{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-3ED32-0AF0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-3ED32-0AF0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-3ED32-0AF0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED32-0AF0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON molded case circuit breaker, 3VA1010-3ED32-0AF0, 3-pole, 100 A at 40 °C, TM210 thermal-magnetic release, 75.6 kA interrupting at 240 V, line protection design.","salesMarkdown":"Interrupting capacity hits 75.6 kA at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V, which gives you headroom for high-fault commercial and light industrial feeders. Insulation voltage is rated 800 V, so it can sit in 480/277 V or 400/230 V panels without derating the dielectric. Maximum power loss is 25 W, which is manageable for enclosed panels with basic ventilation. The auxiliary switch configuration (1 auxiliary + 1 trip alarm switch HQ) gives a dry contact for remote status or PLC input without needing an add-on module. Above that, it derates linearly: 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C. The interrupting ratings step down as voltage climbs: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V. The 3-pole body is the standard SENTRON 3VA width — it occupies three 25.4 mm pole spaces. Trip indicator is present, undervoltage release is not fitted.","metaTitle":"3VA1010-3ED32-0AF0 SENTRON MCCB, 100 A, 3-Pole, TM210","metaDescription":"Siemens SENTRON 3VA1010-3ED32-0AF0 molded case circuit breaker, 100 A at 40 °C, 3-pole, TM210 release, 75.6 kA at 240 V. Active production, sourced to order. Request RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"Yes","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10103ED320AA0","Design Of The Auxiliary Switch":"1 auxiliary switch + 1 trip alarm switch HQ","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AB12","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=121228&mlfb=3VA1010-3ED32-0AF0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED32-0AF0/alternatives.json"},"ai":{"faq":[{"question":"What is the interrupting capacity of 3VA1010-3ED32-0AF0 at 240 V?","answer":"75.6 kA at 240 V. At 415 V it is 52.5 kA, at 440 V it is 32 kA, and at 500 V and 690 V it is 7.5 kA."},{"question":"What does the TM210 release designation mean on this breaker?","answer":"TM210 is a thermal-magnetic overcurrent release. The 'TM' indicates thermal-magnetic trip mechanism; '210' is the specific trip-characteristic curve for the 100 A frame."},{"question":"Where can I buy 3VA1010-3ED32-0AF0 and how is it quoted?","answer":"This breaker is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"Will 3VA1010-3ED32-0AF0 drop into a panel specified around 3VA1110-5EE32-0LC0?","answer":"Both are 3-pole SENTRON 3VA frame breakers with the same 70 mm depth and 76.2 mm width, so the physical footprint is identical. The difference is in the release type and interrupting rating — verify coordination and trip curve before swapping."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-3ED32-0AF0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-3ED32-0AF0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}