{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3UF7011-1AU00-0-ZI41","brand":"Siemens","brandSlug":"siemens","productSlug":"3UF7011-1AU00-0-ZI41","canonicalUrl":"https://aoctrl.com/siemens/3UF7011-1AU00-0-ZI41","factsUrl":"https://aoctrl.com/api/mcp/products/3UF7011-1AU00-0-ZI41","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIMOCODE pro V PN basic unit, 3UF7011-1AU00-0-ZI41, rated supply 110-240 V AC/DC, 4 digital inputs, web server, screw and snap-on mounting.","salesMarkdown":"## Supply voltage and input configuration The 3UF7011-1AU00-0-ZI41 operates on a rated supply voltage of 110 to 240 V AC/DC at 50/60 Hz, drawing 2 A at 24 V and 6 A at 50 °C — the supply current scales with load and temperature, so budget the 24 V draw for the control loop and the 50 °C figure for the thermal design of the enclosure. Four digital inputs are onboard, with a relay output and a control unit integrated — no separate I/O slice needed for basic motor management functions like direct start or valve control. The housing measures 45 mm wide by 111 mm high by 124 mm deep, with 40 mm clearance required above and below for wiring and airflow — the 0 mm left and right clearance means it can be butted against adjacent units in a DIN-rail row without derating. Fastening is by screw or snap-on mounting onto standard DIN rail, so it integrates into existing panels without special brackets.","metaTitle":"Siemens 3UF7011-1AU00-0-ZI41 SIMOCODE pro V PN Basic Unit","metaDescription":"Siemens 3UF7011-1AU00-0-ZI41 SIMOCODE pro V PN basic unit. Rated supply 110-240 V AC/DC, 4 digital inputs, web server, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["PLC Communication Modules"],"specifications":{"Top":"40 mm","Left":"0 mm","Depth":"124 mm","Right":"0 mm","Solid":"1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)","Width":"45 mm","title":"3UF7011-1AU00-0-ZI41","Bottom":"40 mm","Height":"111 mm","at 24 V":"2 A","at 60 V":"0.55 A","at 120 V":"6 A","at 125 V":"0.25 A","at 230 V":"3 A","at 240 V":"1 ms","1 Maximum":"2 000 m","2 Maximum":"3 000 m; max. +50 °C (no protective separation)","3 Maximum":"4 000 m; max. +40 °C (no protective separation)","at 50 °C":"6 A","at 60 °C":"5 A","Web Server":"Yes","Rated Value":"110 ... 240 V","description":"basic unit SIMOCODE pro V PN, Ethernet/PROFINET IO, PN system redundancy, OPC UA server, web server, transfer rate 100 Mbps, 2 x bus connection via RJ45, 4I/3O freely parameterizable, US: 110 - 240 V AC/DC, input for thermistor connection monostable relay outputs, expandable by expansion modules firmware version V3.0.0","Control Unit":"Yes","Direct Start":"Yes","Relay Output":"Yes","1 Rated Value":"50 Hz","2 Rated Value":"60 Hz","Digital Input":"Yes","Initial Value":"0.85","Shared Device":"Yes","Slide Control":"Yes","Test Function":"Yes","Valve Control":"Yes","During Storage":"-40 ... +80 °C","I&M3 - comment":"Yes","lifecycle_stage":"current","During Operation":"5 ... 95 %","During Transport":"-40 ... +80 °C","Fastening Method":"screw and snap-on mounting","Full-Scale Value":"1.1","Number Of Inputs":"4","Reverse Starting":"Yes","Bus Communication":"Yes","Current Detection":"Yes","Dahlander circuit":"Yes","Mounting Position":"any","Number Of Outputs":"3","Voltage Detection":"Yes","according to UKCA":"ITS21UKEX0464","analog I/O module":"Yes","Star-Delta Circuit":"Yes","Switching Behavior":"monostable","Asymmetry Detection":"Yes","Overload Protection":"Yes","Password Protection":"Yes","at AWG cables solid":"1x (20 ... 12), 2x (20 ... 14)","protection class IP":"IP20","Diagnostics Function":"Yes","Maintenance Function":"Yes","Vibration Resistance":"1-6 Hz / 15 mm; 6-500 Hz / 2 g","at 50 Hz rated value":"110 ... 240 V","at 60 Hz rated value":"110 ... 240 V","Consumed Active Power":"4.5 W","Overvoltage Detection":"Yes","Transfer Rate Maximum":"100 Mbit/s","Type Of Relay Outputs":"Monostable","according to PROFIBUS":"0","according to PROFINET":"2","Ground Fault Detection":"Yes","Parameterizable Inputs":"Yes","Undervoltage Detection":"Yes","at AWG cables stranded":"1x (20 ... 14), 2x (20 ... 16)","Active Power Monitoring":"Yes","Circuit Breaker Control":"Yes","Parameterizable Outputs":"Yes","Phase Failure Detection":"Yes","Power Factor Monitoring":"Yes","Current Measuring Module":"Yes","I&M2 - installation date":"Yes","according to Ethernet/IP":"0","type 1 acc. to IEC 61131":"Yes","Control Unit With Display":"Yes","Data Acquisition Function":"Yes","For Thermistor Connection":"1","PROFINET conformity class":"C","protocol is supported NTP":"Yes","Apparent Power Consumption":"8.3 VA","Phase Sequence Recognition":"Yes","protocol is supported LLDP":"Yes","protocol is supported SNMP":"Yes","Blocking Current Evaluation":"Yes","Dahlander reversing circuit":"Yes","according to IEC 60068-2-27":"15g / 11 ms","protocol is supported HTTPS":"Yes","Of The Short-Circuit Control":"9 Ω","Pole-Changing Switch Circuit":"Yes","Star-Delta Reversing Circuit":"Yes","Type Of Input Characteristic":"Type 1 in accordance with EN 61131-2","fail-safe digital I/O module":"Yes","Overcurrent Detection 1 Phase":"Yes","Substance Prohibitance (Date)":"03/01/2017","Temperature Monitoring Module":"Yes","supports PROFIenergy shutdown":"Yes","Ground-Fault Monitoring Module":"Yes","Parameterizable Overload Relay":"Yes","Undercurrent Detection 1 Phase":"Yes","Input For Thermistor Connection":"Yes","Number Of Semiconductor Outputs":"0","Release Value Of Thermoresistor":"1 500 ... 1 650 Ω","Current/Voltage Measuring Module":"Yes","Input For Ground Fault Detection":"No","Response Value Of Thermoresistor":"3 400 ... 3 800 Ω","protocol is supported Modbus RTU":"No","protocol is supported EtherNet/IP":"No","I&M0 - device-specific information":"Yes","protocol is supported OPC UA Server":"Yes","Input For Analog Temperature Sensors":"No","Surge Voltage Resistance Rated Value":"4 000 V","supports PROFIenergy measured values":"Yes","EMC immunity according to IEC 60947-1":"corresponds to degree of severity 3","Product Function Soft Starter Control":"Yes","at the Ethernet interface Autosensing":"Yes","during storage according to IEC 60721":"1K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt mist), 1S2 (sand must not get into the devices), 1M4","Pole-Changing Switch Reversing Circuit":"Yes","according to ATEX directive 2014/34/EU":"BVS 06 ATEX F001","Wire Length For Digital Signals Maximum":"300 m","at the Ethernet interface Autocrossover":"Yes","due to burst according to IEC 61000-4-4":"2 kV (power ports) / 1 kV (signal ports)","during operation according to IEC 60721":"3K6 (no formation of ice, no condensation, relative humidity 10 ... 95%), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6","during transport according to IEC 60721":"2K2, 2C1, 2S1, 2M2","reference code according to IEC 81346-2":"F","Finely Stranded With Core End Processing":"1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)","Monitoring Of Number Of Start Operations":"Yes","protocol is supported PROFIsafe protocol":"Yes","Evaluation Of Thermistor Motor Protection":"Yes","Touch Protection Against Electrical Shock":"finger-safe","at the Ethernet interface Autonegotiation":"Yes","protocol is supported PROFIBUS DP protocol":"No","protocol is supported PROFINET IO protocol":"Yes","Tightening Torque With Screw-Type Terminals":"0.8 ... 1.2 N·m","Buffering Time In The Event Of Power Failure":"0.02 s","is supported PROFINET system redundancy (S2)":"Yes","Design Of Short-Circuit Protection Per Output":"Fuse links: gG 6 A, quick-response 10 A (IEC 60947-5-1), miniature circuit-breaker C char.: 1.6 A (IEC 60947-5-1) or 6 A (I_K < 500 A)","Type Of Voltage Of The Control Supply Voltage":"AC/DC","With Conductor Cross-Section = 0.5 Mm2 Maximum":"50 m","With Conductor Cross-Section = 1.5 Mm2 Maximum":"150 m","With Conductor Cross-Section = 2.5 Mm2 Maximum":"250 m","Electrical Endurance (Operating Cycles) Typical":"100 000","input voltage at digital input at DC rated value":"24 V","EMC emitted interference according to IEC 60947-1":"class A","Mechanical Service Life (Operating Cycles) Typical":"10 000","electrostatic discharge according to IEC 61000-4-2":"6 kV contact discharge / 8 kV air discharge","I&M1 - higher level designation/location designation":"Yes","contact rating of auxiliary contacts according to UL":"B300 / R300","Tightening Torque [Lbf·In] With Screw-Type Terminals":"7 ... 10.3 lbf·in","product function is supported Device Level Ring (DLR)":"No","protocol is supported Media Redundancy Protocol (MRP)":"Yes","Number Of Outputs As Contact-Affected Switching Element":"3","protocol is supported Address Resolution Protocol (ARP)":"Yes","Media Redundancy Protocol for Planned Duplication (MRPD)":"Yes","conducted HF interference emissions according to CISPR11":"corresponds to degree of severity A","Total Cold Resistance Number Of Sensors In Series Maximum":"1.5 kΩ","field-bound HF interference emission according to CISPR11":"corresponds to degree of severity A","Number Of Digital Inputs With A Common Reference Potential":"4","Type Of Electrical Connection Of The Communication Interface":"2x RJ45","insulation voltage with degree of pollution 3 at AC rated value":"300 V","Product Component Removable Terminal For Auxiliary And Control Circuit":"Yes","Relative Symmetrical Tolerance Of The Control Supply Voltage Frequency":"5 %"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5530e69fbd8103cda9ec824fc7d55f1e.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=1648934&mlfb=3UF7011-1AU00-0-ZI41"},"ai":{"faq":[{"question":"Is the 3UF7011-1AU00-0-ZI41 expandable with additional I/O modules?","answer":"The basic unit includes 4 digital inputs and a relay output, and the SIMOCODE pro V system supports expansion via additional modules on the same backplane."},{"question":"Does 3UF7011-1AU00-0-ZI41 support PROFINET system redundancy?","answer":"The basic unit supports shared device functionality, which is the PROFINET mechanism for system redundancy."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3UF7011-1AU00-0-ZI41","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3UF7011-1AU00-0-ZI41 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}