{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3UF7100-1AA00-0","brand":"Siemens","brandSlug":"siemens","productSlug":"3UF7100-1AA00-0","canonicalUrl":"https://aoctrl.com/siemens/3UF7100-1AA00-0","factsUrl":"https://aoctrl.com/api/mcp/products/3UF7100-1AA00-0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS 3UF7100-1AA00-0 Current Measuring Module, 45 x 84 x 45 mm, IP20, 110-690 V AC, trip class 5E, active production.","salesMarkdown":"The Siemens 3UF7100-1AA00-0 is a SIRIUS current measuring module designed for overload protection in motor feeder applications. It measures current without requiring voltage detection, and provides a trip class 5E response — meaning the module trips within that time-current band for overcurrent conditions. It operates on AC supply voltages from 110 to 690 V at 50-60 Hz and consumes just 0.2 W active power. ## Operating range and derating Rated -25 to +60 °C, IP20, altitude derating: full to 2 000 m, then 3 000 m at +50 °C max, 4 000 m at +40 °C max; vibration 1-6 Hz / 15 mm and 6-500 Hz / 2 g. Lifecycle status is current — Siemens still produces this order code, so no last-time-buy or discontinuation concern. We source the 3UF7100-1AA00-0 to order against an RFQ; expect standard lead times for SIRIUS motor protection modules. The module is 45 mm wide and 84 mm high, mounts via screw or snap-on in any orientation, requires 30 mm clearance above and below (sides 0 mm), and has a 7.5 mm cable inlet.","metaTitle":"Siemens 3UF7100-1AA00-0 SIRIUS Current Module, IP20","metaDescription":"Siemens 3UF7100-1AA00-0 SIRIUS current measuring module with overload protection, trip class 5E, 110-690V AC, IP20, active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLC I/O & Expansion Modules"],"specifications":{"Top":"30 mm","Left":"0 mm","Depth":"45 mm","Right":"0 mm","Width":"45 mm","title":"3UF7100-1AA00-0","Bottom":"30 mm","Height":"84 mm","1 Maximum":"2 000 m","2 Maximum":"3 000 m; max. +50 °C (no protective separation)","3 Maximum":"4 000 m; max. +40 °C (no protective separation)","Trip Class":"CLASS 5E","description":"Current measuring module, Set current 0.3...3 A Overall width 45 mm, straight-through transformer","During Storage":"-40 ... +80 °C","Type Of Voltage":"AC","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","During Transport":"-40 ... +80 °C","Fastening Method":"screw and snap-on mounting","Current Detection":"Yes","Mounting Position":"any","Power Measurement":"No","Voltage Detection":"No","according to UKCA":"ITS21UKEX0464","Product Brand Name":"SIRIUS","Current Measurement":"Yes","Overload Protection":"Yes","Product Designation":"Current measuring module","Voltage Measurement":"No","protection class IP":"IP20","Vibration Resistance":"1-6 Hz / 15 mm; 6-500 Hz / 2 g","at 50 Hz rated value":"110 ... 690 V","at 60 Hz rated value":"110 ... 690 V","Consumed Active Power":"0.2 W","Frequency Measurement":"No","Ground-Fault Monitoring":"No","Power Factor Monitoring":"No","Active Power Measurement":"No","Diameter Of Inlet Opening":"7.5 mm","Substance Prohibitance (Date)":"05/28/2009","Input For Thermistor Connection":"No","Operating Frequency Rated Value":"50 ... 60 Hz","Relative Humidity During Operation":"5 ... 95 %","Surge Voltage Resistance Rated Value":"6 000 V","EMC immunity according to IEC 60947-1":"corresponds to degree of severity 3","during storage according to IEC 60721":"1K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt mist), 1S2 (sand must not get into the devices), 1M4","according to ATEX directive 2014/34/EU":"BVS 06 ATEX F001","due to burst according to IEC 61000-4-4":"2 kV","during operation according to IEC 60721":"3K6 (no formation of ice, no condensation, relative humidity 10 ... 95%), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6","during transport according to IEC 60721":"2K2, 2C1, 2S1, 2M2","reference code according to IEC 81346-2":"F","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"No","shock resistance according to IEC 60068-2-27":"15g / 11 ms","with degree of pollution 3 at AC rated value":"690 V","Diameter Of Inlet Opening For Current Measurement":"7.5 mm","EMC emitted interference according to IEC 60947-1":"class A","Number Of Outputs As Contact-Affected Switching Element":"0","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"0.3 ... 3 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$78.74","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9a41bcdd914431fa28450812dad6a143.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=285104&mlfb=3UF7100-1AA00-0"},"ai":{"faq":[{"question":"What compliance documentation does 3UF7100-1AA00-0 carry?","answer":"It holds UKCA certification from ITS (certificate ITS21UKEX0464) and has a substance prohibitance date of May 28, 2009, indicating RoHS compliance."},{"question":"What are the mounting clearance requirements?","answer":"The module requires 30 mm clearance above and 30 mm below. Left and right sides have zero clearance needed."},{"question":"What voltage supply does this module work on?","answer":"It is rated for 110-690 V AC at 50-60 Hz."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3UF7100-1AA00-0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3UF7100-1AA00-0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}