 ... 60 Hz","Operating Measured Value Display":"Yes","Operating frequency 1 rated value":"50 Hz","Operating frequency 2 rated value":"60 Hz","of high feature HMI module usable":"3RW5980-0HF00","of the gG fuse usable up to 690 V":"3NA3136-6; Type of coordination 1, Iq = 65 kA","Between Main And Auxiliary Circuit":"480 V; does not apply for thermistor connection","Start-Up Ramp Time Of Soft Starter":"0 ... 360 s","at 200/208 V at 50 °C rated value":"25 hp","at 220/230 V at 50 °C rated value":"30 hp","at 460/480 V at 50 °C rated value":"60 hp","of circuit breaker usable at 400 V":"3VA2216-7MN32-0AA0; Type of coordination 1, Iq = 15 kA, CLASS 10","of circuit breaker usable at 500 V":"3VA2216-7MN32-0AA0; Type of coordination 1, Iq = 10 kA, CLASS 10","At Inside-Delta Circuit Rated Value":"200 ... 480 V","Programmable Control Inputs/Outputs":"Yes","at the digital inputs at DC maximum":"1 000 m","of communication module Ethernet/IP":"3RW5980-0CE00","Current Unbalance Limiting Value [%]":"10 ... 60 %","Design Of The Overvoltage Protection":"Varistor","Surge Voltage Resistance Rated Value":"6 kV","category according to EN ISO 13849-1":"2","Current Limiting Value [%] Adjustable":"125 ... 800 %","during storage according to IEC 60721":"1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand must not get inside the devices), 1M4","stop category according to EN 60204-1":"0","Between Soft Starter And Motor Maximum":"800 m","Removable Terminal For Control Circuit":"Yes","according to ATEX directive 2014/34/EU":"BVS 18 ATEX F 003 X","at AWG cables for control circuit solid":"1x (20 ... 12), 2x (20 ... 14)","during operation according to IEC 60721":"3K6 (no ice formation, only occasional condensation), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6","during transport according to IEC 60721":"2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)","of communication module PROFIBUS usable":"3RW5980-0CP00","reference code according to IEC 81346-2":"Q","Number of digital outputs with fail-safe":"1","Blocking Voltage Of The Thyristor Maximum":"1 400 V","Evaluation Of Thermistor Motor Protection":"Yes; Type A PTC or Klixon / Thermoclick","Number Of Digital Outputs Parameterizable":"2","average diagnostic coverage level (DCavg)":"90 %","of communication module Modbus RTU usable":"3RW5980-0CR00","of communication module Modbus TCP usable":"3RW5980-0CT00","Creep Speed In Both Directions Of Rotation":"Yes","Ground-Fault Monitoring Limiting Value [%]":"10 ... 95 %","Soft Starting At Heavy Starting Conditions":"Yes","For Main Contacts With Screw-Type Terminals":"40 ... 53 lbf·in","safety device type according to IEC 61508-2":"Type B","Recovery Time After Overload Trip Adjustable":"60 ... 1 800 s","Number Of Digital Outputs Not Parameterizable":"1","Type Of Voltage Of The Control Supply Voltage":"AC/DC","With Conductor Cross-Section = 0.5 Mm2 Maximum":"50 m","With Conductor Cross-Section = 1.5 Mm2 Maximum":"150 m","With Conductor Cross-Section = 2.5 Mm2 Maximum":"250 m","Holding Current In Bypass Operation Rated Value":"870 mA","hardware fault tolerance according to IEC 61508":"0","utilization category according to IEC 60947-4-2":"AC 53a","PFHD with high demand rate according to EN 62061":"1E-6 1/h","Product Feature Integrated Bypass Contact System":"Yes","of communication module PROFINET standard usable":"3RW5980-0CS00","SIL Claim Limit (subsystem) according to EN 62061":"SIL 1","Control Supply Current In Standby Mode Rated Value":"440 mA","PFDavg with low demand rate according to IEC 61508":"0.09","performance level (PL) according to EN ISO 13849-1":"c","Relative Negative Tolerance Of The Operating Voltage":"-15 %","Relative Positive Tolerance Of The Operating Voltage":"10 %","contact rating of auxiliary contacts according to UL":"R300-B300","of communication module PROFINET high-feature usable":"3RW5950-0CH00","Inrush Current By Closing The Bypass Contacts Maximum":"6.3 A","Design Of Short-Circuit Protection For Control Circuit":"4 A gG fuse (Icu=1 kA), 6 A quick-acting fuse (Icu=1 kA), C1 miniature circuit breaker (Icu= 600 A), C6 miniature circuit breaker (Icu= 300 A); Is not part of scope of supply","Relative Negative Tolerance Of The Operating Frequency":"-10 %","Relative Positive Tolerance Of The Operating Frequency":"10 %","Installation Altitude At Height Above Sea Level Maximum":"2 000 m; Derating as of 1000 m, see catalog","of the gG fuse usable at inside-delta circuit up to 500 V":"3NA3136-6; Type of coordination 1, Iq = 65 kA","of circuit breaker usable at 400 V at inside-delta circuit":"3VA2220-7MN32-0AA0; Type of coordination 1, Iq = 15 kA, CLASS 10","of circuit breaker usable at 500 V at inside-delta circuit":"3VA2220-7MN32-0AA0; Type of coordination 1, Iq = 10 kA, CLASS 10","Diagnostics Test Interval By Internal Test Function Maximum":"1 000 s","For Auxiliary And Control Contacts With Screw-Type Terminals":"7 ... 10.3 lbf·in","For Control Circuit Finely Stranded With Core End Processing":"1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)","relative negative tolerance of the control supply voltage at DC":"-20 %","relative positive tolerance of the control supply voltage at DC":"20 %","For Main Contacts For Box Terminal Using Both Clamping Points Solid":"2x (2.5 ... 16 mm²)","Relative Negative Tolerance Of The Control Supply Voltage Frequency":"-10 %","Relative Positive Tolerance Of The Control Supply Voltage Frequency":"10 %","Inrush Current Peak At Application Of Control Supply Voltage Maximum":"7.5 A","For Main Contacts For Box Terminal Using Both Clamping Points Stranded":"2x (6 ... 16 mm²), 2x (10 ... 50 mm²)","For Main Contacts For Box Terminal Using The Back Clamping Point Solid":"1x (2.5 ... 16 mm²)","of back-up R fuse link for semiconductor protection usable up to 690 V":"3NE3227; Type of coordination 2, Iq = 65 kA","For Main Contacts For Box Terminal Using The Front Clamping Point Solid":"1x (2.5 ... 16 mm²)","Duration Of Inrush Current Peak At Application Of Control Supply Voltage":"20 ms","relative negative tolerance of the control supply voltage at AC at 50 Hz":"-20 %","relative negative tolerance of the control supply voltage at AC at 60 Hz":"-20 %","relative positive tolerance of the control supply voltage at AC at 50 Hz":"20 %","relative positive tolerance of the control supply voltage at AC at 60 Hz":"20 %","For Main Contacts For Box Terminal Using The Back Clamping Point Stranded":"1x (10 ... 70 mm²)","of full range R fuse link for semiconductor protection usable up to 690 V":"3NE1224-0; Type of coordination 2, Iq = 65 kA","For Main Contacts For Box Terminal Using The Front Clamping Point Stranded":"1x (10 ... 70 mm²)","Relative Negative Tolerance Of The Operating Voltage At Inside-Delta Circuit":"-15 %","Relative Positive Tolerance Of The Operating Voltage At Inside-Delta Circuit":"10 %","at AWG cables for main contacts for box terminal using the back clamping point":"1x (10 ... 2/0)","OFF-delay time with safety-related request when switched off via control inputs maximum":"100 ms","For Main Contacts For Box Terminal Using Both Clamping Points Finely Stranded With Core End Processing":"2x (2.5 ... 35 mm²)","For Main Contacts For Box Terminal Using The Back Clamping Point Finely Stranded With Core End Processing":"1x (2.5 ... 50 mm²)","For Main Contacts For Box Terminal Using The Front Clamping Point Finely Stranded With Core End Processing":"1x (2.5 ... 50 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f13db076f202fe099e374ed5ee56ba23.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=831178&mlfb=3RW5527-1HF04"},"ai":{"faq":[{"question":"What is the ATEX certification on this soft starter?","answer":"The 3RW5527-1HF04 carries ATEX and IECEx certification, approving it for use in explosive atmospheres as defined by the ATEX directive and IECEx scheme."},{"question":"What fieldbus protocols does the 3RW5527-1HF04 support?","answer":"On-board protocols include PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP."},{"question":"What compliance documentation does Siemens provide for 3RW5527-1HF04?","answer":"The starter carries CE marking, UL approval, and CSA approval."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5527-1HF04","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5527-1HF04 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}