{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3UF7011-1AB00-0-ZI41","brand":"Siemens","brandSlug":"siemens","productSlug":"3UF7011-1AB00-0-ZI41","canonicalUrl":"https://aoctrl.com/siemens/3UF7011-1AB00-0-ZI41","factsUrl":"https://aoctrl.com/api/mcp/products/3UF7011-1AB00-0-ZI41","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMOCODE pro V PN basic unit, 3UF7011-1AB00-0-ZI41, 45 mm wide, 4 digital inputs, relay output, current detection, web server.","salesMarkdown":"## Motor management on PROFINET The Siemens 3UF7011-1AB00-0-ZI41 is a SIMOCODE pro V PN basic unit — the central control and communication module for a motor management system on PROFINET. It integrates bus communication, current detection, a control unit, and a web server into a single 45 mm wide housing that mounts on DIN rail with screw or snap-on fastening. ## 4 inputs, relay output, current sensing This basic unit provides 4 digital inputs, a relay output, direct start and reverse starting capability, and current detection with a full-scale value of 1.2 A and an initial value of 0.85 A.","metaTitle":"Siemens 3UF7011-1AB00-0-ZI41 SIMOCODE pro V PN Basic Unit","metaDescription":"Siemens 3UF7011-1AB00-0-ZI41 SIMOCODE pro V PN basic unit. 45 mm wide, 4 digital inputs, relay output, current detection, web server.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLC Communication Modules"],"specifications":{"Top":"40 mm","Left":"0 mm","Depth":"124 mm","Right":"0 mm","Solid":"1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)","Width":"45 mm","Bottom":"40 mm","Height":"111 mm","at 24 V":"1.1 ms","at 60 V":"0.55 A","at 120 V":"6 A","at 125 V":"0.25 A","at 230 V":"3 A","1 Maximum":"2 000 m","2 Maximum":"3 000 m; max. +50 °C (no protective separation)","3 Maximum":"4 000 m; max. +40 °C (no protective separation)","at 50 °C":"6 A","at 60 °C":"5 A","Web Server":"Yes","Rated Value":"24 V","Control Unit":"Yes","Direct Start":"Yes","Relay Output":"Yes","Digital Input":"Yes","Initial Value":"0.85","Shared Device":"Yes","Slide Control":"Yes","Test Function":"Yes","Valve Control":"Yes","During Storage":"-40 ... +80 °C","I&M3 - comment":"Yes","lifecycle_stage":"current","During Operation":"5 ... 95 %","During Transport":"-40 ... +80 °C","Fastening Method":"screw and snap-on mounting","Full-Scale Value":"1.2","Number Of Inputs":"4","Reverse Starting":"Yes","Bus Communication":"Yes","Current Detection":"Yes","Dahlander circuit":"Yes","Mounting Position":"any","Number Of Outputs":"3","Voltage Detection":"Yes","according to UKCA":"ITS21UKEX0464","analog I/O module":"Yes","Star-Delta Circuit":"Yes","Switching Behavior":"monostable","Asymmetry Detection":"Yes","Overload Protection":"Yes","Password Protection":"Yes","at AWG cables solid":"1x (20 ... 12), 2x (20 ... 14)","protection class IP":"IP20","Diagnostics Function":"Yes","Maintenance Function":"Yes","Vibration Resistance":"1-6 Hz / 15 mm; 6-500 Hz / 2 g","Consumed Active Power":"3.6 W","Overvoltage Detection":"Yes","Transfer Rate Maximum":"100 Mbit/s","Type Of Relay Outputs":"Monostable","according to PROFIBUS":"0","according to PROFINET":"2","Ground Fault Detection":"Yes","Parameterizable Inputs":"Yes","Undervoltage Detection":"Yes","at AWG cables stranded":"1x (20 ... 14), 2x (20 ... 16)","Active Power Monitoring":"Yes","Circuit Breaker Control":"Yes","Parameterizable Outputs":"Yes","Phase Failure Detection":"Yes","Power Factor Monitoring":"Yes","Current Measuring Module":"Yes","I&M2 - installation date":"Yes","according to Ethernet/IP":"0","type 1 acc. to IEC 61131":"Yes","Control Unit With Display":"Yes","Data Acquisition Function":"Yes","For Thermistor Connection":"1","PROFINET conformity class":"C","protocol is supported NTP":"Yes","Phase Sequence Recognition":"Yes","protocol is supported LLDP":"Yes","protocol is supported SNMP":"Yes","Blocking Current Evaluation":"Yes","Dahlander reversing circuit":"Yes","according to IEC 60068-2-27":"15g / 11 ms","protocol is supported HTTPS":"Yes","Of The Short-Circuit Control":"9 Ω","Pole-Changing Switch Circuit":"Yes","Star-Delta Reversing Circuit":"Yes","Type Of Input Characteristic":"Type 1 in accordance with EN 61131-2","fail-safe digital I/O module":"Yes","Overcurrent Detection 1 Phase":"Yes","Substance Prohibitance (Date)":"03/01/2017","Temperature Monitoring Module":"Yes","supports PROFIenergy shutdown":"Yes","Ground-Fault Monitoring Module":"Yes","Parameterizable Overload Relay":"Yes","Undercurrent Detection 1 Phase":"Yes","Input For Thermistor Connection":"Yes","Number Of Semiconductor Outputs":"0","Release Value Of Thermoresistor":"1 500 ... 1 650 Ω","Current/Voltage Measuring Module":"Yes","Input For Ground Fault Detection":"No","Response Value Of Thermoresistor":"3 400 ... 3 800 Ω","protocol is supported Modbus RTU":"No","protocol is supported EtherNet/IP":"No","I&M0 - device-specific information":"Yes","protocol is supported OPC UA Server":"Yes","Input For Analog Temperature Sensors":"No","Surge Voltage Resistance Rated Value":"4 000 V","supports PROFIenergy measured values":"Yes","EMC immunity according to IEC 60947-1":"corresponds to degree of severity 3","Product Function Soft Starter Control":"Yes","at the Ethernet interface Autosensing":"Yes","during storage according to IEC 60721":"1K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt mist), 1S2 (sand must not get into the devices), 1M4","Pole-Changing Switch Reversing Circuit":"Yes","according to ATEX directive 2014/34/EU":"BVS 06 ATEX F001","Wire Length For Digital Signals Maximum":"300 m","at the Ethernet interface Autocrossover":"Yes","due to burst according to IEC 61000-4-4":"2 kV (power ports) / 1 kV (signal ports)","during operation according to IEC 60721":"3K6 (no formation of ice, no condensation, relative humidity 10 ... 95%), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6","during transport according to IEC 60721":"2K2, 2C1, 2S1, 2M2","reference code according to IEC 81346-2":"F","Finely Stranded With Core End Processing":"1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)","Monitoring Of Number Of Start Operations":"Yes","protocol is supported PROFIsafe protocol":"Yes","Evaluation Of Thermistor Motor Protection":"Yes","Touch Protection Against Electrical Shock":"finger-safe","at the Ethernet interface Autonegotiation":"Yes","control supply voltage 1 at DC rated value":"24 V","protocol is supported PROFIBUS DP protocol":"No","protocol is supported PROFINET IO protocol":"Yes","Tightening Torque With Screw-Type Terminals":"0.8 ... 1.2 N·m","Buffering Time In The Event Of Power Failure":"0.02 s","is supported PROFINET system redundancy (S2)":"Yes","Design Of Short-Circuit Protection Per Output":"Fuse links: gG 6 A, quick-response 10 A (IEC 60947-5-1), miniature circuit-breaker C char.: 1.6 A (IEC 60947-5-1) or 6 A (I_K < 500 A)","Type Of Voltage Of The Control Supply Voltage":"DC","With Conductor Cross-Section = 0.5 Mm2 Maximum":"50 m","With Conductor Cross-Section = 1.5 Mm2 Maximum":"150 m","With Conductor Cross-Section = 2.5 Mm2 Maximum":"250 m","Electrical Endurance (Operating Cycles) Typical":"100 000","input voltage at digital input at DC rated value":"24 V","EMC emitted interference according to IEC 60947-1":"class A","Mechanical Service Life (Operating Cycles) Typical":"10 000","electrostatic discharge according to IEC 61000-4-2":"6 kV contact discharge / 8 kV air discharge","I&M1 - higher level designation/location designation":"Yes","contact rating of auxiliary contacts according to UL":"B300 / R300","Tightening Torque [Lbf·In] With Screw-Type Terminals":"7 ... 10.3 lbf·in","product function is supported Device Level Ring (DLR)":"No","protocol is supported Media Redundancy Protocol (MRP)":"Yes","Number Of Outputs As Contact-Affected Switching Element":"3","protocol is supported Address Resolution Protocol (ARP)":"Yes","Media Redundancy Protocol for Planned Duplication (MRPD)":"Yes","conducted HF interference emissions according to CISPR11":"corresponds to degree of severity A","Total Cold Resistance Number Of Sensors In Series Maximum":"1.5 kΩ","field-bound HF interference emission according to CISPR11":"corresponds to degree of severity A","Number Of Digital Inputs With A Common Reference Potential":"4","Type Of Electrical Connection Of The Communication Interface":"2x RJ45","insulation voltage with degree of pollution 3 at AC rated value":"300 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"Yes"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/892b8416519957d3ad49a0793d7de28a.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1648933&mlfb=3UF7011-1AB00-0-ZI41","alternativesUrl":"https://aoctrl.com/api/mcp/products/3UF7011-1AB00-0-ZI41/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy Siemens 3UF7011-1AB00-0-ZI41?","answer":"Submit a request for quote to confirm availability and current pricing."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3UF7011-1AB00-0-ZI41","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3UF7011-1AB00-0-ZI41 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}