{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-2ED32-0HA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-2ED32-0HA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-2ED32-0HA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED32-0HA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens 3VA1 IEC Frame 100, circuit breaker, 3-pole, 100 A, switching capacity class B, Icu=16 kA @ 415 V, system protection TM210, FTFM, shunt release (STL) 12-30 V DC / 24 V AC.","salesMarkdown":"The Siemens 3VA1010-2ED32-0HA0 is a 3-pole IEC Frame 100 circuit breaker rated 100 A with a switching capacity class B interrupting capacity of 16 kA at 415 V. It is configured for system protection with a TM210 thermal-magnetic trip unit — fixed overload protection at Ir=100 A and fixed short-circuit protection at Ii = 10 × In (1000 A). This is a DIN-rail-mounting breaker sized for distribution panels and sub-distribution boards where the 16 kA SCCR at 415 V is sufficient for the fault level at the point of installation. The lug terminals accept standard copper conductors; no adapter kit needed for panel wiring. For a panel with a prospective fault current above 16 kA at the breaker's location, you would need a higher-capacity frame (class C or higher) or upstream current-limiting fuses to coordinate. The fixed Ir=100 A means this breaker is not field-adjustable for overload pickup — it is a dedicated 100 A thermal-magnetic unit. If the connected load draws less than 100 A continuously, the breaker still protects at its fixed rating; if the load is expected to exceed 100 A, select a higher-rated frame. The fixed Ii=1000 A (10 × In) short-circuit pickup is suitable for motor circuits where the inrush may reach 6-8× FLA, but verify coordination with downstream branch devices. The shunt release coil draws power only during the trip command — it is not continuously energized. The 12-30 V DC / 24 V AC control voltage range covers common industrial control voltages; verify the control transformer or DC supply matches the coil rating before wiring.","metaTitle":"Siemens 3VA1010-2ED32-0HA0 Circuit Breaker, 100 A, 16 kA","metaDescription":"Siemens 3VA1010-2ED32-0HA0 circuit breaker, IEC Frame 100, 3-pole, 100 A, Icu=16 kA @ 415 V. Current lifecycle stage. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"lifecycle_stage":"current"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=495078&mlfb=3VA1010-2ED32-0HA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED32-0HA0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of this breaker?","answer":"The interrupting capacity Icu is 16 kA at 415 V AC, switching capacity class B per IEC 60947-2."},{"question":"How do I get pricing and availability for 3VA1010-2ED32-0HA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time."},{"question":"What is the closest alternative to this breaker in the same family?","answer":"Within the 3VA1 frame, the closest variant would differ by trip unit type (adjustable thermal vs fixed), shunt release voltage, or terminal style (box lug vs ring lug). No pin-compatible direct drop-in exists with identical fixed settings — verify the trip curve and accessory voltage before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-2ED32-0HA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-2ED32-0HA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}