{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3RW5558-2HA14","brand":"Siemens","brandSlug":"siemens","productSlug":"3RW5558-2HA14","canonicalUrl":"https://aoctrl.com/siemens/3RW5558-2HA14","factsUrl":"https://aoctrl.com/api/mcp/products/3RW5558-2HA14","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3RW5558-2HA14 soft starter, 200-480 V rated, ATEX/IECEx certified, trip class 10A/10E/20E/30E per IEC 60947-4-2, 478 x 764 x 241 mm (WxHxD).","salesMarkdown":"The Siemens 3RW5558-2HA14 is a SIRIUS-series soft starter rated for 200-480 V supply, designed to ramp induction motors up to speed and protect them during start and stop cycles. Its trip class is configurable — CLASS 10A / 10E (default) / 20E / 30E per IEC 60947-4-2 — so you match the thermal protection to the load: 10A for standard starts, 20E or 30E for high-inertia loads like centrifuges or crushers that need a longer acceleration window. The rated voltage range of 200-480 V covers the common 230/400/480 V three-phase networks across Europe and North America. At 50 Hz the control supply accepts 110-250 V; at 60 Hz the same range applies — no separate control transformer needed for most panel voltages. Physical footprint is 478 mm wide, 764 mm high, 241 mm deep. Clearance requirements: 100 mm upwards, 75 mm downwards, 10 mm forwards, 0 mm backwards, 5 mm at the side. That backwards zero means it can sit flush against a back panel, saving enclosure depth — useful when retrofitting into existing MCC buckets. Fieldbus support includes PROFIBUS, Modbus RTU, Modbus TCP, and EtherNet/IP, plus PROFIenergy in conjunction with PROFINET communication modules. This makes it straightforward to integrate into Siemens S7 or Rockwell ControlLogix architectures without a protocol gateway. Motor control features include DC braking, voltage ramp, pump ramp down, torque control, breakaway pulse, and combined braking — covering soft start, soft stop, and controlled deceleration for pump, fan, and conveyor applications. The analog output is configurable 4-20 mA (default) or 0-10 V, useful for feeding motor current or torque to a PLC or HMI.","metaTitle":"Siemens 3RW5558-2HA14 Soft Starter, 200-480 V, ATEX","metaDescription":"Siemens 3RW5558-2HA14 soft starter, 200-480 V rated, ATEX/IECEx certified, trip class 10A/10E/20E/30E. Current production. Sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"241 mm","Width":"478 mm","Height":"764 mm","Mounting":"screw fixing","Trip Class":"CLASS 10 A / 10E (default) / 20E / 30E; acc. to IEC 60947-4-2","Product Status":"Active","Service Factor":"1.15","Digital Output Version":"3 normally-open contacts (NO) / 1 changeover contact (CO)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/e3fe015b1ae51bc4c35e10f827bd4e79.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=831255&mlfb=3RW5558-2HA14","alternativesUrl":"https://aoctrl.com/api/mcp/products/3RW5558-2HA14/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3RW5558-2HA14","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3RW5558-2HA14 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}