{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-2ED32-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-2ED32-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-2ED32-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED32-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-2ED32-0JA0, molded case circuit breaker, 3-pole, 100 A, line protection, TM210 thermal-magnetic release, 52.5 kA at 240 V.","salesMarkdown":"The Siemens SENTRON 3VA1010-2ED32-0JA0 is a 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current at 40 °C — that's the full rating up to 50 °C, then it derates to 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. For a panel that runs warm, the 100 A frame still holds up in a 50 °C ambient without derating, which is where many breakers start to lose headroom. The interrupting ratings are 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — so at 415 V it handles a 32 kA fault, which covers most industrial distribution panels fed from a 1 MVA transformer. Mounts in a standard distribution panel or motor control center; the 76.2 mm width (3-pole frame) and 70 mm depth fit the SENTRON 3VA family footprint. The shunt trip (STL) auxiliary release is built in, so you can remotely trip the breaker from an emergency-stop circuit or a PLC output without adding an external undervoltage coil. No auxiliary contact version means you'll need a separate 3VA9688-0BL32 auxiliary trip block if you want a status feedback signal back to the controller.","metaTitle":"Siemens 3VA1010-2ED32-0JA0 SENTRON MCCB, 100 A, 3-Pole, Line","metaDescription":"Siemens 3VA1010-2ED32-0JA0 SENTRON molded case circuit breaker, 100 A rated continuous, 3-pole, line protection, TM210 release, 52.5 kA at 240 V. Active production. Quoted to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"Without","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"1 000 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"0","Protective function of the overcurrent release":"LI","Switching capacity class of the circuit breaker":"B","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=6932&mlfb=3VA1010-2ED32-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED32-0JA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1010-2ED32-0JA0?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings for 3VA1010-2ED32-0JA0?","answer":"Rated continuous current 100 A, 3-pole, interrupting 52.5 kA at 240 V / 32 kA at 415 V / 13.6 kA at 440 V / 7.5 kA at 690 V, TM210 thermal-magnetic release, shunt trip, IP40 front."},{"question":"Will 3VA1010-2ED32-0JA0 drop into a panel built for 3VA1010-2ED42-0AE0?","answer":"Yes — both are 3-pole, 100 A frame, same 76.2 mm width and 70 mm depth. The difference is the interrupting rating: the 2ED42-0AE0 carries a higher kA rating at certain voltages. If the panel's fault current is within the 2ED32-0JA0's ratings, it's a direct mechanical fit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-2ED32-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-2ED32-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}