{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"3VA1010-3ED32-0KC0","brand":"Siemens","brandSlug":"siemens","productSlug":"3VA1010-3ED32-0KC0","canonicalUrl":"https://aoctrl.com/siemens/3VA1010-3ED32-0KC0","factsUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED32-0KC0","rawCanonicalId":null},"summary":{"shortDescription":"Siemens SENTRON 3VA1010-3ED32-0KC0, 3-pole molded case circuit breaker, 100 A rated continuous current, TM210 thermal-magnetic overcurrent release, 75.6 kA interrupting at 240 V, 70 mm depth × 76.2 mm width × 130 mm height, IP40 front protection, with shunt trip and 2 auxiliary switches.","salesMarkdown":"It carries a 75.6 kA interrupting capacity at 240 V, 52.5 kA at 415 V, and 32 kA at 440 V — numbers that tell you it handles high-fault utility feeds or transformer secondaries without cascading upstream breakers. Rated insulation voltage is 800 V, and the frame holds the full 100 A from 40 °C up through 50 °C without derating; at 55 °C it's 96 A, at 60 °C it's 94 A, and at 70 °C it's 90 A. That flat curve up to 50 °C buys you headroom in a warm enclosure — a packed panel that hits 50 °C still lets you run the full 100 A through this breaker. The 3VA1010-3ED32-0KC0 measures 70 mm deep by 76.2 mm wide by 130 mm tall, which is the standard 3-pole SENTRON 3VA1 frame width. The shunt trip (STL) and two auxiliary switches (HQ) are integrated; the auxiliary release order code is 3VA9688-0BL33 if you need a spare or a documented part number for the BOM.","metaTitle":"Siemens 3VA1010-3ED32-0KC0 SENTRON MCCB, 100 A, 75.6 kA","metaDescription":"Siemens 3VA1010-3ED32-0KC0 SENTRON molded case circuit breaker, 100 A rated continuous, 75.6 kA at 240 V. 3-pole, TM210 release, shunt trip, IP40 front. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":null,"categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"70 mm","Width":"76.2 mm","Height":"130 mm","at 240 V":"75.6 kA","at 415 V":"52.5 kA","at 440 V":"32 kA","at 690 V":"7.5 kA","at 40 °C":"100 A","at 45 °C":"100 A","at 50 °C":"100 A","at 55 °C":"96 A","at 60 °C":"94 A","at 65 °C":"92 A","at 70 °C":"90 A","Trip indicator":"No","Number of poles":"3","Product version":"Line protection","Voltage trigger":"Yes","lifecycle_stage":"current","Product brand name":"SENTRON","Product designation":"Molded case circuit breaker","Latching - endurance":"15 000","Undervoltage Release":"No","Communication Function":"No","Phase failure detection":"No","During Storage / Maximum":"80 °C","During Storage / Minimum":"-40 °C","Auxiliary contact version":"2 auxiliary switches HQ","During Operation / Maximum":"70 °C","During Operation / Minimum":"-25 °C","Other Measurement Function":"No","Rated continuous current Iu":"100 A","Rated insulation voltage Ui":"800 V","Design of the auxiliary release":"Shunt trip (STL)","Ground fault monitoring version":"Without","Of The Integrated Auxiliary Trip":"3VA9688-0BL33","Design of the overcurrent release":"TM210","Design of short-circuit protection":"For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter","Protection class IP / on the front":"IP40","Reference code / acc. to DIN EN 81346-2":"Q","Adjustable response value time / tr max.":"1","Adjustable response value time / tr min.":"1","Max. rated operational voltage Ue with DC":"500 V","Undervoltage Release With Leading Contact":"No","Product extension / optional / motor drive":"No","Adjustable response value current / Ir max.":"100 A","Adjustable response value current / li max.":"1 000 A","Adjustable response value current / li min.":"1 000 A","Adjustable response value current / lr min.":"100 A","Neutral conductors / upgradeable/retrofittable":"No","Number of CO contacts / for auxiliary contacts":"2","Protective function of the overcurrent release":"LI","Of The Integrated Auxiliary Switch/Alarm Switch":"3VA9988-0AA12","Switching capacity class of the circuit breaker":"N","Max. rated operational current of the frame size":"100 A","Max. rated operational voltage Ue with AC 50/60Hz":"690 V","Type of electrical connection / for main current circuit":"lug terminal","Arrangement of electrical connectors / for main current circuit":"Front terminal","Type of connectable conductor cross-section, connection screw, width x thickness , max.":"17 x 6.5","Type of connectable conductor cross-section, connection screw, width x thickness , min.":"12 x 0"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":null,"sourceUrl":"https://support.industry.siemens.com/webbackend/api/ProductSupport/TechnicalData?language=en&region=cn&productId=24585&mlfb=3VA1010-3ED32-0KC0","alternativesUrl":"https://aoctrl.com/api/mcp/products/3VA1010-3ED32-0KC0/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy 3VA1010-3ED32-0KC0?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time."},{"question":"What is the closest functional second-source to 3VA1010-3ED32-0KC0?","answer":"The 3VA1010-2ED32-0JA0 is the closest peer in the same SENTRON 3VA1 frame — same 3-pole, 100 A, TM210 release, and similar interrupting ratings. The main difference is the auxiliary contact count and the shunt trip configuration. Verify the auxiliary wiring scheme before dropping it into a panel specified around the -3ED32-0KC0."},{"question":"What are the key interrupting ratings for 3VA1010-3ED32-0KC0?","answer":"At 240 V it interrupts 75.6 kA; at 415 V it's 52.5 kA; at 440 V it's 32 kA; at 690 V it's 7.5 kA. The 690 V rating is the one to watch — if your fault current exceeds that, you need a different frame or a current-limiting upstream device."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/siemens/3VA1010-3ED32-0KC0","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/siemens/3VA1010-3ED32-0KC0 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}