{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-2ED42-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-2ED42-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-2ED42-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED42-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA series, molded case circuit breaker (MCCB), 3VA1010-2ED42-0JA0, 100 A, 4-pole, TM210 thermal-magnetic release, shunt trip (STL), 52.5 kA at 240 V.","salesMarkdown":"## Siemens SENTRON 3VA1010-2ED42-0JA0 — 100 A MCCB with Shunt Trip The Siemens SENTRON 3VA1010-2ED42-0JA0 is a 4-pole molded case circuit breaker (MCCB) rated for line protection, carrying 100 A continuously at 40 °C ambient with no derating needed up to 50 °C. Its TM210 thermal-magnetic release provides fixed overload and short-circuit protection, while the integrated shunt trip (STL) allows remote tripping via a separate control voltage — useful for emergency-stop or interlock circuits where you need to drop the load without opening the main disconnect. Rated breaking capacity reaches 52.5 kA at 240 V, 32 kA at 415 V, and 13.6 kA at 440 V — figures that cover most industrial distribution panels fed from a typical 400 V transformer. At 500 V and 690 V the rating holds at 7.5 kA, so this breaker can serve as a main or branch device in 480 V and 600 V class systems where the available fault current stays within that limit. Current rating holds flat at 100 A from 40 °C through 50 °C, then derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. Maximum power loss is 25 W at rated load — a figure to include in enclosure thermal calculations, especially in sealed or high-ambient panels. Dimensions are 130 mm height, 101.6 mm width, and 70 mm depth — a standard 4-pole MCCB footprint that mounts on a DIN rail or panel-mount base. No trip indicator is fitted on this variant; the voltage-triggered shunt trip coil is the only auxiliary release.","metaTitle":"Siemens 3VA1010-2ED42-0JA0 SENTRON MCCB, 100A, 4-Pole, Shunt","metaDescription":"Siemens SENTRON 3VA1010-2ED42-0JA0 molded case circuit breaker, 100A rated at 40°C, 4-pole, 52.5 kA at 240 V. TM210 release, shunt trip. Active production, quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"101.6 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"52.5 kA","at 415 V":"32 kA","at 440 V":"13.6 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"4 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"4","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10102ED420AA0","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","design of the N-conductor protection":"without","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"600 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"B","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=191345&mlfb=3VA1010-2ED42-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-2ED42-0JA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1010-2ED42-0JA0 and how is it quoted?","answer":"This part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at the time of quotation — no stock or price figures are published here."},{"question":"What is the breaking capacity of 3VA1010-2ED42-0JA0 at 415 V?","answer":"The rated breaking capacity at 415 V is 32 kA. At 240 V it is 52.5 kA, and at 440 V it is 13.6 kA."},{"question":"What type of overcurrent release does this MCCB use?","answer":"It uses a TM210 thermal-magnetic release — fixed thermal and magnetic trip settings, not adjustable. The shunt trip (STL) is a separate auxiliary release for remote tripping."},{"question":"Will 3VA1010-2ED42-0JA0 fit in a panel designed for 3VA1010-2ED32-0AD0?","answer":"Both share the same SENTRON 3VA frame size and identical mounting dimensions (130 mm height, 101.6 mm width, 70 mm depth), so the physical footprint is interchangeable. The difference is in the release configuration — this variant has a shunt trip and a TM210 release, while the -2ED32-0AD0 has a different release variant. Verify the auxiliary wiring before drop-in replacement."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-2ED42-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-2ED42-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}