{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-3ED32-0AA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-3ED32-0AA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-3ED32-0AA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED32-0AA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-3ED32-0AA0, 3-pole molded case circuit breaker, 100 A continuous, TM210 release, 75.6 kA interrupting at 240 V, line protection design.","salesMarkdown":"## What the 75.6 kA interrupting rating means for your panel The Siemens 3VA1010-3ED32-0AA0 is a SENTRON 3-pole molded case circuit breaker (MCCB) rated for 100 A continuous current and a maximum interrupting capacity of 75.6 kA at 240 V AC. At 415 V it still handles 52.5 kA, and at 440 V it drops to 32 kA, so the voltage on your line determines how much fault current this breaker can interrupt. The TM210 overcurrent release is a thermal-magnetic trip unit — thermal for overload protection (the bimetal curve), magnetic for short-circuit instant trip. This is line-protection design, meaning it's intended for feeder or distribution circuits, not motor-starting duty where you'd want a motor-protective breaker with adjustable magnetic pickup. If you're protecting a motor branch, you'd want a different release type; for a panel feeder or a sub-distribution board, the TM210 is the right fit. ## Thermal derating — what the 100 A rating actually delivers Above that, the breaker derates: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. That derating curve is built into the thermal-magnetic release, so you don't have to apply an external factor; the breaker's own bimetal will respond to the ambient temperature and trip earlier. At 76.2 mm wide, 130 mm tall, and 70 mm deep, this MCCB fits a standard 3-pole MCCB footprint on a DIN rail or panel-mount base.","metaTitle":"Siemens 3VA1010-3ED32-0AA0 SENTRON MCCB, 100 A, 75.6 kA","metaDescription":"Siemens SENTRON 3VA1010-3ED32-0AA0 molded case circuit breaker, 3-pole, 100 A continuous, 75.6 kA at 240 V. TM210 release. Current production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","title":"3VA1010-3ED32-0AA0","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","description":"Circuit breaker 3VA1 IEC Frame 100 Switching capacity class N Icu=25 kA @ 415 V 3-pole, system protection TM210, FTFM, In=100 A Overload protection Ir=100 A non-adjustable short-circuit protection Ii = 10 x In Lug terminal","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Ground-Fault Monitoring Version":"Without","Continuous Current / Rated Value":"100 A","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Continuous Current / Rated Value / Maximum":"100 A","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$106.68","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f89be7fa306fd10d0feb83be4c2dba48.pdf","sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=95837&mlfb=3VA1010-3ED32-0AA0"},"ai":{"faq":[{"question":"Where can I buy the 3VA1010-3ED32-0AA0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What is the interrupting rating at 240 V?","answer":"75.6 kA at 240 V AC. At 415 V it's 52.5 kA, at 440 V it's 32 kA, and at 500 V or 690 V it's 7.5 kA."},{"question":"Does the 3VA1010-3ED32-0AA0 have a shunt trip or undervoltage release?","answer":"No. This variant has no undervoltage release, no shunt trip, no communication function, and no ground-fault monitoring. It's a straight thermal-magnetic breaker for line protection."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-3ED32-0AA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-3ED32-0AA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}