{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-2ED36-0KC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-2ED36-0KC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-2ED36-0KC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED36-0KC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-2ED36-0KC0, Molded case circuit breaker, 3-pole, 100 A, TM210 release, 52.5 kA at 240 V, 32 kA at 415 V, 2 auxiliary switches HQ, shunt trip STL.","salesMarkdown":"The shunt trip order code is 3VA9688-0BL33 — order that separately if remote trip is needed. Derating begins at 55 °C (96 A), then 94 A at 60 °C, 92 A at 65 °C, and 90 A at 70 °C. Mounting in a sealed, non-ventilated enclosure will raise internal ambient — account for that when loading the breaker near its nameplate. ## Mechanical fit and auxiliary wiring The 3-pole width of 76.2 mm is standard for this frame size — it drops into the same DIN-rail or screw-mount footprint as other 3VA10 frame breakers. The two HQ auxiliary switches are wired via the integrated terminal block; no external add-on module needed for basic N/O and N/C status. Mechanical endurance rated at 15,000 operations — typical for a distribution MCCB not cycled daily.","metaTitle":"Siemens 3VA1010-2ED36-0KC0 SENTRON MCCB, 100 A, 3-Pole, 52.5","metaDescription":"Siemens 3VA1010-2ED36-0KC0 SENTRON molded case circuit breaker, 100 A rated current, 3-pole, interrupting ratings up to 52.5 kA at 240 V. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL33","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"1 000 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"B","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"box terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, round conductor terminal, stranded":"1 x (1.5 - 70 mm²)"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=268648&mlfb=3VA1010-2ED36-0KC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED36-0KC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1010-2ED36-0KC0 and get a price?","answer":"This part is sourced and quoted to order through independent distribution. Submit an RFQ; availability and current pricing are confirmed at quote time."},{"question":"Will 3VA1010-2ED36-0KC0 drop into a panel specified for 3VA1010-2ED42-0AE0 without rewiring?","answer":"The 3VA10 frame shares the same 76.2 mm width and overall footprint, so mechanical fit is identical. However, the 2ED42-0AE0 variant carries a different release and interrupting rating — verify the release type and trip settings before substituting. The wiring terminals and auxiliary contact positions are the same across the frame."},{"question":"What are the key ratings for 3VA1010-2ED36-0KC0?","answer":"Rated continuous current 100 A, 3-pole, TM210 thermal-magnetic release. Interrupting capacity: 52.5 kA at 240 V, 32 kA at 415 V, 13.6 kA at 440 V, 7.5 kA at 690 V. Rated insulation voltage 800 V. Operating ambient -25 °C to +70 °C."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-2ED36-0KC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-2ED36-0KC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}