{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-2ED32-0KC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-2ED32-0KC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-2ED32-0KC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED32-0KC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-2ED32-0KC0, 3-pole molded case circuit breaker, 100 A at 40 °C, breaking capacity 52.5 kA at 240 V AC, line protection design with shunt trip (STL) and 2 auxiliary switches HQ.","salesMarkdown":"Breaking capacity is 52.5 kA at 240 V AC, dropping to 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at 500/690 V. That 52.5 kA at 240 V covers high-fault service-entrance applications; the 7.5 kA at 690 V still handles most motor-circuit fault levels on 690 V industrial networks. Maximum power loss is 25 W — a figure to factor into enclosure thermal calculations when grouping multiple breakers. ## Built-in accessories and integration Dimensions are 130 mm height, 76.2 mm width (3 in), 70 mm depth — a standard SENTRON 3VA1 footprint that drops into existing panel cutouts and busbar systems without re-drilling. The basic switch core is order code 3VA10102ED320AA0, so replacement of the switching mechanism alone is possible if the accessory tray is reused. The breaker has no communication function or trip indicator — it is a straightforward thermal-magnetic line-protection device, not a metering or smart breaker.","metaTitle":"Siemens 3VA1010-2ED32-0KC0 SENTRON MCCB, 100A, 52.5kA at 240","metaDescription":"Siemens 3VA1010-2ED32-0KC0 SENTRON molded case circuit breaker, 3-pole, 100A rated at 40°C, 52.5kA breaking capacity at 240V AC. Line protection design with shunt trip. Active prod","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10102ED320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL33","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"B","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=197968&mlfb=3VA1010-2ED32-0KC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED32-0KC0/alternatives.json"},"ai":{"faq":[{"question":"What accessories are built into 3VA1010-2ED32-0KC0?","answer":"It includes a shunt trip (STL) for remote tripping and two auxiliary switches (HQ) for status indication. No undervoltage release or ground-fault monitoring is fitted."},{"question":"Will 3VA1010-2ED32-0KC0 fit in a panel designed for 3VA1010-2ED32-0DC0?","answer":"Yes — both share the same SENTRON 3VA1 footprint: 130 mm height, 76.2 mm width, 70 mm depth. The difference is in the built-in accessories (shunt trip vs. other release types), not the mounting or busbar interface."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-2ED32-0KC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-2ED32-0KC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}