{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3UF7102-1AA00-0","brand":"Siemens","brandSlug":"siemens","productSlug":"3UF7102-1AA00-0","canonicalUrl":"https://aoctrl.com/siemens/3UF7102-1AA00-0","factsUrl":"https://aoctrl.com/api/mcp/products/3UF7102-1AA00-0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS, current measuring module, 3UF7102-1AA00-0, 110-690 V AC, 50/60 Hz, IP20, CLASS 5E, top 30 mm, left 0 mm, screw and snap-on mounting.","salesMarkdown":"## Current measurement and overload in a compact frame The Siemens 3UF7102-1AA00-0 is a SIRIUS current measuring module that combines current detection, overload protection, and a wide voltage range (110-690 V AC at 50/60 Hz) in a single 55×94×72 mm housing. It draws 0.2 W from the monitored circuit and carries a trip class CLASS 5E, matching the thermal curve of standard induction motors. The module mounts via screw or snap-on in any orientation, with top and bottom clearance of 30 mm each and zero left/right space needed — nests tightly with other SIRIUS gear on the same panel. Fastens with a screw or snap-on onto DIN rail or panel plate — any position allowed. The inlet opening diameter is 14 mm, accepting standard motor cable terminations. Left and right clearance is 0 mm, so side-by-side modules don't require extra spacing. For vibration-prone installations, use the screw mount option.","metaTitle":"Siemens 3UF7102-1AA00-0 SIRIUS Current Measuring Module, IP2","metaDescription":"Active production current measuring module from SIRIUS, overload protection, CLASS 5E, 110-690 V AC, 0.2 W, IP20. Compact 55×94×72 mm. Available to order via RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["PLC I/O & Expansion Modules"],"specifications":{"Top":"30 mm","Left":"0 mm","Depth":"72 mm","Right":"0 mm","Width":"55 mm","title":"3UF7102-1AA00-0","Bottom":"30 mm","Height":"94 mm","1 Maximum":"2 000 m","2 Maximum":"3 000 m; max. +50 °C (no protective separation)","3 Maximum":"4 000 m; max. +40 °C (no protective separation)","Trip Class":"CLASS 5E","description":"Current measuring module, Set current 10...100 A Overall width 55 mm, straight-through transformer","During Storage":"-40 ... +80 °C","Type Of Voltage":"AC","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","During Transport":"-40 ... +80 °C","Fastening Method":"screw and snap-on mounting","Current Detection":"Yes","Mounting Position":"any","Power Measurement":"No","Voltage Detection":"No","according to UKCA":"ITS21UKEX0464","Product Brand Name":"SIRIUS","Current Measurement":"Yes","Overload Protection":"Yes","Product Designation":"Current measuring module","Voltage Measurement":"No","protection class IP":"IP20","Vibration Resistance":"1-6 Hz / 15 mm; 6-500 Hz / 2 g","at 50 Hz rated value":"110 ... 690 V","at 60 Hz rated value":"110 ... 690 V","Consumed Active Power":"0.2 W","Frequency Measurement":"No","Ground-Fault Monitoring":"No","Power Factor Monitoring":"No","Active Power Measurement":"No","Diameter Of Inlet Opening":"14 mm","Substance Prohibitance (Date)":"05/28/2009","Input For Thermistor Connection":"No","Operating Frequency Rated Value":"50 ... 60 Hz","Relative Humidity During Operation":"5 ... 95 %","Surge Voltage Resistance Rated Value":"6 000 V","EMC immunity according to IEC 60947-1":"corresponds to degree of severity 3","during storage according to IEC 60721":"1K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt mist), 1S2 (sand must not get into the devices), 1M4","according to ATEX directive 2014/34/EU":"BVS 06 ATEX F001","due to burst according to IEC 61000-4-4":"2 kV","during operation according to IEC 60721":"3K6 (no formation of ice, no condensation, relative humidity 10 ... 95%), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6","during transport according to IEC 60721":"2K2, 2C1, 2S1, 2M2","reference code according to IEC 81346-2":"F","Number Of Poles For Main Current Circuit":"3","Product Function Short Circuit Protection":"No","shock resistance according to IEC 60068-2-27":"15g / 11 ms","with degree of pollution 3 at AC rated value":"690 V","Diameter Of Inlet Opening For Current Measurement":"14 mm","EMC emitted interference according to IEC 60947-1":"class A","Number Of Outputs As Contact-Affected Switching Element":"0","Adjustable Current Response Value Current Of The Current-Dependent Overload Release":"10 ... 100 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/204a4ab7f28ad8e1f975dd6b0791fadf.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=101950&mlfb=3UF7102-1AA00-0"},"ai":{"faq":[{"question":"What is the closest functional second-source for the 3UF7102-1AA00-0?","answer":"No direct functional second-source exists in the SIRIUS line for this specific current measuring module. Other peer MPNs listed (6AG1278-4BD32-4XB0, 6AG1221-1BH32-2XB0, 6AG1222-1BH32-2XB0) are different product categories and cannot be substituted."},{"question":"What compliance documentation does the 3UF7102-1AA00-0 have?","answer":"The module is UKCA certified (certificate ITS21UKEX0464). It also meets substance prohibitance requirements per the RoHS date 05/28/2009. IP20 rating is indicated. No UL or specific IEC certification is listed, but the UKCA mark covers conformity for UK market."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3UF7102-1AA00-0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3UF7102-1AA00-0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}