{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-2ED36-0JH0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-2ED36-0JH0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-2ED36-0JH0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED36-0JH0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-2ED36-0JH0, 3-pole molded case circuit breaker, 100 A rated current, 52.5 kA breaking capacity at 240 V AC, line protection design with shunt trip and auxiliary switches.","salesMarkdown":"## Breaking capacity across voltages — where it fits The 3VA1010-2ED36-0JH0: This MCCB delivers 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, and holds 7.5 kA at both 500 V and 690 V. That 52.5 kA at 240 V is the headline number — it's built for high-fault panels on 240 V line-to-line or 240/120 V split-phase services where upstream transformer capacity is substantial. ## Thermal derating — don't guess the real ampacity Rated 100 A from 40 °C through 50 °C ambient, then it tapers: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. If your panel internal temperature runs hot — say a sealed enclosure near a motor drive — you lose 9 A off the nameplate by 70 °C. That's a 9% derate; plan your load wiring and upstream protection accordingly. ## Built-in accessories — shunt trip and auxiliary switches That means you can wire it for remote shutdown from a safety PLC or E-stop circuit without adding an external shunt trip accessory later. The auxiliary switches give you status feedback — open/closed and tripped — back to the control system. Measures 130 mm high, 76.2 mm wide, 70 mm deep — a standard 3-pole MCCB footprint that fits most DIN-rail or screw-mounted panel layouts.","metaTitle":"Siemens 3VA1010-2ED36-0JH0 SENTRON MCCB, 100A, 52.5kA at 240","metaDescription":"Siemens SENTRON 3VA1010-2ED36-0JH0 molded case circuit breaker, 3-pole, 100A, 52.5kA breaking capacity at 240V AC. Current production. Sourced to order. Request quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10102ED360AA0","Design Of The Auxiliary Switch":"2 auxiliary switches + 1 trip alarm switch HQ","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"3","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"B","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"box terminal on both sides","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=70746&mlfb=3VA1010-2ED36-0JH0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED36-0JH0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1010-2ED36-0JH0 and how do I get a price?","answer":"This part is sourced to order through independent industrial distribution. Submit an RFQ for current pricing and availability — both are confirmed at quote time. No stock count or price is published here because both fluctuate with market conditions."},{"question":"What is the breaking capacity of 3VA1010-2ED36-0JH0 at 240 V?","answer":"52.5 kA at 240 V AC. At 415 V it clears 32 kA, at 440 V it's 13.6 kA, and at both 500 V and 690 V it holds 7.5 kA."},{"question":"Does 3VA1010-2ED36-0JH0 include a shunt trip or auxiliary contacts?","answer":"Yes, it comes factory-fitted with a shunt trip (STL) release for remote tripping, plus two auxiliary switches and one trip alarm switch (HQ). No external accessory kit needed for remote shutdown or status feedback."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-2ED36-0JH0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-2ED36-0JH0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}