{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3UG5462-1AA41","brand":"Siemens","brandSlug":"siemens","productSlug":"3UG5462-1AA41","canonicalUrl":"https://aoctrl.com/siemens/3UG5462-1AA41","factsUrl":"https://aoctrl.com/api/mcp/products/3UG5462-1AA41","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SIRIUS DC load monitoring relay, 3UG5462-1AA41, for PROFINET, measurable current -63 … +63 A, adjustable voltage 0 … 60 V, screw and snap-on mounting on 35 mm DIN rail.","salesMarkdown":"The 3UG5462-1AA41: The -63 to +63 A measurable current range covers most DC motor and process loads in industrial panels. The 0 to 60 V adjustable voltage range matches common 24 V and 48 V DC control buses. The PROFINET IO interface (conformity class A) allows direct integration into a Siemens S7-1500 or other PROFINET controller without an extra analog input module — the relay reports current and voltage values digitally, and the trip thresholds are set via the controller or the device's own adjustable time delay (0 to 999 s on start-up). The auxiliary contact rating (0.5 A at 125 V AC, resistive load up to 40 °C) is sufficient for signaling to a PLC input or a pilot light, but not for switching a contactor coil directly — use an interposing relay if the coil draw exceeds that. The 45 mm width (3 HP) fits standard enclosure space. Front face is IP20; terminals are IP00 — keep live parts behind a panel door. Power loss is 3 W maximum, so no forced cooling needed in a typical cabinet.","metaTitle":"Siemens 3UG5462-1AA41 SIRIUS DC Load Monitoring Relay, -63…+","metaDescription":"Siemens SIRIUS 3UG5462-1AA41 DC load monitoring relay, PROFINET IO, measures -63…+63 A, 0…60 V. Active production. Sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"NRND","categoryPath":["Process / Temperature Controllers"],"specifications":{"1":"-63 ... +63 A","Note":"0.5 A 125 V AC, with resistive load up to 40 °C","Depth":"141.6 mm","Solid":"1x (0.5 ... 4 mm²), 2x (0.5 ... 2.5 mm²)","Width":"45 mm","Height":"100 mm","Upwards":"50 mm","at 24 V":"1 A","Forwards":"0 mm","Stranded":"2x (1 ... 16 mm²), 1x (1 ... 16 mm²)","Backwards":"0 mm","Downwards":"50 mm","auto-RESET":"Yes","At The Side":"3 mm","On The Front":"IP20","When Starting":"0 ... 999 s","During Storage":"-40 ... +80 °C","Of The Terminal":"IP00","lifecycle_stage":"current","During Operation":"-25 ... +60 °C","During Transport":"-40 ... +80 °C","Fastening Method":"screw and snap-on mounting onto 35 mm DIN rail","Product Function":"DC load monitoring relay","Mounting Position":"any","Measurable Current":"-63 ... +63 A","Product Brand Name":"SIRIUS","Product Designation":"DC load monitoring relay","PROFINET IO protocol":"Yes","Design Of The Product":"for PROFINET","Response Time Maximum":"100 ms","power loss [W] maximum":"3 W","Adjustable Voltage Range":"0 ... 60 V","Between Input And Output":"Yes","measurable voltage at DC":"0 ... 60 V","overcurrent detection DC":"Yes","overvoltage detection DC":"Yes","PROFINET conformity class":"A","undercurrent detection DC":"Yes","undervoltage detection DC":"Yes","Electromagnetic Compatibility":"IEC 60947-1 / IEC 61000-6-2 / IEC 61000-6-4","Substance Prohibitance (Date)":"05/31/2019","Type Of Electrical Connection":"screw-type terminals","Type Of Current For Monitoring":"DC","Type Of Voltage For Monitoring":"DC","at AWG cables for main contacts":"1x (18 ... 1), 2x (18 ... 2)","Address Resolution Protocol (ARP)":"Yes","Design Of The Electrical Isolation":"Protective separation","interface design 1 RJ45 (Ethernet)":"Yes","supply voltage 1 at DC rated value":"24 V","With Lower Or Upper Limit Violation":"0 ... 999 s","Number Of Ports At The 1st Interface":"1","Surge Voltage Resistance Rated Value":"6 kV","at AWG cables for auxiliary contacts":"1x (20 ... 12), 2x (20 ... 14)","Between Control And Auxiliary Circuit":"24 V","Type Of Voltage Of The Supply Voltage":"DC","service for open IE communication LLDP":"Yes","Between Auxiliary And Auxiliary Circuit":"24 V","due to burst according to IEC 61000-4-4":"2 kV","reference code according to IEC 81346-2":"K","Finely Stranded With Core End Processing":"2x (0,5 ... 1,5 mm²), 1x (0,5 ... 4 mm²)","network load class according to PROFINET":"1","transmission mode for Industrial Ethernet":"PROFINET with 100 Mbps full duplex (100BASE-TX)","number of interfaces according to PROFINET":"1","For Main Contacts With Screw-Type Terminals":"3 ... 4.5 N·m","Internal Resistance Of The Measuring Circuit":"10 mΩ","number of CO contacts for auxiliary contacts":"1","shock resistance according to IEC 60068-2-27":"sinusoidal half-wave 15g / 11 ms","Between The Voltage Supply And Other Circuits":"Yes","design of the interface Fast Ethernet interface":"Yes","vibration resistance according to IEC 60068-2-6":"1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g","For Auxiliary Contacts With Screw-Type Terminals":"0.6 ... 0.8 N·m","Mechanical Service Life (Operating Cycles) Typical":"10 000 000","Relative Temperature-Related Measurement Deviation":"0.5 %","electrostatic discharge according to IEC 61000-4-2":"6 kV contact discharge / 8 kV air discharge","Product Component Removable Terminal For Main Circuit":"No","Installation Altitude At Height Above Sea Level Maximum":"2 000 m","operating range factor supply voltage rated value at DC":"0.85 ... 1.15","product function at the 1st interface PROFINET IO device":"Yes","product function at the Ethernet interface Autocrossover":"Yes","Ampacity For Overcurrent Duration < 1 S Maximum Permissible":"1 A","Thermal Current Of The Switching Element With Contacts Maximum":"1 A","continuous current of the DIAZED fuse link of the output relay":"2 A","Electrical Endurance (Operating Cycles) For Relay Outputs Maximum":"100 000","Product Component Removable Terminal For Auxiliary And Control Circuit":"Yes"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":null,"alternativesUrl":"https://aoctrl.com/api/mcp/products/3UG5462-1AA41/alternatives.json"},"ai":{"faq":[{"question":"What is the measurable current range of the 3UG5462-1AA41?","answer":"The relay measures DC currents from -63 to +63 A, covering both directions of current flow."},{"question":"What compliance documentation is available for the 3UG5462-1AA41?","answer":"The relay meets EMC standards IEC 60947-1, IEC 61000-6-2, and IEC 61000-6-4. It carries the SIRIUS brand from Siemens. For specific RoHS/REACH/UL declarations, request the manufacturer's compliance documents with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3UG5462-1AA41","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3UG5462-1AA41 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}