{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-2ED32-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-2ED32-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-2ED32-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED32-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-2ED32-0JH0, 3-pole molded case circuit breaker, 100 A rated continuous current, TM210 thermal-magnetic trip, line protection version, breaking capacity 52.5 kA at 240 V AC.","salesMarkdown":"It is a 3-pole, line-protection version, meaning it's built for feeder and distribution circuits where you need to protect cables and busbars, not motor loads with their inrush curves. ## Breaking capacity — what the voltages tell you This breaker clears 52.5 kA at 240 V AC, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V. At 690 V you're limited to 7.5 kA, so check your transformer size and cable run before committing. Above that it starts to walk down: 96 A at 55 °C, 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. That's the practical number for sizing, not the nameplate. ## Auxiliary contacts and shunt trip — what's on board The shunt trip is part number 3VA9688-0BL32 if you ever need a replacement. No communication function onboard, so if remote monitoring is needed you'd add an external module or a separate power meter. It has a trip indicator (mechanical flag) so you can see at a glance whether the breaker tripped on fault vs. being manually switched off — useful when you're walking a row of breakers after a nuisance trip. The voltage trigger refers to the shunt trip release: apply voltage to that coil and the breaker opens remotely, which is how you'd integrate it with an emergency-stop circuit or a PLC-driven shutdown sequence.","metaTitle":"Siemens 3VA1010-2ED32-0JH0 SENTRON MCCB, 100A, 52.5kA at 240","metaDescription":"Siemens 3VA1010-2ED32-0JH0 SENTRON molded case circuit breaker, 3-pole, 100A rated, TM210 trip, 52.5kA at 240V breaking capacity. Active production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"Yes","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches + 1 trip alarm switch HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL32","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"1 000 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"3","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching capacity class of the circuit breaker":"B","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=348011&mlfb=3VA1010-2ED32-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED32-0JH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the 3VA1010-2ED32-0JH0 and get a price?","answer":"This part is sourced to order against an RFQ through independent distribution. Submit a request for current pricing and availability — confirmed at quote time."},{"question":"What is the 3VA1010-2ED32-0JH0's breaking capacity at 240 V?","answer":"It clears 52.5 kA at 240 V AC, 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 690 V."},{"question":"Does this breaker include a shunt trip?","answer":"Yes, it comes with a factory-fitted shunt trip release (STL) for remote tripping. The auxiliary contact configuration is 2 auxiliary switches plus 1 trip alarm switch (HQ)."},{"question":"What are the physical dimensions of the 3VA1010-2ED32-0JH0?","answer":"Depth 70 mm, width 76.2 mm, height 130 mm. Front IP40 protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-2ED32-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-2ED32-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}