{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5544-6HA04","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5544-6HA04","canonicalUrl":"https://aoctrl.com/siemens/3RW5544-6HA04","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5544-6HA04","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3RW5544-6HA04 soft starter, 200-480 V, ATEX, IECEx, Class 10A/10E/20E/30E, screw terminals, active production.","salesMarkdown":"## Trip class and motor protection profile The 3RW5544-6HA04: Trip class is selectable: CLASS 10A / 10E (default) / 20E / 30E per IEC 60947-4-2. For a pump or conveyor start, Class 10A clears the start within 10 seconds at locked-rotor current — match this to the motor's acceleration time or the soft starter will trip on a normal start. The default 10E is the electronic equivalent; 20E and 30E extend the window for high-inertia loads. Accuracy Class 5 (per IEC 61557-12) means the current measurement uncertainty is within ±5 % of reading — adequate for overload protection but not for precision energy monitoring. ## Mounting clearances and panel fit The unit measures 393 mm high, 210 mm wide, 203 mm deep. Required free space around the enclosure: 100 mm above, 75 mm below, 10 mm in front, 5 mm at the sides, and 0 mm behind. For a panel builder, the 203 mm depth plus the 10 mm front clearance means the back panel to door clearance must be at least 213 mm — check this against the enclosure depth before laying out the backplate. Screw terminals are standard; no special tooling needed. ## Control features and communication options Built-in control functions include voltage ramp, torque control, breakaway pulse, pump ramp down, DC braking, and combined braking — all parameterizable via the onboard interface. Communication protocols supported: PROFIBUS, Modbus RTU, Modbus TCP, EtherNet/IP, and PROFIenergy (the latter requires a PROFINET High-Feature communication module). For a field service tech, the Modbus TCP port is the easiest for laptop-based commissioning; the event list and error logbook (both listed as Yes) store the last fault sequence, which helps isolate nuisance trips without a PC. ## Operating temperature and derating For a line-down spare in a hot enclosure (e.g., near a motor or in a non-climate-controlled panel), the continuous current rating drops above 40 °C — confirm the motor FLA against the derated value at the actual ambient temperature before committing the BOM line. The service factor of 1.15 provides a 15 % overload margin above the nameplate rating, but this does not bypass the temperature derating curve.","metaTitle":"Siemens 3RW5544-6HA04 Soft Starter, 200-480V, ATEX, Active","metaDescription":"Siemens 3RW5544-6HA04 soft starter, 200-480V, ATEX, IECEx, UL/CSA/CE. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"203 mm","Width":"210 mm","Height":"393 mm","Mounting":"screw fixing","Trip Class":"CLASS 10 A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2","Product Status":"Active","Service Factor":"1.15"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$3,442.97","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/592f16496fd605bdc9166dbaeea3c45c.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=831382&mlfb=3RW5544-6HA04","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW5544-6HA04/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5544-6HA04","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5544-6HA04 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}