{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-2ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-2ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-2ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-2ED32-0AA0, 3-pole molded case circuit breaker, 100 A rated continuous current, TM210 thermal-magnetic release, line protection design.","salesMarkdown":"## Siemens SENTRON 3VA1010-2ED32-0AA0 — 100 A MCCB, Line Protection, TM210 Release Its interrupting capacity reaches 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V — so at typical 400 V class distribution voltages, it handles fault currents up to 32 kA, which covers most secondary distribution panels. Thermal derating is minimal up to 50 °C — it holds full 100 A — then drops to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. Dimensions are 130 mm high, 76.2 mm wide, and 70 mm deep — a standard 3-pole MCCB footprint that drops into most Siemens SENTRON distribution panels and switchboard chassis without modification. Operating temperature range is -25 °C to 70 °C, storage from -40 °C to 80 °C — fine for most indoor industrial environments, but the upper operating limit matches the derating curve's endpoint, so don't expect full 100 A above 70 °C. For BOM freeze or PCN watch, the 3VA platform is Siemens' mainstream MCCB line, so replacements and upgrades tend to follow the same physical footprint and accessory ecosystem. If you need those features, you'd look at the 3VA1 with the appropriate suffix.","metaTitle":"Siemens 3VA1010-2ED32-0AA0 SENTRON MCCB, 100 A, 3-Pole, TM21","metaDescription":"Siemens 3VA1010-2ED32-0AA0 SENTRON molded case circuit breaker, 100 A rated, 3-pole, TM210 release, 52.5 kA at 240 V. Current production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VA1010-2ED32-0AA0","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","description":"Circuit breaker 3VA1 IEC Frame 100 Switching capacity class B Icu=16 kA @ 415 V 3-pole, system protection TM210, FTFM, In=100 A Overload protection Ir=100 A non-adjustable short-circuit protection Ii = 10 x In Lug terminal","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"B","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/aa698eb552e16b970e5de1a0df34f61a.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=217597&mlfb=3VA1010-2ED32-0AA0"},"ai":{"faq":[{"question":"What does the TM210 release designation mean?","answer":"TM210 means a thermal-magnetic release with a 100 A fixed thermal element (the '100' in the code) and an adjustable magnetic short-circuit pickup — standard for feeder protection where you set the magnetic threshold above motor inrush."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-2ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-2ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}