{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-2ED36-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-2ED36-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-2ED36-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED36-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-2ED36-0AA0, molded case circuit breaker (MCCB), 3-pole, 100 A rated continuous current, TM210 thermal-magnetic overcurrent release, line protection design, breaking capacity 52.5 kA at 240 V AC.","salesMarkdown":"Breaking capacity is 52.5 kA at 240 V AC, dropping to 32 kA at 415 V and 13.6 kA at 440 V. Thermal derating is minimal up to 50 °C — still 100 A. At 55 °C it drops to 98 A, at 65 °C to 94 A, and at 70 °C to 91 A. For a panel with a 40 °C ambient design target, you get full rating; if the panel runs hot (say 55 °C inside a non-ventilated enclosure), you lose only 2 A. That keeps the wire sizing simple. ## What you don't get — and why that matters for BOM accuracy The design is strictly line protection — overcurrent and short-circuit only. If your spec calls for remote tripping or ground-fault alarm, you need a different 3VA suffix (e.g., a -2ED36-0AC0 with the UVR option, or a -2ED32-0AD0 with a different trip curve). The 3VA1010-2ED36-0AA0 is a pure thermal-magnetic breaker with no auxiliary electronics. Compared to the 3VA1010-2ED32-0AD0, the -2ED36-0AA0 shares the same frame, pole count, and 100 A rating but uses the TM210 release instead of the TM240. The -2ED32-0AD0 has a different trip-threshold curve; swapping one for the other changes the coordination study. Depth of 70 mm (2.76 in) leaves room for rear bus bars or a gland plate behind the breaker. Maximum power loss is 25 W at rated current. In a sealed, non-ventilated enclosure with multiple breakers, factor that into the thermal budget — a 4-breaker panel dissipates 100 W just from these MCCBs. Suitable for unheated warehouses or outdoor enclosures in moderate climates, provided the ambient inside the enclosure stays within the derating curve.","metaTitle":"Siemens 3VA1010-2ED36-0AA0 SENTRON MCCB, 100 A, 3-Pole, TM21","metaDescription":"Siemens 3VA1010-2ED36-0AA0 SENTRON molded case circuit breaker. 100 A continuous, 3-pole, TM210 release. Breaking capacity 52.5 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VA1010-2ED36-0AA0","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","description":"Circuit breaker 3VA1 IEC Frame 100 Switching capacity class B Icu=16 kA @ 415 V 3-pole, system protection TM210, FTFM, In=100 A Overload protection Ir=100 A non-adjustable short-circuit protection Ii = 10 x In Terminal connection","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"B","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1f5e98e4c4ff189bd4bd3d3a3f9bda51.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=138250&mlfb=3VA1010-2ED36-0AA0"},"ai":{"faq":[{"question":"Where can I buy 3VA1010-2ED36-0AA0 and how do I get a price?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time."},{"question":"Will 3VA1010-2ED36-0AA0 drop into a panel specified around 3VA1010-2ED32-0AD0 without rewiring?","answer":"Yes, physically it fits — same 70 mm depth, 76.2 mm width, 130 mm height, same 3-pole frame. No bus-bar or mounting-hole changes needed. However, the TM210 release has a different trip curve than the TM240 on the -2ED32-0AD0, so the coordination study must be rechecked."},{"question":"What is the breaking capacity of 3VA1010-2ED36-0AA0 at 480 V?","answer":"At 440 V it is rated 13.6 kA; at 500 V, 7.5 kA. For a 480 V system, the 440 V rating (13.6 kA) is the applicable conservative figure — the breaker will interrupt fault currents up to that level at 480 V."},{"question":"Does 3VA1010-2ED36-0AA0 include ground-fault protection or communication?","answer":"No. This variant has no ground-fault monitoring, no communication function, no undervoltage release, and no trip indicator. It is a pure thermal-magnetic line-protection breaker — overcurrent and short-circuit only."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-2ED36-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-2ED36-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}