{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-2ED36-0JC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-2ED36-0JC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-2ED36-0JC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED36-0JC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-2ED36-0JC0, 3-pole molded case circuit breaker, 100 A rated current, 52.5 kA breaking capacity at 240 V AC, line protection design with integrated shunt trip and auxiliary switches.","salesMarkdown":"The 3VA1010-2ED36-0JC0: Breaking capacity runs 52.5 kA at 240 V AC, dropping to 32 kA at 415 V, 13.6 kA at 440 V, and 7.5 kA at both 500 V and 690 V. That covers most industrial supply voltages; the 690 V rating matters for 600 V class panels common in North American heavy industry. Thermal derating is mild: holds 100 A from 40 °C through 50 °C, then steps down to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. For a panel running at 50 °C ambient — typical for a closed electrical room — you get full 100 A without downsizing the breaker. ## Built-in auxiliary hardware saves panel space That saves a DIN-rail position and cuts wiring time. The auxiliary switches report position back to the controller or status lamp. Standard 3-pole MCCB footprint — drops into the same panel cutout as other SENTRON 3VA1 frames. Maximum power loss is 25 W at full load — accounts for in panel thermal calculations. ## Lifecycle and sourcing: active, no LTB pressure The base switch assembly (3VA10102ED360AA0) is the core; the -0JC0 suffix adds the shunt trip and auxiliary switches as factory-installed options. No field retrofitting required.","metaTitle":"Siemens 3VA1010-2ED36-0JC0 SENTRON MCCB, 100A, 52.5kA at 240","metaDescription":"Siemens 3VA1010-2ED36-0JC0 SENTRON 3-pole molded case circuit breaker, 100A rated current, 52.5kA breaking capacity at 240V AC. Line protection with integrated shunt trip and auxil","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10102ED360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"B","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=234364&mlfb=3VA1010-2ED36-0JC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED36-0JC0/alternatives.json"},"ai":{"faq":[{"question":"What compliance documentation does this breaker carry?","answer":"As a current-production SENTRON MCCB, it carries UL/CSA/CE/IEC certifications standard for the series. Specific RoHS/REACH declarations available with the order documentation."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-2ED36-0JC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-2ED36-0JC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}