{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-2ED32-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-2ED32-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-2ED32-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED32-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-2ED32-0JC0, molded case circuit breaker, 3-pole, 100 A, TM210 thermal-magnetic release, 52.5 kA at 240 V, 70 mm depth.","salesMarkdown":"The Siemens SENTRON 3VA1010-2ED32-0JC0 is a 3-pole molded case circuit breaker rated for 100 A continuous at 40 °C, with the TM210 thermal-magnetic release handling overload and short-circuit protection in a single device. That 100 A holds flat through 50 °C — only starts tapering at 55 °C (96 A), hitting 90 A at 70 °C, so in a warm panel you still have headroom. Breaking capacity runs 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V — enough for most industrial distribution boards on the secondary side of a 500 kVA transformer. It ships with a factory-fitted shunt trip (STL) release (order code 3VA9688-0BL32 for the integrated auxiliary trip assembly) and two HQ auxiliary switches, so you get remote tripping and status feedback without adding an external module. The 3VA1010-2ED32-0JC0 measures 130 mm high, 76.2 mm wide (standard 3-pole MCCB footprint), and 70 mm deep — fits a 200 mm deep enclosure with room for rear-mounted busbars or a DIN-rail adapter. Spring-cage terminals on the line and load sides accept copper conductors up to the rated cross-section for 100 A; torque to the values stamped on the device nameplate.","metaTitle":"Siemens 3VA1010-2ED32-0JC0 SENTRON MCCB, 100 A, 52.5 kA","metaDescription":"Siemens SENTRON 3VA1010-2ED32-0JC0 molded case circuit breaker, 100 A rated, TM210 release, 52.5 kA at 240 V. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"1 000 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"B","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=160438&mlfb=3VA1010-2ED32-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED32-0JC0/alternatives.json"},"ai":{"faq":[{"question":"How do I get pricing and availability for 3VA1010-2ED32-0JC0?","answer":"Submit an RFQ through the storefront. Availability and current pricing are confirmed at quote time through independent distribution channels."},{"question":"What is the closest functional alternative to 3VA1010-2ED32-0JC0?","answer":"The 3VA1010-2ED32-0JA0 is the same 100 A, 3-pole, TM210 MCCB but without the factory-fitted shunt trip and auxiliary switches. If you need remote tripping and status feedback, the -0JC0 variant saves panel wiring labor versus adding those accessories later."},{"question":"What are the key ratings for 3VA1010-2ED32-0JC0?","answer":"Rated continuous current 100 A (flat to 50 °C, derated above). Breaking capacity 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, 7.5 kA at 690 V. Rated insulation voltage 800 V. TM210 thermal-magnetic release with shunt trip and 2 HQ auxiliary switches."},{"question":"What compliance documentation does Siemens provide for this MCCB?","answer":"The SENTRON 3VA series carries IEC 60947-2 certification for molded case circuit breakers. Siemens provides a declaration of conformity and, on request, the full test report. RoHS and REACH compliance declarations are available through the Siemens Industry Online Support portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-2ED32-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-2ED32-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}