{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-2ED32-0DC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-2ED32-0DC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-2ED32-0DC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED32-0DC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-2ED32-0DC0, molded case circuit breaker, 3-pole, 100 A rated current Iu, TM210 thermal-magnetic release, 52.5 kA at 240 V, 70 mm depth.","salesMarkdown":"Breaking capacity runs 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V — so the interrupting rating you spec depends on your system voltage. Thermal derating is flat to 50 °C — still 100 A — then drops to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. Footprint is 76.2 mm wide, 130 mm tall, 70 mm deep — a standard 3-pole MCCB envelope that fits most DIN-rail or panel-mount backplates without re-drilling. Undervoltage release is present; no voltage-trip or ground-fault monitoring on this variant. ## What the TM210 release means This is the standard fixed-release design for line protection — no electronic adjustment, no communication function, just reliable electromechanical trip.","metaTitle":"Siemens 3VA1010-2ED32-0DC0 SENTRON MCCB, 100 A, 52.5 kA at 2","metaDescription":"Siemens SENTRON 3VA1010-2ED32-0DC0 molded case circuit breaker, 100 A rated, 52.5 kA breaking capacity at 240 V. TM210 release, 3-pole, 70 mm depth. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Product version":"Line protection","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"27.5 W","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","rated insulation voltage Ui":"800 V","Of The Supplied Basic Switch":"3VA10102ED320AA0","Courant permanent assigné Iu":"100 A","Ground-Fault Monitoring Version":"Without","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Neutral conductors / upgradeable/retrofittable":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"B","Max. rated operational current of the frame size":"100 A","Mechanical Service Life (Switching Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5 mm","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 1 mm"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=483799&mlfb=3VA1010-2ED32-0DC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED32-0DC0/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of 3VA1010-2ED32-0DC0 at different voltages?","answer":"Breaking capacity is 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V. Choose the rating that matches your system voltage."},{"question":"Where can I buy 3VA1010-2ED32-0DC0?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-2ED32-0DC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-2ED32-0DC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}