{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-2ED42-0DC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-2ED42-0DC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-2ED42-0DC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED42-0DC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-2ED42-0DC0, molded case circuit breaker, 4-pole, line protection, 100 A at 40 °C, 52.5 kA interrupting at 240 V, undervoltage release, 2 auxiliary switches HQ.","salesMarkdown":"The Siemens 3VA1010-2ED42-0DC0 is a SENTRON molded case circuit breaker (MCCB) for line protection, rated 100 A at 40 °C across four poles. It interrupts fault currents up to 52.5 kA at 240 V AC — enough headroom for most industrial service-entrance or feeder applications where the available fault current is high. The 800 V rated insulation voltage (Ui) means it can sit on a 480 V or 600 V panel bus without derating the dielectric clearance. The 70 mm depth and 101.6 mm width fit standard MCCB panel cutouts; it's a direct swap for other 4-pole SENTRON 3VA devices of the same frame size. No communication module on board — this is a standalone thermal-magnetic or electronic-trip unit for hardwired distribution.","metaTitle":"Siemens 3VA1010-2ED42-0DC0 SENTRON MCCB, 100 A, 4-pole, 52.5","metaDescription":"Siemens SENTRON 3VA1010-2ED42-0DC0 molded case circuit breaker, 100 A, 4-pole, 52.5 kA interrupting at 240 V. Active production, sourced to order. Request a quote.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"27.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10102ED420AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"without","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB25","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"B","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=13755&mlfb=3VA1010-2ED42-0DC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED42-0DC0/alternatives.json"},"ai":{"faq":[{"question":"What are the key ratings of 3VA1010-2ED42-0DC0?","answer":"It is a 4-pole SENTRON MCCB rated 100 A at 40 °C, with an interrupting capacity of 52.5 kA at 240 V AC and 32 kA at 415 V AC. Rated insulation voltage is 800 V. It includes an undervoltage release and two auxiliary switches."},{"question":"Where can I buy 3VA1010-2ED42-0DC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the closest functional second-source for 3VA1010-2ED42-0DC0?","answer":"The 3VA1010-2ED32-0DC0 is a 3-pole variant of the same frame — same interrupting ratings and current class, but one pole fewer. It will not drop into a 4-pole panel without rewiring the neutral or third-phase path. For a 4-pole replacement, stick with the -2ED42- suffix."},{"question":"What compliance documentation does this brand provide for 3VA1010-2ED42-0DC0?","answer":"Siemens provides RoHS and REACH declarations, plus UL and IEC certification documentation for the SENTRON 3VA series. Specific certificates are available on request."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-2ED42-0DC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-2ED42-0DC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}