{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-3ED32-0CC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-3ED32-0CC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-3ED32-0CC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED32-0CC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-3ED32-0CC0, molded case circuit breaker, 3-pole, 100 A (40 °C), line protection, 70 mm depth, 75.6 kA interrupting capacity at 240 V AC.","salesMarkdown":"It's rated 100 A continuous at 40 °C ambient, holds that rating through 50 °C, then derates to 98 A at 55 °C, 96 A at 60 °C, 94 A at 65 °C, and 91 A at 70 °C — useful if this breaker lands in a warm enclosure or near other heat sources. Interrupting capacity runs 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V — check your available fault current at the point of installation against the applicable voltage column. No ground-fault monitoring, no communication function, no trip indicator. The 70 mm depth is relatively shallow for a 100 A MCCB — helps when back-panel clearance is tight.","metaTitle":"Siemens 3VA1010-3ED32-0CC0 SENTRON MCCB, 100A, 3-Pole, 70mm","metaDescription":"Siemens 3VA1010-3ED32-0CC0 SENTRON molded case circuit breaker, 100A rated at 40°C, 3-pole, 70mm depth. Active production. Interrupting capacity 75.6kA at 240V. Sourced to order ag","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"No","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"Yes","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"27.5 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10103ED320AA0","Design Of The Auxiliary Switch":"2 auxiliary switches HQ","Design Of The Auxiliary Release":"undervoltage release (UVR)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9608-0BB24","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"2","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=46365&mlfb=3VA1010-3ED32-0CC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED32-0CC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1010-3ED32-0CC0?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time."},{"question":"What is the interrupting capacity of this MCCB?","answer":"75.6 kA at 240 V AC, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V AC."},{"question":"What are the physical dimensions of 3VA1010-3ED32-0CC0?","answer":"70 mm deep, 76.2 mm wide, 130 mm tall. Fits standard DIN-rail or panel-mount footprints for 3-pole MCCBs in this current class."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-3ED32-0CC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-3ED32-0CC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}