{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-3ED32-0JA0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-3ED32-0JA0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-3ED32-0JA0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED32-0JA0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-3ED32-0JA0, molded case circuit breaker, 3-pole, 100 A (40 °C), TM210 overcurrent release, shunt trip (STL), line protection, 70 mm depth.","salesMarkdown":"It carries a TM210 thermal-magnetic overcurrent release — the TM210 designation means the thermal fixed trip is set at 100 A (the full rated current) and the magnetic short-circuit pickup is 10× In (1000 A), making it a standard motor-branch or feeder breaker, not a high-magnetic version for transformer inrush. The shunt trip (STL) auxiliary release allows remote tripping via a separate control voltage, which is how this breaker integrates into an emergency-stop chain or a fire-safety loop. ## Breaking capacity — the real coordination figure This MCCB's interrupting capacity is voltage-dependent: 75.6 kA at 240 V, 52.5 kA at 415 V, 32 kA at 440 V, and 7.5 kA at both 500 V and 690 V. The steep drop above 440 V is typical of a compact-frame breaker — at 690 V the 7.5 kA figure limits it to low-fault applications (small transformers, secondary feeders) unless upstream current-limiting fuses or a larger-frame breaker provide backup protection. For a 415 V panel with a prospective fault current above 52.5 kA, this breaker needs a series-rated combination or a higher-interrupting variant from the 3VA family. Physical footprint is 130 mm tall, 76.2 mm wide (3 in), and 70 mm deep (2.76 in). The 3-pole width matches standard Siemens 3VA fixed- and plug-in-base mounting, so it swaps directly into existing SENTRON panel layouts without bus-bar rework.","metaTitle":"Siemens 3VA1010-3ED32-0JA0 SENTRON MCCB, 100A, 3-Pole, Shunt","metaDescription":"Siemens 3VA1010-3ED32-0JA0 SENTRON molded case circuit breaker, 100A rated at 40°C, 3-pole, 70mm depth, with TM210 release and shunt trip. Breaking capacity 75.6kA at 240V. Active","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","Maximum":"0 A","Minimum":"0 A","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 500 V":"7.5 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"98 A","at 60 °C":"96 A","at 65 °C":"94 A","at 70 °C":"91 A","Depth [In]":"2.76 in","Width [In]":"3 in","Height [In]":"5.12 in","Trip Indicator":"No","Number Of Poles":"3","Voltage Trigger":"Yes","lifecycle_stage":"current","Product Brand Name":"SENTRON","Product Designation":"Molded case circuit breaker","Undervoltage Release":"No","Design Of The Product":"Line protection","Communication Function":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","power loss [W] / maximum":"25 W","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Of The Supplied Basic Switch":"3VA10103ED320AA0","Design Of The Auxiliary Release":"shunt trip (STL)","Ground-Fault Monitoring Version":"Without","Insulation Voltage / Rated Value":"800 V","Design Of The Overcurrent Release":"TM210","Design Of Short-Circuit Protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","protection class IP / on the front":"IP40","Of The Integrated Auxiliary Trip Unit":"3VA9688-0BL32","Product Function / Grounding Protection":"No","operating voltage / at AC / rated value":"690 V","operating voltage / at DC / rated value":"500 V","reference code / according to IEC 81346-2":"Q","Product Extension / Optional / Motor Drive":"No","Protection Function Of The Overcurrent Release":"LI","number of CO contacts / for auxiliary contacts":"0","Switching Capacity Class Of The Circuit Breaker":"N","Mechanical Service Life (Operating Cycles) / Typical":"20 000","Type Of Electrical Connection / For Main Current Circuit":"nut keeper kit on both ends","Arrangement Of Electrical Connectors / For Main Current Circuit":"Front terminal"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=59968&mlfb=3VA1010-3ED32-0JA0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED32-0JA0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1010-3ED32-0JA0 and how is it quoted?","answer":"It is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"Will 3VA1010-3ED32-0JA0 drop into a panel specified for 3VA1110-5EF32-0LA0?","answer":"Both are 3-pole SENTRON MCCBs on the same 76.2 mm width and 130 mm height footprint, so the physical mounting and bus-bar connections are identical. The difference is in the release: this unit uses a TM210 thermal-magnetic release, while the 3VA1110 variant uses an electronic release — the wiring for the shunt trip and auxiliary contacts is the same."},{"question":"What compliance documentation does Siemens provide for 3VA1010-3ED32-0JA0?","answer":"As a current-production SENTRON MCCB, it carries IEC 60947-2 certification and is designed to meet UL 489 requirements. Siemens provides a declaration of conformity (CE/UKCA) and RoHS/REACH compliance documentation with the shipment."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-3ED32-0JA0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-3ED32-0JA0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}